King-Gage 5800 Series User manual

Quick Start Guide
"Intelligent" Pressure and Level Transmitters
SERIES 5800
8019 Ohio River Blvd, PO Box 305
Newell WV, 26050 U.S.A.
Phone: (304) 387-1200 FAX: (304) 367-4417 www.king-gage.com
1-(800)-573-4243
www.ksecorp.com

Quick Start Guide Series 5800
EX-1861-10 Page 2of 7
TABLE OF CONTENTS
Page
1. DISPLAY AND PUSH BUTTONS.......................................................................................................3
1.1 DISPLAY READOUT
1.2 SUMMARY PROGRAMMING POINTS
2. EXPLANATION PROGRAMMING POINTS.....................................................................................4-7
2.1 ZERO ADJUSTMENT (ZERO)
2.2 SPAN ADJUSTMENT (SPAN)
2.3 CANCEL MOUNTING POSITION EFFECT
2.4 DISPLAY SETTING OF UNITS
2.5 OUTPUT SELECTION 4-20 mA or 20-4 mA
2.6 DAMPING ADJUSTMENT
2.7 TEMPERATURE UNITS
2.8 DEVICE SETUP
2.9 READOUT
2.10 BURST MODE (HART®)
2.11 INFORMATION

Quick Start Guide Series 5800
EX-1861-10 Page 3of 7
1. DISPLAY AND PUSH BUTTONS
The Series 5800 has a high contrast display for optimal readout. The menu is controlled by three
buttons. Navigate with the up and down arrows through the menus and adjust measuring values. Enter
a menu and confirm selections with the menu button.
Push the up button to browse through various menus and adjust values.
Push the down button to browse through various menus and adjust values.
Push the menu button to enter menus or confirm a selection.
Display Series 5800
1.1 DISPLAY READOUT
When the transmitter is powered, a startup screen with the software version and the pressure range
appears for a few seconds. After the startup screen the transmitter will automatically continue to the
main screen with the actual measurement reading.
1.2 SUMMARY PROGRAMMING POINTS
PROGRAM POINT
NAME
FUNCTION
P100
Menu-Exit menu
Start and exit
P101
ZERO value
Zero adjustment (ZERO 4 mA) with or without test pressure
P102
SPAN value
Span adjustment (SPAN 20 mA) with or without test pressure
P103
MOUNT correction
Cancel mounting position effect
P104
UNITS
Selection of engineering units
P105
REVERSE mA
Output selection: 4-20 mA or 20-4 mA
P106
DAMPING
Adjustable damping: 0.00 till 25.00 seconds
P107
TEMP UNITS
Temperature unit selection: Celsius or Fahrenheit
P108
DEVICE SETUP
Configuration: Protection, HART, Display mode, Display update
P109
READOUT
Readout options on display: Current, Unit, percentage and temperature
P110
BURST MODE
Continuously broadcast a standard HART reply message

