KIOUR TOUCH RSD2 Instruction Manual

TEMPERATURE CONTROLLER TOUCH LINE Model RSD2
DESCRIPTION
RSD2 is a temperature controller for refrigerator rooms using touch technology for the keyboard. Through a PTC sensor controls room’s temperatures in range -50÷+150°C
(-58÷+302°F). In scale -19.9÷+99.9°C there is a decimal analysis with accuracy ±0.1°C. It has two relays (compressor, fan). It has also defrost control and a buzzer activation
due to an alarm. The controller has a serial input and can connect to the KIOUR CAMIN modbus network for full monitoring and data logging of the device.
At the startup of the device, the temperature controller performs a self-check for 7sec and the room’s temperature is displayed. Do not touch the screen during self-check. By
pressing the two buttons ([ ], [ ] at the same time for 3 seconds the countdown starts and the temperature controller unlocks (images below). By pressing [ ] for 3sec
we turn ON or turn OFF the controller (images below). The keyboard locks automatically after 50sec without activity.
By pressing more than 3sec the
button [ ] we switch ON or OFF
By pressing [ ] we enter the parameter’s menu.
The first parameter “SPO”is displayed and with [ ], [ ] we scroll into the parameters with the order they appear to parameters table below .
By pressing [SET] the value of the parameter is displayed and with the [ ], [ ] we change the value.
By pressing [ ] we confirm the new value and the name of the parameter is displayed.
By pressing [SET] we cancel the new value and the name of the parameter is displayed.
By pressing [ ] we exit the parameters menu.
Power supply: 230VAC 50/60Hz / Maximum power consumption: 3W
It is recommended to use a power supply safety switch: fuse 0,5A (not included)
Cabinet’s temperature sensor PTC 1Κ25oC / Accuracy: 0.5°C
Relay compressor 250VAC 30A resistive load 2HP / Relays fan 250VAC 10A
Operating temperature: -15÷+70°C / Storage temperature: -20÷+80°C
The device is mounted through panel hole 29x71mm and secured with snap-in brackets. Connection with terminal tabs 6.3×0.8mm
RSD2 can connect to the key programmer or to the data logger Mini Logger or to the KIOUR CAMIN network or to any modbus network.
Key programmer: controller’s parameter values can be saved or retrieved from the programming key. Plug in the programming key to the controller and press at the same
time [SET]+[ ]. The device connects to the key and the message “Eo”is displayed. By pressing [ ] the device downloads the parameters from the key and the message
“ro”= read O.K. or “rF” = read Fail is displayed. By pressing [ ] the device uploads the parameters to the key and the message “Yo”= Write O.K. or “YF”= Write Fail is
displayed. In case of failure (rF or YF) reenter the key to the serial input and repeat the procedure from the beginning. The key can connect to all KIOUR devices. If you try
to read the parameters of a different device, message “rF”is displayed. At any time, we can perform the aforesaid operation. After 10sec the key is disconnected.
Data logger Mini Logger: the controller is connected to the data logger via cable and by programming the parameter Add = 1. Automatically, based on selected minutes,
the data logger writes to a microSD memory card the controller’s temperatures, status and alarms.
CAMIN network: the controller can connect to the CAMIN network via an interface NET-INS-485. CAMIN is an PC software application designed to collect information,
watch and fully control a net of KIOUR devices while sending SMS and email in case of an alarm. The maximum length of the net can be 1000 meters.
INDICATIONS AND BUTTON OPERATIONS
button
Operations
pressed once
pressed more than 3 sec
pressed at the same time
enter parameter’s menu
confirm new value
-
-
MUTE
temperature scale indication °C/°F
mute buzzer
ON/OFF controller
unlock device
T2
-
-
df
cancel new value
manual defrost
-
Indications
compressor ON
fan ON
defrost ON
locked keyboard
sensor malfunction
STARTING UP - SWITCHING ON/OFF THE DEVICE
PROGRAMMING THE PARAMETERS
TECHNICAL SPECIFICATIONS
CONNECTIONS - DIMENSIONS
SERIAL INPUT

PARAMETER TABLE
#
code
description
min
max
RSD2
UOM
1
SΡo
SET POINT: temperature control room
SLo
SHi
0.0
°C/°F
2
ALo
lower alarm limit temperature of the room
-50
AHi
-4.0
°C/°F
3
AΗi
higher alarm limit temperature of the room
ALo
+150
15.0
°C/°F
4
dFr
deFrost repetition time in hours
1
12
4
h
5
Cod
code to enter parameter’s menu = “22"
with Cod=1 and exit the menu back to factory settings
0
255
0
-
6
diF
differential operating temperature of SPo
0.1
25.0
3.0
°C/°F
7
CFA
In case of sensor’s malfunction (LF1), the compressor operates as follows:
0 = 40% compressor’s operation (3min ΟΝ, 4min OFF),
1 = 100% compressor’s operation (ΟΝ continuously).
