Kieback&Peter BMR410 Technical specifications

Kieback&Peter GmbH & Co. KG
Tempelhofer Weg 50, 12347 Berlin/Germany
Telefon: +49 30 60095-0, Telefax: +49 30 60095-164
www.kieback-peter.de, info@kieback-peter.com
Datasheet 2.70-10.411-01-EN
BMR410
Issue 2011-04-27
A
Änderungen vorbehalten - Contents subject to change - Sous réserve de modifications - Reservado el derecho a modificación - Wijzigingen
voorbehouden - Con riserva di modifiche - Innehåll som skall ändras - Změny vyhrazeny - Zmiany zastrzeżone - Возможны изменения -
A változtatások jogát fenntartjuk - 保留未经通知而改动的权力
Product Description
BMR410 Controller
Application
The BMR410 is a DDC controller for regulating,
controlling, monitoring and optimizing heating, ventilation
and air conditioning systems.
The BMR410 also has a fieldbus to allow for flexible
enhancement with input and output modules, as well as
with room control modules.
With an integrated Ethernet interface, the BMR410 has a
built in web server to facilitate visualization, remote
control and data backup over a web browser without the
need of any additional software.
Parameterization can be carried out using the BMRTool, the SI Tool or the PS4000.
Additional main features of the BMR410:
■Native BACnet® in accordance with DIN EN ISO 16484-5 (BACnet® server functionality);
facilitates communication with the BMS by Ethernet or modem.
■The BMRTool allows you to configure the controller quickly and easily. Plant macros are set to configure the
BMR410 completely, set the associated BMR software objects, configure the parameters and assign the input
and output signals.
■Simple turn-knob operation with illuminated display
■Weekly schedule and annual schedule
■Trend data can be saves and visualized
■Code keys for quick display and adjustment of plant values at different access levels;
customer-specific plaintext for every parameter
■Can be operated in 12 languages (Czech, Dutch, English, French, German, Hungarian, Italian, Latvian, Polish,
Russian, Spanish and Swedish)
■3 closed-loop control circuits for heating or 2 for ventilation, which can be extended by hardware and software
objects
■Malfunction message logging with time and date
Content Page
Important Information Regarding Product Safety ..................................................................................................2
Item........................................................................................................................................................................3
Technical Data.....................................................................................................................................................3
Accessories (not included in delivery) .................................................................................................................4
Dimensions..........................................................................................................................................................5
Connectable fieldbus modules.............................................................................................................................6
Connection...........................................................................................................................................................6
Fieldbus Power Supply ........................................................................................................................................8
Installation..............................................................................................................................................................9
Opening the Housing ...........................................................................................................................................9
Removal...............................................................................................................................................................10

APage 2 / 10
Product DescriptionBMR410
Datasheet 2.70-10.411-01-EN Issue 2011-04-27
Important Information Regarding Product Safety
Safety Instructions
This data sheet contains information on installing and commissioning the product "BMR410". Each
person who carries out work on this product must have read and understood this data sheet. If you
have any questions that are not resolved by this data sheet, you can obtain further information from
the supplier or manufacturer.
If the product is not used in accordance with this data sheet, the protection provided will be impaired.
Applicable regulations must be observed when installing and using the device. Within the EU, these
include regulations regarding occupational safety and accident prevention as well as those from the
VDE (Association for Electrical, Electronic & Information Technologies). If the device is used in other
countries, it is the responsibility of the system installer or operator to comply with local regulations.
Mounting, installation and commissioning work on the devices may only be carried out by qualified
technicians. Qualified technicians are persons who are familiar with the described product and who
can assess given tasks and recognize possible dangers due to technical training, knowledge and
experience as well as knowledge of the appropriate regulations.
Legend
WARNING
Indicates a hazard of medium risk which can result in death or severe bodily injury if it is not avoided.
CAUTION
Indicates a hazard of low risk which can result in minor or medium bodily injury if it is not avoided.
!NOTICE
Indicates a hazard of medium risk which can result in material damage or malfunctions if it is not
avoided.
NOTE
Indicates additional information that can simplify the work with the product for you.
Notes on Disposal
For disposal, the product is considered waste from electrical and electronic equipment (electronic
waste) and must not be disposed of as household waste. Special treatment for specific components
may be legally binding or ecologically sensible. The local and currently applicable legislation must be
observed.

