Kieback&Peter MD15-FTL-HE User manual

Kieback&Peter GmbH & Co. KG
Tempelhofer Weg 50, 12347 Berlin/Germany
Telefon: +49 30 60095-0, Telefax: +49 30 60095-164
www.kieback-peter.de, [email protected]
Datasheet 3.09-20.315-01-EN
MD15-FTL-HE, MD15-FTL-OV
Issue 2017-01-09 Rev 1
A
Änderungen vorbehalten - Contents subject to change - Sous réserve de modifications - Reservado el derecho a modificación - Wijzigingen
voorbehouden - Con riserva di modifiche - Innehåll som skall ändras - Změny vyhrazeny - Zmiany zastrzeżone - Возможны изменения -
A változtatások jogát fenntartjuk - ؍⮉ᵚ㓿䙊⸕㘼᭩ࣘⲴᵳ࣋
Product Description
MD15-FTL-HE and MD15-FTL-OV wireless small actuator
For valves of the R10..20D/E/DV/EV series and valves from manufac-
turers such as Heimeier, Honeywell-MNG, Junkers,
Honeywell-Baukmann, Oventrop and Cazzaniga
Application
Small radio controlled, battery-powered actuator for room temperature control
For thermostat valve bodies for direct mounting on commercially available
radiator valves for room-specific temperature control in heating systems.
The actuator is radio controlled based on the non-proprietary EnOcean radio
protocol.
The following EnOcean Equipment Profile (EEP) is supported:
■EEP A5-20-01 Battery Powered Actuator
Content Page
Important Information Regarding Product Safety ..................................................................................................2
MD15-FTL-HE and MD15-FTL-OV wireless small actuator ..................................................................................3
Technical Data.....................................................................................................................................................3
Accessories (not included in delivery) .................................................................................................................4
Dimensions..........................................................................................................................................................4
Wireless small actuator operating modes..............................................................................................................5
Radio Interface ......................................................................................................................................................7
EnOcean Equipment Profiles EEP A5-20-01 (Battery Powered Actuator) ..........................................................8
R10..20D/E/DV/EV Two-Way Valves for MD15-FTL-HE Radio Small Actuator ..................................................10
Types.................................................................................................................................................................10
Technical Data - R10..20D/E/DV/EV Valves .....................................................................................................10
Mounting the Valve ..............................................................................................................................................12
Installing the wireless small actuator ...................................................................................................................13
Installing accessories Z800 to Z816 ....................................................................................................................15
Removing the Radio Small Actuator....................................................................................................................16
Commissioning ....................................................................................................................................................17
Teaching In the Radio Small Actuator on a Radio Partner ................................................................................19
Deleting the Radio Partner ................................................................................................................................19
Performing a Communication Test ....................................................................................................................20
Switching the Valve Block Protection Feature On and Off ................................................................................20
Switching the Energy Block Feature (Automatic “Window Open” Recognition) On and Off..............................21
Setting the Radio Communication Interval ........................................................................................................21
Replacing Batteries..............................................................................................................................................22

APage 2 / 22
Product DescriptionMD15-FTL-HE, MD15-FTL-OV
Datasheet 3.09-20.315-01-EN Issue 2017-01-09 Rev 1
Important Information Regarding Product Safety
Safety Instructions
This data sheet contains information on installing and commissioning the product "MD15-FTL-HE,
MD15-FTL-OV". Each person who carries out work on this product must have read and understood
this data sheet. If you have any questions that are not resolved by this data sheet, you can obtain
further information from the supplier or manufacturer.
If the product is not used in accordance with this data sheet, the protection provided will be impaired.
Applicable regulations must be observed when installing and using the device. Within the EU, these
include regulations regarding occupational safety and accident prevention as well as those from the
VDE (Association for Electrical, Electronic & Information Technologies). If the device is used in other
countries, it is the responsibility of the system installer or operator to comply with local regulations.
Mounting, installation and commissioning work on the devices may only be carried out by qualified
technicians. Qualified technicians are persons who are familiar with the described product and who
can assess given tasks and recognize possible dangers due to technical training, knowledge and
experience as well as knowledge of the appropriate regulations.
Legend
WARNING
Indicates a hazard of medium risk which can result in death or severe bodily injury if it is not avoided.
CAUTION
Indicates a hazard of low risk which can result in minor or medium bodily injury if it is not avoided.
!NOTICE
Indicates a hazard of medium risk which can result in material damage or malfunctions if it is not
avoided.
NOTE
Indicates additional information that can simplify the work with the product for you.
Notes on Disposal
For disposal, the product is considered waste from electrical and electronic equipment (electronic
waste) and must not be disposed of as household waste. Special treatment for specific components
may be legally binding or ecologically sensible. The local and currently applicable legislation must be
observed.