Quick Start Guide Series 5800
EX-1861-10 Page 4of 7
2. EXPLANATION OF PROGRAMMING POINTS
2.1 ZERO ADJUSTMENT (ZERO)
The transmitter is set to 0 PSI at atmospheric pressure.
The ZERO can be adjusted to a lower or higher point.
Example: Increase ZERO to 2 PSI
1. The measuring unit of the transmitter is set to PSI. If not, this can be selected by choosing the
right measuring unit in program point P104.
2. Navigate to program point P101, and push the button to enter the menu.
3. The actual measured value appears on the display.
4. Increase this value with the arrow button to 2 PSI, and push and hold the button until
“Saved” appear on the display.
5. The transmitter will return to the home screen. The measurement value at atmospheric pressure is
now -2 PSI. At an applied pressure of 2 PSI the transmitter will display 0 PSI.
The transmitter can be adjusted to zero in a real process situation. The transmitter will measure the
pressure in an actual process. This measurement will be used as the zero value (4 mA).
1. Go to the home screen, the transmitter will display the actual measured value.
2. Push and hold the button until the actual measured zero and the message “ZERO PUSHED”appear.
3. The transmitter will return to home screen.
2.2 SPAN ADJUSTMENT (SPAN)
This setting can be used to adjust the range (SPAN) according to an entered value or
adjusted with or without an applied pressure. The maximum pressure which can be
measured: The measurement at ZERO (P101) + the entered value SPAN (P102). If the
ZERO (P101) is increased, the maximum measured value will automatically be set higher
at same rate as the zero. This will be explained step by step through an example.
Example: Measurement range 0 –29 PSI.
1. The span must be set at 29 PSI
2. Navigate to program point P102, and push the button to enter the menu.
3. Adjust the SPAN with the push buttons to 29 PSI and push and hold the button until “Saved”
appears on the display.
4. The transmitter will return to the home screen.
The span can also be adjusted to a real process situation. The transmitter will measure the pressure in
an actual process. This measurement will be used as the span value (20 mA).
1. Go to the home screen, the transmitter will display the actual measured value.
2. Push and hold the button until the actual measured span and the message “SPAN PUSHED”appear on
the display.
3. The transmitter will return to home screen.
P102 is the adjustment of the total span.
When a compound range is desired (for example, -2 till +29 PSI), a span of 31 PSI must be programmed.
The Zero (P101) must be set at -2 PSI. The transmitter is set to –2 PSI = Zero and 29 PSI = Span.
If the process temperature at -14.5 PSI is above 20 °C another filling oil must be applied inside the transmitter.
If the process temperature at -7.3 PSI is above 60 °C another filling oil must be applied inside the transmitter.

Quick Start Guide Series 5800
EX-1861-10 Page 5of 7
2.3 CANCEL MOUNTING POSITION EFFECT
The transmitter might exhibit a small "mounting position" effect at the zero. In other
words, the pressure value displayed could vary depending on how the transmitter is
oriented when installed.
1. Navigate to program point P103, and push the button to enter the menu.
2. Two choices appear on the screen: Set and Reset.
Choosing Set will adjust the zero to 0.000 PSI in the mounting position when applicable.
Select Set, and push the button to confirm.
The corrected value is shown on the display.
Push the button to save.
Choosing Reset will put the transmitter back to factory default.
Select Reset, and push the button to confirm the reset back to factory default.
The transmitter will return to the home screen.
Do not apply pressure when executing "Cancel mounting position effect"
2.4 DISPLAY SETTING OF UNITS
Various engineering units can be displayed on the display.
Factory setting = PSI
1. Navigate to program point P104, and push the button to enter the menu.
2. Several engineering units can be selected. Each selected engineering unit is automatically
converted to the correct value of the corresponding unit.
3. Navigate through this menu and choose the required unit, push the button confirm.
4. The transmitter will return to the home screen. The measured reading will be displayed in the
selected unit on the home screen.
The selected pressure unit is only visible on the display when UNITS is chosen in program point P109.
2.5 OUTPUT SELECTION 4-20 mA or 20-4 mA
Factory setting = 4 - 20 mA
1. Navigate to program point P105, and push the button to enter the menu.
2. Two choices appear on the screen: 4-20 and 20-4
3. Make an output choice and push the button to confirm.
4. The transmitter will return to the home screen.
2.6 DAMPING ADJUSTMENT
The transmitter has an adjustable damping between 0.00 to 25.00 seconds.
Factory setting = 0.00 seconds
1. Navigate to program point P106, and push the button to enter the menu.
2. Two choices appear on the screen: Set and Reset
Choosing Set allows a value to be set between 0.00 and 25.00 seconds.
Select Set, and push the button to confirm.
Adjust the damping with the buttons and push the button to confirm.
The transmitter will return to the home screen.
Choosing Reset will put the transmitter back to factory default (0.00 seconds)