A
Page 3 / 10
Datasheet 2.70-10.411-01-EN
BMR410Product Description
Issue 2011-04-27
Item
Technical Data
BMR410 DDC controller with operating function and integrated Web server for
remote control
Nominal voltage AC 110 V to 230 V AC ± 10%; 50 Hz to 60 Hz; 10 VA
Fuse Fuse S1 630 mA (T) on the mains side
Inputs and outputs 5 binary outputs Voltage-free relay contact max. 5 (3) A; AC
250 V
2 binary inputs Also for pulse counting up to 80 Hz
8 universal inputs/outputs that can be independently configured as:
- Binary output
- Binary input
- Analog output
Transistor outputs DC 24 V, max. 40 mA
Contact input (voltage-free)
DC 0 V to 10 V; max. 2.5 mA
- Analog input See table "Sensor Types", page 4.
Ports Ethernet RJ45 Data backup; WEB server communication;
BACnet® in accordance with DIN EN ISO
16484-5
Cascade plug For connecting a BMF400 input/output module
CAN Fieldbus DC 12 V; 6 W (module power supply);
2,000 m; 20 kBd
RS232 Modem connection for fax, SMS and BMS with
BACnet® in accordance with DIN EN ISO
16484-5
Displays Backlit graphic display, LED for error message and bus operation
Operation Knob with confirmation key [SET] and backspace key [ESC]
Additional keys: Info, alarm query, freely programmable key
RAM 8 MB dyn. RAM; 512 kB stat. RAM, 8 MB flash
Mains failure backup Buffered by lithium battery; up to 1 year mains failure; recommended
maintenance interval: 5 years
■Project planning
■Data
■Time
Degree of protection IP20 (when installed)
Ambient temperature 0 °C to 45 °C
Ambient humidity During operation: 20% to 80% r.h., non-condensing;
Out of operation: 5% to 90% r.h., non-condensing
Mounting Standard rail EN 50022 in closed housing
This device is intended for installation in a wall-mounted enclosure/switch
cabinet having protection class II.
Dimensions WxHxD mm 143.5 x 90 x 67
Weight 0.38 kg

APage 4 / 10
Product DescriptionBMR410
Datasheet 2.70-10.411-01-EN Issue 2011-04-27
Sensor Types
Accessories (not included in delivery)
Sensor Type Value Range
0 to 10 V 0 to 100%
KP10 -50 to 150°C
KP250 -50 to 150°C
PT100 -50 to 350°C
PT1000 -50 to 350°C
Ni100 -50 to 150°C
Ni1000 (DIN) -50 to 150°C
Ni1000 (L&G) -50 to 150°C
ML2 -50 to 150°C
BMRTool Configuration tool for BMR
Z179 Cascade plug
■Replacement for power supply and bus
cables
■Connection with cascade plug on the BMR:
one BMF
A386KD Lithium battery with increased temperature stability
TPC35 Remote display and operator panel with 3.5" /
8.9 cm screen
■Remote control of up to 3 BMRs
TPC56 Remote display and operator panel with 5.6" /
14.2 cm screen
■Remote control of up to 99 BMRs
HW-103455 Mounting frame for BMR
■Installation space: one row, 216 mm
(12HP);1BMRand1FBU,forexample

A
Page 5 / 10
Datasheet 2.70-10.411-01-EN
BMR410Product Description
Issue 2011-04-27
Dimensions
Z180 Housing for wall mounting
■Installation space: one row, 324 mm
(18HP);1BMR,2FBUsand2HPfree
Z68 Adapter frame for installing a BMR in the
switch cabinet door
■Installation space: one row, 144 mm (8 HP);
1 BMR, for example
Z63 Adapter frame for BMR/modules
■Format: 19"
■Installation space: one row, 288 mm
(16 HP); 1 BMR and 2 FBU, for example
Z62 Adapter frame for TPC35
■Format: 19"
■Front cutout: fits TPC35
■Rear standard rail: one row, 414 mm wide
(23HP),1BMR,3FBUsand3HPfree,for
example
■Z62 with BMR and TPC35 can be used as a
replacement for MRP with SP in a KA frame.
44,7
0,
0
9
60,0
143,5

APage 6 / 10
Product DescriptionBMR410
Datasheet 2.70-10.411-01-EN Issue 2011-04-27
Connectable fieldbus modules
Up to 3 Input/output modules and up to 3 additional Room control modules can be connected to the
BMR410.
Input/output modules
■FBU410
■FBM(0)18
■FBM(0)24
■BMF400 (maximum 1 can be installed on the BMR410 using the cascade connection)
■FBS51/04 (maximum 1 can be installed on the BMR410)
Room control modules
■DDC110-3
■DDC110S
■DDC110-3S1
■DDC110-4
Connection
1 DC 12 V for fieldbus power supply
2 Z179 cascade plug for power supply and communication with the BMF
3
26
5
487
BMR410
21
20
19 28
27
24
23
22 25 31
30
29 34
33
32 36
35
26
P11 P12 P13
Y GND
P8
P7
B GND
P6
P5
5(3)A 5(3)A
5(3)A
RJ45
L1 N
K GND
P10
K GND
P9
+-
0V
+-
GND
CAN RS485
13 16
15
14 18
17
P1 P2
B GND
Y GND
P3 P4
12
11
P15
10
9
9
P14
1
12VDC
0V
*2)
*1)
NC
+++
+
+++
+
5(3)A 5(3)A
37 38 39
GND
RS232
Rx
Tx
Z179
230V~
110..230V~