A
Page 3 / 22
Datasheet 3.09-20.315-01-EN
MD15-FTL-HE, MD15-FTL-OVProduct Description
Issue 2017-01-09 Rev 1
MD15-FTL-HE and MD15-FTL-OV wireless small actuator
Technical Data
■When used properly, this device complies with the requirements
of the R&TTE Directive (1999/5/EC).
MD15-FTL-HE Radio small actuator for valves with an M30x1.5 connec-
tion manufactured by Heimeier, Honeywell-MNG, Junk-
ers, Honeywell-Baukmann, Oventrop (1998 and later),
Cazzaniga, etc.
MD15-FTL-OV Radio small actuator for valves with an M30x1
connection manufactured by Oventrop (before 1998)
Nominal voltage Battery-operated, 3 alkaline AA batteries (LR6AD Panasonic Powerline
1.5 V)
Battery life Depends on the frequency and method of operation
- approx. 3 years with default settings
Measuring system Integrated digital temperature sensor; 0..40 °C; ±0.5 °C at 25 °C
Interfaces EnOcean® radio interface:
■Radio telegram: EnOcean radio telegram, bidirectional
■EEP A5-20-01 (Battery Powered Actuator)
■Frequency: 868.3 MHz
■Range: approx. 30 m in buildings (depending on building structure)
■Duty cycle: < 1 %
■Transmission/reception interval: every 2..20 min, can be set in 2 min incre-
ments
Motor switch-off Actuator spindle: when extending = load-dependent, when retracting =
path-dependent
Display Multicolored status LED
Actuating noise < 28 dB (A)
Nominal stroke Up to 3 mm
Travel time 10 s/mm
Positioning force 100 N (nominal)
Position indication Stroke range scale
Housing RAL 9010 pure white, battery compartment cover with mechanical locking
mechanism
Ambient temp. 0..50 °C
Degree of protection IP40
Installation position Anywhere from vertical to horizontal
Maintenance Maintenance-free
Weight 157 g (without batteries); 225 g (with batteries)

APage 4 / 22
Product DescriptionMD15-FTL-HE, MD15-FTL-OV
Datasheet 3.09-20.315-01-EN Issue 2017-01-09 Rev 1
Accessories (not included in delivery)
Adapters for radiator valves with MD15-FTL-HE radio small actuators
Dimensions
MD15-FTL-HE, MD15-FTL-OV
Z220 Protective battery cover for MD15-FTL-xx
VS3 Anti-vandalism protector for MD15-xx-HE
Item no. ID Type
Z800 9703-24 Danfoss series 2 - 20 x 1
Z801 9704-24 Danfoss series 3 - 23.5 x 1.5
Z802 - Danfoss RA2000
Z803 9800-24 Danfoss RAV
Z804 9700-24 Danfoss RAV-L
Z805 9700-27 Vaillant Ø 30 mm
Z806 9701-28 TA (M28 x 1.5)
Z807 9700-30 Herz (M28 x 1.5)
Z808 9700-55 Comap (M28 x 1.5)
Z809 9700-10 Oventrop (M30 x 1)
Z810 9700-33 Giacomini
Z811 9700-36 ISTA (M32 x 1)
Z812 9700-32 Rotex (M30 x 1)
Z814 9700-34 Uponor (Velta) valves
Z815 9701-34 Uponor (Velta) Provario
Z816 9700-41 Markaryd
85 47
71,5
62,5
91,5
M30x1,5 DIN 13 (MD15-FTL-HE)
M30x1 DIN 13 (MD15-FTL-OV)