Quick Start Guide Series 5800
EX-1861-10 Page 6of 7
Select Reset, and push the button to confirm the reset back to factory default.
The transmitter will return to the home screen.
2.7 TEMPERATURE UNITS
In this menu the preferred temperature unit can be selected.
1. Navigate to program point P107, and push the button to enter the menu.
2. Two choices appear on the screen: Celsius and Fahrenheit.
3. Make a choice and push the button to confirm.
4. The transmitter will return to the home screen.
2.8 DEVICE SETUP
In this menu, several operational settings can be made for the transmitter and the display.
1. Navigate to program point P108, and push the button to enter the menu.
2. Five choices appear on the screen:
LocProtect : The transmitter can be protected against local adjustments
ComProtect : The transmitter can be protected against adjustments with HART.
HART : Option for HART® 5 and HART® 7 communication.
DispMode : Option for turning the display on or off.
Disp.Upd.: Option to adjust the refresh rate of the measured value on the display between 0.0 to 5.0
seconds. For example when this value is set to 2.0 seconds, the measured value on the display will be
refreshed every 2 seconds.
Select Set, and push the button to confirm.
Adjust the setting with the buttons and confirm with the button.
The transmitter will return to the home screen.
Choosing Reset will put the transmitter back to factory default (0.0 seconds).
2.9 READOUT
In this menu, the type of readout on the display can be adjusted.
Factory Setting = Unit
1. Navigate to program point P109, and push the button to enter the menu.
2. Four choices appear on the screen:
Current : Current value (4 - 20 mA)
Unit : Pressure unit (Selected in P104)
Percentage : 0 - 100%
Temperature : Actual process temperature (°C or °F)
3. Navigate to the desired choice, confirm by pushing the button.
4. The transmitter will return to the home screen.
2.10 BURST MODE (HART®)
The transmitter (only when HART® is present) can be configured for Burst mode. This will
enable continuous broadcasting of standard HART® reply messages.
1. Navigate to program point P110, and push the button to enter the menu.
2. Five choices appear on the screen: Mode Cntrl, Cmd number, Message, Period and Trigger

Quick Start Guide Series 5800
EX-1861-10 Page 7of 7
3. Select Mode Cntrl, and push to confirm.
4. Two choices appear on the screen: “On” and “Off”
Choose On to turn on burst mode.
Choose Off to turn off burst mode.
5. Select Message to select the burst message 0,1,2 or 3 and push the button to confirm.
6. Select Cmd number, and push the button to confirm.
Five choices appear on the screen:
Cmd 01 = PRIMARY VARIABLE
Cmd 02 = CURRENT AND PERCENT OF RANGE
Cmd 03 = DYNAMIC VARIABLES AND CURRENT
Cmd 09 = DEVICE VARIABLES WITH STATUS
Cmd 48 = ADDITIONAL TRANSMITTER STATUS
Choose the preferable burst mode, and push button to confirm.
7. Select Period, and push the button to confirm.
Two choices appear on the screen: “Max Time” and “Min Time”
Select Max Time to set the maximum amount of time the message will be sent. This
value can be set from 0.5 to 3600 seconds.
Select Min Time to set the minimum amount of time the message will be sent. This
value can be set from 0.5 to 3600 seconds.
Enter the preferred value, and push the button to confirm.
8. Select Trigger, and push the button to confirm.
9. Five choices appear on the screen:
Continuous = The Burst message is sent continuously.
Windowed = The Burst message is triggered when the measured value
deviates more than the specified trigger value.
Rising = The Burst message is triggered when the measured value rises above
the triggered value.
Falling = The Burst message is triggered when the measured value falls below
the triggered value.
On-Change = The Burst message is triggered when the measured value changes at all.
Choose the desired burst mode, and set the preferred parameters.
2.11 INFORMATION
This menu summarizes information about the configuration of the transmitter.
V No: Software Version Number Tunit: Temperature unit (C or F)
No: Serial number of the transmitter Tph: Highest measured process temperature
Z: Zero adjustment Tpl: Lowest measured process temperature
S: Span adjustment Tah: Highest measured ambient temperature
Da: Out delay on display Tal: Lowest measured ambient temperature
O: Output (4-20mA or 20-4 mA) Tc no: Tag number
Lpro: Local protection (on/off)
1-(800)-573-4243
www.ksecorp.com
Table of contents
Other King-Gage Transmitter manuals
Popular Transmitter manuals by other brands

Christie
Christie Terra user manual

DSE
DSE RE-HDMI-RG owner's manual

Satson
Satson HDM-IP-001C user manual

BAPI
BAPI Wireless Room Temperature and Humidity... Installation and operating instructions

NAPCO
NAPCO GEM-TRANSLP installation instructions

Jerguson
Jerguson MTII4200 Series Installation, operation & maintenance instructions