A
Page 7 / 10
Datasheet 2.70-10.411-01-EN
BMR410Product Description
Issue 2011-04-27
Sensor and actuator connection
Fieldbus connection
Fieldbus
When connecting the fieldbus, use a cable of at least type JY(St)Y 2x2x0.8 Lg: two x two wires,
twisted to a pair with plastic insulation and an electrostatic shield with a wire diameter of at least
0.8 mm. Use a stranded pair of wires for the data lines (+ and -) and another free wire for the ground
connection (0).
At the end of the fieldbus (furthest point from the DDC controller), install a terminating resistor of
about 180 ohms between both data lines (+ and -). The terminating resistor is included with the DDC
controller.
The maximum cable length for the Fieldbus is 2000 m.
!NOTICE
Deviating GND wiring may lead to errors in measurement.
P1..P8
18
36
24VAC
24V
0V
24V
0V Y
P1..P8
18
36
24VAC
24V
0V
24V
0V b
0..10V DC
30
24VDC
24V
0V
3330
P1..P8
28
P1..P8
15
P1..P8
28
KP10
KP250
Y
GND
Y
GND
K
GND
K
GND
B
GND
33
P1..P8
15
B
GND
ϑ
BMR410
21
20
19 22
+-
0V
12VDC
19
18
17 20
FBM(0)18
FBM(0)24
FBU410
BMR410
21
20 22
+-
0V
21
20 22
FBS51/04

APage 8 / 10
Product DescriptionBMR410
Datasheet 2.70-10.411-01-EN Issue 2011-04-27
Fieldbus Power Supply
In the simplest case, the fieldbus module can be supplied with power from the BMR410.
When JY(St)Y 2x2x0.8 Lg bus cables are used, the following maximum fieldbus lengths are possible:
Tab. 1: Maximum fieldbus length per power supply
By installing additional power supplies, you can use a fieldbus length of up to 2000 m.
■Fieldbus Power Supply: DC 12 V; 6 W
NOTE
The BMF does not require any additional power supplies as it is supplied over the cascade plug and
not from the fieldbus.
NOTE
FBS modules always need to be supplied with external power as they require an AC 24 V power
supply (the power supply for the fieldbus is DC 12 V). Therefore, the fieldbus length is not limited for
FBS modules.
FBU and FBM modules DDC110 modules Maximum fieldbus length
3 0 to 3 20 m
2 0 to 3 40 m
1 0 to 3 80 m
0 0 to 3 160 m
0 to 3 < 2 m 0 to 3 160 m

A
Page 9 / 10
Datasheet 2.70-10.411-01-EN
BMR410Product Description
Issue 2011-04-27
Installation
WARNING
Danger of death by electrocution
Mount or remove only when power is switched off.
Opening the Housing
When mounting or connecting the fieldbus module, it may be necessary to open the housing of the
BMR410.
WARNING
Danger of death by electrocution
Open the housing only when power is switched off.
1 2 3 4
1 2 3

APage 10 / 10
Product DescriptionBMR410
Datasheet 2.70-10.411-01-EN Issue 2011-04-27
Removal
WARNING
Danger of death by electrocution
Mount or remove only when power is switched off.
1 2 3 4
5 6
Table of contents
Other Kieback&Peter Controllers manuals

Kieback&Peter
Kieback&Peter DDC4200e User manual

Kieback&Peter
Kieback&Peter DDC4400e Technical specifications

Kieback&Peter
Kieback&Peter MD15-FTL-902 User manual

Kieback&Peter
Kieback&Peter FBR5 User manual

Kieback&Peter
Kieback&Peter MD15-HR User manual

Kieback&Peter
Kieback&Peter MD15/230 Technical specifications

Kieback&Peter
Kieback&Peter MD15/230-HR Technical specifications

Kieback&Peter
Kieback&Peter MD15-R-HE Technical specifications

Kieback&Peter
Kieback&Peter MD15-FTL-HE User manual

Kieback&Peter
Kieback&Peter MD15-FTL-315 User manual