A
Page 5 / 22
Datasheet 3.09-20.315-01-EN
MD15-FTL-HE, MD15-FTL-OVProduct Description
Issue 2017-01-09 Rev 1
Wireless small actuator operating modes
!NOTICE
All operating modes including self-controlled mode and frost protection function become available
after startup, i.e. after successful teach-in on a radio partner
Actuator mode
If a 0 to 100% EnOcean telegram is received from an external radio partner for controlling the radio
small actuator, the internal loop controller is not active.
The transmitted actuating signal is translated into a positioning movement.
A suitable radio single room controller takes over the control functions.
Self-controlling operation
The integrated room temperature controller is activated if no external 0 to 100%
EnOcean radio telegram is received.
- Without external operator panel (= emergency mode):
The temperature is controlled to a fixed setpoint of 20 °C using the integrated temperature sensor
(actual value) and the integrated control function of the actuator.
- With external operator panel (EnOcean technology):
Using the operator panel, the users can freely determine the setpoint or enter their own schedule.
The actual value and the setpoint are transmitted via an EnOcean telegram (EEP A5-20-01).
The integrated control algorithm makes room control easy and convenient.
Battery monitoring
The battery capacity is continuously monitored. If the battery capacity is too low, a radio signal is
transmitted to the radio partner and 2 acoustic signal tones are emitted in succession every 6 hours.
If this message is activated, the remaining capacity of the batteries is < 10%.
!NOTICE
The batteries must be replaced within the next 30 days.
As the battery level decreases, the interval between the audible signals becomes shorter and the
number of signal tones increases to 4 signal tones in succession every 3 hours.
If the remaining battery capacity is insufficient to maintain motorized operation, the actuator moves
into the safety position of 50%.
The radio communication with the radio partner still functions in this operating state.

APage 6 / 22
Product DescriptionMD15-FTL-HE, MD15-FTL-OV
Datasheet 3.09-20.315-01-EN Issue 2017-01-09 Rev 1
Valve recognition
During commissioning, the actuator detects the closing point and the total stroke of the valve.
After the batteries are changed or after the unit is successfully taught in on a radio partner, this
detection process is performed again via the Init.
Valve block protection
Block protection prevents the cone from jamming when the valve is inactive for a long time. When
block protection is active, the actuator performs a displacement of 50% once every 21 days.
If the remaining battery level is < 10% (see “Battery monitoring” section), this function is inactive.
This function can be switched on and off (see p. 20).
Automatic closing point control
The small actuator continuously monitors the closing point and corrects it if necessary.
Communication test
The radio communication path to the radio partner is checked.
Performing a communication test has no effect on the transmission/reception interval (see p. 20).
Energy block (automatic “Window open” recognition)
When a window is open, the flow of heat energy to the room is interrupted. An open window is
signified by a large and rapid temperature drop at the MD15-FTL-xx small actuator. If such a drop is
measured by the internal temperature sensor, the small actuator closes the valve for 30 min.
After 30 minutes, the small actuator returns to normal operation and the automatic “Window open”
recognition function is active again.
If the remaining battery level is < 10% (see “Battery monitoring” section), this function is inactive.
This function can be switched on and off (see p. 21).
Frost protection function
If the temperature at the integrated temperature sensor drops below 6 °C, the small actuator opens
the valve until 8 °C is reached.
Summer mode
If the status message “Summer mode on” is received from an external radio partner, the small
actuator closes the valve.
The transmission/reception interval in summer mode is permanently set to 60 minutes.

