KNX GIRA User manual

Dimming actuator, 4-gang
Dimming actuator, 4-gang Standard
Order no.: 2015 00
Dimming actuator, 4-gang Komfort
Order no.: 2025 00
Operating instructions
1 Safety instructions
Electrical devices may only be mounted and connected by electrically skilled persons.
Serious injuries, fire or property damage possible. Please read and follow manual fully.
Danger of electric shock. Always disconnect before carrying out work on the device or load.
Danger of electric shock. Device is not suitable for disconnection from supply voltage. The load
is not electrically isolated from the mains even when the output is switched off.
Risk of destruction of the dimmer and load if the set operating mode and load type do not
match. Set the correct dimming principle before connecting or exchanging the load.
Fire hazard. For operation with inductive transformers, each transformer must be fused on the
primary side in accordance with the manufacturer's instructions. Only safety transformers ac-
cording to EN 61558-2-6 may be used.
These instructions are an integral part of the product, and must remain with the end customer.
2 Device components
Figure1: Device components
(1) Button field for manual operation
(2) Programming button and LED
(3) KNX connection
(4) Status LEDs for outputs
(5) Load connections
3 Function
System information
This device is a product of the KNX system and complies with the KNX directives. Detailed tech-
nical knowledge obtained in KNX training courses is a prerequisite to proper understanding.
1 / 11
82402712 10.07.2020

Dimming actuator, 4-gang
The function of this device depends upon the software. Detailed information on loadable soft-
ware and attainable functionality as well as the software itself can be obtained from the manu-
facturer´s product database.
The device can be updated. Firmware can be easily updated with the Gira ETS Service App
(additional software).
The device is KNX Data Secure capable. KNX Data Secure offers protection against manipula-
tion in building automation and can be configured in the ETS project. Detailed specialist know-
ledge is required. A device certificate, which is attached to the device, is required for safe com-
missioning. During mounting, the certificate must be removed from the device and stored se-
curely.
Planning, installation and commissioning of the device are carried out with the aid of the ETS,
version 5.7.3 and above.
Intended use
– Switching and dimming of
incandescent lamps,
HV halogen lamps,
dimmable HV-LED lamps,
dimmable compact fluorescent lamps,
dimmable inductive transformers with LV halogen or LV LED lamps,
dimmable electronic transformers with LV halogen or LV LED lamps
– Operating in KNX systems
– Mounting on DIN rail according to EN 60715 in sub-distribution unit
If inductive or electronic transformers are connected, observe the data of the transformer
manufacturer on loads and the dimming principle.
HV-LED and compact fluorescent lamps generate high pulsed currents, when they are
operated in the leading edge phase control.
Our dimmers take into account the different electronic characteristics of most LED lamps
found on the market. However, it cannot be guaranteed that in individual cases the de-
sired results may not be achieved.
Product characteristics
– Outputs can be operated manually, construction site mode
– Feedback in manual mode and in bus mode
– Disabling of individual outputs via bus
– Status feedback
– KNX Data Secure compatible
– Updateable with ETS Service App
Only for "Comfort" version:
– Disabling of individual outputs manually or by bus
Dimming operation characteristics
– Automatic or manual selection of the dimming principle suitable for the load
– Protected against no-load, short-circuit and overheating
– Feedback of the switching position and the dimming value
– Parameterisable switch-on and dimming behaviour
– Time functions: switch-on delay, switch-off delay, staircase lighting timer with run-on time
– Light scene operation
– Status indicator of the outputs via LED
– Mains failure longer than approx. 5 seconds leads to switch-off of the dimming actuator.
Depending on the parameter setting, the connected load is calibrated after resumption of
power supply.
– Power extension possible by means of power boosters.
2 / 11
82402712 10.07.2020