0
1
0
-
8
Crt
minimum pause time of the compressor
0
4
2
min
9
dti
maximum duration of deFrost
1
90
25
min
10
dLΕ
Temperature limit of deFrost: above this temperature the automatic deFrost stops and it is not possible to
start the procedure again manually.
Manual deFrost lasts 20 min and does not stop based on “dLE” temperature limit.
0.0
25.5
10.0
°C/°F
11
doP
type of deFrost: compressor OFF (not programmable)
-
-
0
-
12
dri
dripping time, in which the compressor remains OFF after deFrost ends
0
10
0
min
13
tdF
During deFrost the indication “dFr” is displayed, where: 0 = the room’s temperature is displayed during defrost.
0
99
20
min
14
ΑJ1
zero adjustment of temperature sensor
-9.9
+15.5
0.0
°C/°F
15
ΑJ2
(not in use)
0.0
16
tSd
time delay for refreshing the temperature indication on screen
0
20
0
sec
17
F_C
switch °C/°F (0=°C, 1=°F) ATTENTION: changes between °C/°F do not apply on SPo
0
1
0
°C/°F
18
brA
baud rate (9600mbps)
-
-
-
-
19
trE
time response of the device to the CAMIN network
0
100
20
msec
20
FFu
Fan’s relay operation (1=ON continuously, 0=ON when the compressor is ON). The fan operates during deFrost.
0
1
0
-
21
UFu
serial input operating mode, where 0 = operates with the network and the serial key,1 = connects with an
external device for exporting alarms. ATTENTION: if the value in
“Add” parameter is ≠ 0, then the “Ufu” is programmed automatically to 0.
0
1
0
-
22
SLo
minimum temperature limit of SPo
-50
SHi
0.0
°C/°F
23
SΗi
maximum temperature limit of SPo.
SLo
+150
+8.0
°C/°F
24
Odo
Door input polarity (0=OFF, 1=ON with ΝΟ contact, 2=ΟΝ with NC contact). When the door opens, the fan
turns OFF immediately.
0
2
0
-
25
At2
Start delay time alarm, where:
0 = activate immediately,
1 ÷ 120 min = the alarm is activated after the selected minutes.
For sensor and door failure alarms, the above rules do not apply.
0
120
20
min
26
U3
(not in use)
-
-
-
-
27
U4
(not in use)
-
-
-
-
28
U5
(not in use)
-
-
-
-
29
Add
address of the device in the CAMIN network
0
255
1
-
Made in Greece.
ATTENTION according to safety standards, the device must be properly positioned and protected from any contact with electrical parts. All parts that provide protection must
be fastened in such a way that they cannot be removed without the use of tools. ATTENTION: disconnect the power supply of the device before proceeding to any kind of
maintenance. ATTENTION: do not place the device near heat sources, equipment containing strong magnets, in areas affected by direct sunlight or rain. ATTENTION:
prevent electrostatic discharges at the side slots of the device and sharp objects from been inserted. ATTENTION: separate the signal's cables from the power supply's
cables to prevent electromagnetic disorders. Signal cables must never be in the same pipe with the power supply cables. Use the device only as described in this
document, not to use itself as a security device. The device must be disposed of in accordance with local standards for the collection of electrical and electronic
equipment. Read and keep these instructions. The device is under two year's guarantee of good operation. The guarantee is valid only if the manual instructions have
been applied. The control and service of the device must be done by an authorized technician. The guarantee covers only the replacement or the service of the device.
preserves the right to adjust its products without further notice.
V1.1.230518
ALARM TABLE
1
LF1
cabinet sensor malfunction
2
ΑLo
alarm low temperature in the cabinet
3
ΑHi
alarm high temperature in the cabinet
4
dοr
open door alarm ( if the door is open more than 2min the alarm is activated and the compressor stops)
The alarms are automatically deactivated when the cause of the alarm disappears.
Table of contents
Other KIOUR Temperature Controllers manuals