A
Page 7 / 22
Datasheet 3.09-20.315-01-EN
MD15-FTL-HE, MD15-FTL-OVProduct Description
Issue 2017-01-09 Rev 1
Radio Interface
The communication with the radio partner is cyclical, bidirectional and includes intelligent reception/
transmission management.
Upon the first reception of the radio telegram (for teaching-in a radio partner, see page 19), the radio
small actuator automatically adapts its operating mode according to the method of control from the
radio partner (actuator mode or self-controlled mode).
NOTE
If the communication with the radio partner is disrupted, the “emergency mode” status bit
(self-controlled mode) is set (can be evaluated for service diagnostics).
After the malfunction has been rectified (details can be found in the documentation of the radio
partner), the radio partner is automatically resynchronized.
!NOTICE
This product uses only EnOcean telegrams
When selecting a radio partner, ensure that the radio interface also works with the EnOcean telegram
EEP A5-20-01 (Battery Powered Actuator).

APage 8 / 22
Product DescriptionMD15-FTL-HE, MD15-FTL-OV
Datasheet 3.09-20.315-01-EN Issue 2017-01-09 Rev 1
EnOcean Equipment Profiles EEP A5-20-01 (Battery Powered Actuator)
DATA BYTES
Transmit mode: Message from the actuator to the controller
DB_3 Current Value value 0...100 %, linear n=0...100
DB_2.BIT_7 Service on
DB_2.BIT_6 Energy input enabled (not applicable)
DB_2.BIT_5 Energy Storage > xx% charged (not applicable)
DB_2.BIT_4 Battery capacity > 10%
DB_2.BIT_3 Contact, cover open
DB_2.BIT_2 Failure temperature sensor, out of range
DB_2.BIT_1 Detection, window open
DB_2.BIT_0 Actuator obstructed
DB_1 Temperature 0...40°C, linear n=0...255
DB_0.BIT_7 Not used
DB_0.BIT_6 Not used
DB_0.BIT_5 Not used
DB_0.BIT_4 Not used
DB_0.BIT_3 LRN Bit 0b0 Teach-in telegram
0b1 Data telegram
DB_0.BIT_2 Self-controlled mode 0b0 off
0b1 on
DB_0.BIT_1 Not used
DB_0.BIT_0 Not used
Receive mode: Commands from the controller to the actuator
rx time = max. 1s Note:
The data transfer from the radio partner to the radio small actuator must be
completely finished within a maximum time window of 1 s.
DB_3 Valve set point 0...100 %, linear n=0...100
Temperature set point 0...40°C, linear n= 0...255
DB_2 Temperature actual from RCU = 0b0, Room controller-unit …
DB_1.BIT_7 Run init sequence, only active in service mode
DB_1.BIT_6 Lift set, only active in service mode
DB_1.BIT_5 Valve open, only active in service mode
DB_1.BIT_4 Valve closed, only active in service mode
DB_1.BIT_3 Summer bit, reduction of energy consumption
DB_1.BIT_2 Set point selection DB_3 0b0 set point 0...100 %,
0b1 temperature set point 0...40°C
DB_1.BIT_1 Set point inverse
DB_1.BIT_0 Select function 0b0 RCU
0b1 service on

A
Page 9 / 22
Datasheet 3.09-20.315-01-EN
MD15-FTL-HE, MD15-FTL-OVProduct Description
Issue 2017-01-09 Rev 1
R10..20D/E/DV/EV Two-Way Valves for MD15-FTL-HE Radio Small Actuator
Types
PN10 gunmetal two-way valve for the small actuator (water up to 120 °C)
Technical Data - R10..20D/E/DV/EV Valves
Type DN PN Kvs R
Straight throughput R10D 10 10 1.25 3/8"
R15D 15 10 1.35 1/2"
R20D 20 10 2.5 3/4"
Right-angled throughput R10E 10 10 1.25 3/8"
R15E 15 10 1.35 1/2"
R20E 20 10 2.5 3/4"
Straight throughput R10DV 10 10 0.73 3/8"
with Kvs setting R15DV 15 10 0.73 1/2"
R20DV 20 10 0.73 3/4"
Right-angled throughput R10EV 10 10 0.73 3/8"
with Kvs setting R15EV 15 10 0.73 1/2"
R20EV 20 10 0.73 3/4"
Nominal diameter DN10 - 20
Pressure rating PN10
Connection Pipe screw connections in accordance with DIN EN 2115
Actuating stroke 2 mm
Temperature of
medium
Water up to 120 °C
Housing Gunmetal; nickel-plated
Cone EPDM
Valve spindle Stainless steel
Spindle seal EPDM
Maintenance Maintenance-free
R10..20D, R10..20DV R10..20E, R10..20EV

APage 10 / 22
Product DescriptionMD15-FTL-HE, MD15-FTL-OV
Datasheet 3.09-20.315-01-EN Issue 2017-01-09 Rev 1
Dimensions
Kvs default setting for R10 - 20DV/EV valves
To adjust to the heat requirement, the R10 - 20DV/EV valves have 8 flow settings for the radiator
mass flow rate.
The maximum flow rate, Kvs value (m³/h) can be selected by using the settings 1, 2, 3, 4, 5, 6, 7 or
8 (delivery setting = 8, corresponds to a Kvs value = 0.86).
The setting can be made using a Z29 socket key (accessory). The setting between 1 and 8 can be
read from the valve, and will be implemented by the installed small actuator.
Position 1 2 3 4 5 6 7 8
Kvs value 0,049 0,102 0,185 0,313 0,420 0,565 0,740 0,860
(1) Setting marks
(2) Z29 socket key (accessory)
1
2

A
Page 11 / 22
Datasheet 3.09-20.315-01-EN
MD15-FTL-HE, MD15-FTL-OVProduct Description
Issue 2017-01-09 Rev 1
Mounting the Valve
!NOTICE
The valve may only be installed by qualified technicians. In addition to the generally valid installation
guidelines, the following points are to be observed:
■The pipeline system and the interior of the fitting must be free of foreign objects. In the event of
contaminated media, dirt collectors are to be inserted upstream of the valves with fine screens,
mesh width 0.25 mm.
■There must be no tension between the valve and the pipeline connection.
■To avoid eddy formations in the valve body, the valve should be installed in a straight section of the
pipe. A distance of 10 times the nominal diameter is recommended between the valve flange and
manifold or other similar parts.
■The installation location is to be selected so that the ambient temperature at the actuator is kept
between 0 – +50 °C.
■When carrying out installation, the permissible maximum pressure difference p and the specified
direction of flow must be observed (see table in "Types" section).
■Once the valve is installed, make sure the ball in the valve seating can be moved easily by pushing
in the valve stem.
■Approximately 30 mm of free space is required above the actuator to install the actuator and
remove the housing cover.
■For safety reasons, do not suspend the small actuators from under the valve.
■Observe the direction of flow arrow on the valve body. Inverting the direction of flow impairs control
behavior.
M
M
M

APage 12 / 22
Product DescriptionMD15-FTL-HE, MD15-FTL-OV
Datasheet 3.09-20.315-01-EN Issue 2017-01-09 Rev 1
Installing the wireless small actuator
!NOTICE
Insert the batteries with the correct polarity.
When inserting the batteries, observe the polarity as marked in the battery compartment.
Use only alkaline batteries (type: AA, LR6 1.5 V).
NOTE
After changing the batteries, the radio small actuator goes into storage mode (actuator spindle is
retracted).
When the actuator receives a radio signal, it switches over to normal operation.
≤ 90°
> 30 mm

A
Page 13 / 22
Datasheet 3.09-20.315-01-EN
MD15-FTL-HE, MD15-FTL-OVProduct Description
Issue 2017-01-09 Rev 1
- MD15-FTL-HE, MD15-FTL-OV
►Open the battery compartment cover using the special key supplied by inserting it into the
intended place. Remove the cover.
The special key is included with delivery of the small actuator.
►Inserting the batteries and close the battery compartment cover.
►Place the small actuator on the threaded connection of the valve and tighten hand-tight using the
union nut.
123
+
+
–
4
567 8
9

APage 14 / 22
Product DescriptionMD15-FTL-HE, MD15-FTL-OV
Datasheet 3.09-20.315-01-EN Issue 2017-01-09 Rev 1
Installing accessories Z800 to Z816
Z802..Z805
Z800..Z801 and Z806..816
ID
1 2 3
2mm
4
5 6 7 8
ID
1 2 3 4
5 6 7

A
Page 15 / 22
Datasheet 3.09-20.315-01-EN
MD15-FTL-HE, MD15-FTL-OVProduct Description
Issue 2017-01-09 Rev 1
Removing the Radio Small Actuator
CAUTION
Before beginning to remove the unit, make sure that no differential pressure builds up in the valve
body before beginning work. If necessary, close the gate valve and turn off pumps.
After the pipeline has cooled off, you can begin removal of the small actuator.
- MD15-FTL-HE, MD15-FTL-OV
►Open the battery compartment cover using the special key supplied by inserting it into the
intended place. Remove the cover.
The special key is included with delivery of the small actuator.
►Remove the battery.
►Loosen the union nut.
►Remove the small actuator from the valve.
1 2 3 4
5 6

APage 16 / 22
Product DescriptionMD15-FTL-HE, MD15-FTL-OV
Datasheet 3.09-20.315-01-EN Issue 2017-01-09 Rev 1
Commissioning
- Overview of functions

A
Page 17 / 22
Datasheet 3.09-20.315-01-EN
MD15-FTL-HE, MD15-FTL-OVProduct Description
Issue 2017-01-09 Rev 1
!NOTICE
This product description describes specific settings and functions of the MD15-FTL-xx. In addition to
these instructions, the product descriptions of other system components, such as radio partners, are
to be observed.
■The buttons and LED displays that are used during commissioning are located inside the housing.
■Remove the housing cover before commissioning (Figures 1 and 2).
(1) Status LED
(2) Push-button
1234
5678
12

APage 18 / 22
Product DescriptionMD15-FTL-HE, MD15-FTL-OV
Datasheet 3.09-20.315-01-EN Issue 2017-01-09 Rev 1
Teaching In the Radio Small Actuator on a Radio Partner
►Set the radio partner to teach-in standby mode (Figure 3, page 17). Details are described in the
documentation of the radio partner.
►To trigger a teach-in telegram on the MD15-FTL-xx, press the push-button (2) on the
MD15-FTL-xx until a signal tone is heard and the status LED (1) lights up green (Figure 4, page
17).
►Release the push-button (2).
The teach-in process is started.
The radio partner confirms that the teach-in process was successful. Details are described in
the documentation of the radio partner.
The radio small actuator confirms that the teach-in process was successful both visually
(status LED flashes green 2 times) and acoustically (2 signal tones in succession).
An initialization run is automatically carried out.
►Close the housing of the MD15-FTL-xx by snapping on the housing cover (Figure 7, page 17).
NOTE
After the teach-in procedure has been successfully completed, the device ID of the radio partner is
permanently stored in the radio small actuator. You do not need to perform the teach-in procedure
again if you change the batteries.
NOTE
If the teach-in process was not successful, this is indicated visually (status LED flashes red for
approx. 1 s) and acoustically (downward sequence of tones).
Start the teach-in process again.
Deleting the Radio Partner
It is not possible to delete the device ID of the radio partner which is saved internally on the
MD15-FTL-xx. This ID is overwritten by the new radio ID when a new teach-in process is performed.

A
Page 19 / 22
Datasheet 3.09-20.315-01-EN
MD15-FTL-HE, MD15-FTL-OVProduct Description
Issue 2017-01-09 Rev 1
Performing a Communication Test
►Press the push-button (2) and hold it until you hear 2 successive signal tones and the status LED
flashes green 2 times.
►Release the push-button.
After the push-button (2) is released, the radio communication path to the radio partner is checked.
A successful communication test is indicated both visually (status LED flashes green 2 times) and
acoustically (2 signal tones in succession).
NOTE
A successful communication test may require an adjustment of the current valve position.
If the communication test was not successful, this is indicated visually (status LED flashes red for
approx. 1 s) and acoustically (downward sequence of tones).
The radio small actuator switches to emergency mode.
NOTE
In case of an unsuccessful communication test, check the radio partner and the transmission path.
NOTE
If the communication with the radio partner is interrupted for longer than 1 h, the radio small actuator
switches to emergency mode (see page 5) and the “emergency mode” status bit (self-controlled
mode) is activated.
When a correct telegram is received, the radio small actuator automatically returns to normal
operation.
Switching the Valve Block Protection Feature On and Off
►Press the push-button (2) and hold it until you hear 3 successive signal tones and the status LED
flashes green 3 times.
►Release the push-button.
After the push-button (2) is released, the current status (on or off) is indicated visually and acousti-
cally.
■Valve block protection feature on:
Status LED flashes green 2 times and 2 signal tones are emitted
■Valve block protection feature off:
Status LED flashes red for approx. 1 s and a long signal tone is emitted
►To change the status, you must again press and release the push-button (2) within the next 5 s.
The new function setting, either “valve block protection feature on” or “valve block protection
feature off,” is indicated visually and acoustically as described above.
Factory setting:On

APage 20 / 22
Product DescriptionMD15-FTL-HE, MD15-FTL-OV
Datasheet 3.09-20.315-01-EN Issue 2017-01-09 Rev 1
Switching the Energy Block Feature (Automatic “Window Open” Recognition) On and Off
►Press the push-button (2) and hold it until you hear 4 successive signal tones and the status LED
flashes green 4 times.
►Release the push-button.
After the push-button (2) is released, the current status (on or off) is indicated visually and acousti-
cally.
■Energy block feature on:
Status LED flashes green 2 times and 2 signal tones are emitted
■Energy block feature off:
Status LED flashes red for approx. 1 s and a long signal tone is emitted
►To change the status, you must again press and release the push-button (2) within the next 5 s.
The new function setting, either “energy block feature on” or “energy block feature off,” is
indicated visually and acoustically as described above.
Factory setting:On
Setting the Radio Communication Interval
The transmission or reception interval can be set in increments of two minutes.
►Press the push-button (2) and hold it until you hear 5 successive signal tones and the status LED
flashes green 4 times and orange 1 time.
►Release the push-button (2).
The new radio communication interval is acknowledged again both visually and acoustically;, siehe
Tabelle 1.1. "Radio communication interval".
►To change the radio communication interval, you must press the push-button (2) again within
thenext 5 s and release it once the desired radio communication interval is reached.
This is indicated visually and acoustically, siehe Tabelle 1.1. "Radio communication interval".
►Release the push-button (2).
The new radio communication interval is acknowledged again both visually and acoustically;
see Table 1.1 "Radio communication interval".
Default setting: Transmission and reception interval: 10 min
Tab. 1: Radio communication interval
NOTE
If you press and hold the push-button (2) until 6 successive signal tones are heard and the status LED
flashes 6 times, the status LED lights up red and a long signal tone (approx. 1 s) is emitted to indicate
the end of the setting procedure.
Radio com-
munication
interval
Signal
2 min Status LED flashes 1 time and 1 signal tone is emitted
4 min Status LED flashes 2 times and 2 signal tones are emitted
::
20 min Status LED flashes 10 times and 10 signal tones are emitted
This manual suits for next models
1
Table of contents
Other Kieback&Peter Controllers manuals

Kieback&Peter
Kieback&Peter MD15-FTL-315 User manual

Kieback&Peter
Kieback&Peter DDC4200e User manual

Kieback&Peter
Kieback&Peter MD15-FTL-902 User manual

Kieback&Peter
Kieback&Peter MD15/230-HR Technical specifications

Kieback&Peter
Kieback&Peter DDC4400e Technical specifications

Kieback&Peter
Kieback&Peter FBR5 User manual

Kieback&Peter
Kieback&Peter MD15-HR User manual

Kieback&Peter
Kieback&Peter MD15/230 Technical specifications

Kieback&Peter
Kieback&Peter BMR410 Technical specifications

Kieback&Peter
Kieback&Peter MD15-R-HE Technical specifications