Dimming actuator, 4-gang
Only for "Comfort" version:
– Signal in the event of a short-circuit
– Increase in output power possible through parallel switching of multiple outputs
– Operating hours counter
Delivery state: Construction site mode, outputs can be operated using button field.
Flickering of the connected lamps due to undershoot of the specified minimum load or
through centralised pulses from the power stations. This does not represent any defect in
the device.
Logic function characteristics
Only for "Comfort" version:
– logic gates
– Transformer (conversion)
– Disabling element
– comparator
– Limit value switch
4 Operation
Operating elements
Figure2: Operating elements
(4) Status LEDs for outputs
– on: output switched on, 1...100%
– flashes at 1 Hz: short-circuit or manual mode
– flashes at 2 Hz: overload, mains voltage failure or firmware update
(6) Button ǃ – Manual operation
(7) LED ǃ – on: continuous manual mode
(8) LED ON|+ – on: selected output on, 1...100%
(9) ON|+Button: Switch on/Increase brightness
(10) OFF|−Button: Switch off/Reduce brightness
(11) LED OFF|− – on: selected output off
(12) ALL OFFButton: Switching off all outputs
The LEDs (4) optionally indicate the states of the outputs only temporarily (parameter-de-
pendent).
Operating modes
– Bus operation: Operation via push-button sensors or other bus devices
– Temporary manual control: manual control locally with keypad, automatic return to bus
control
3 / 11
82402712 10.07.2020

Dimming actuator, 4-gang
– Continuous manual mode: Exclusively manual operation on the device
No bus operation is possible in manual mode.
After a bus failure and restoration the device switches to bus operation.
The manual mode can be disabled in ongoing operation via a bus telegram.
Switching on the temporary manual control
Operation using the button field is programmed and not disabled.
■ Press button ǃ (6) briefly.
LED ǃ (7) flashes, LED A1... (4) of the first configured output flashes.
Short-time manual operation is switched on.
After 5 s without a key-press, the actuator returns automatically to bus operation.
Switching off temporary manual operation
The device is in short-term manual mode.
■ No button-press for 5 s.
- or -
■ Press ǃ (6) button briefly as many time as necessary until the actuator leaves the
short-time manual mode.
Status LED A1... (4) no longer flash, but rather indicate the output status.
Short-time manual operation is switched off.
When switching off the manual control, the outputs, depending on the programming,
switch to the active position, e.g. forced position, logic operation.
Switching on permanent manual control
Operation using the button field is programmed and not disabled.
■ Press the ǃ (6) button for at least 5 s.
LED ǃ (7) lights, LED A1... (4) of the first configured output flashes.
Continuous manual mode is switched on.
Switching off permanent manual control
The device is in continuous manual mode.
■ Press the ǃ (6) button for at least 5 s.
LED ǃ (7) is off.
Continuous manual mode is switched off. Bus operation is switched on.
When switching off the manual control, the outputs, depending on the programming,
switch to the active position, e.g. forced position, logic operation.
Operating the outputs
The device is in continuous or short-term manual mode.
■ Press the button ǃ (6) briefly as many times as necessary until the desired output is se-
lected.
The LED of the selected output A1... (4) flashes.
The LEDs ON|+ (8) and OFF|− (11) indicate the status.
■ Operate output with ON|+ (9) button or OFF|− (10) button.
Short: switch on/off.
Long: dim brighter/darker.
Release: Stop dimming.
The LEDs ON|+ (8) and OFF|− (11) indicate the status.
4 / 11
82402712 10.07.2020

Dimming actuator, 4-gang
Short-term manual operation: After running through all of the outputs the device exits
manual mode after another brief press.
Switching off all outputs
The device is in continuous manual mode.
■ Press the button ALL OFF (7).
All outputs are shut off.
5 Information for electrically skilled persons
DANGER!
Mortal danger of electric shock.
Disconnect the device. Cover up live parts.
5.1 Fitting and electrical connection
Fitting the device
In secure operation (preconditions):
– Secure commissioning is activated in the ETS.
– Device certificate entered/scanned or added to the ETS project. A high resolution camera
should be used to scan the QR code.
– Document all passwords and keep them safe.
Observe ambient temperature. Ensure adequate cooling.
■ Maintain a distance of 18 mm, 1 module when operating multiple dimmers or power units
within the same control cabinet.
■ Mount device on DIN rail.
■ In secure operation: The device certificate must be removed from the device and stored
securely.
Connecting the device
■ Connect bus line with KNX connecting terminal according to their correct polarity.
■ Attach the cover cap to the KNX connection as protection against hazardous voltages.
CAUTION!
Danger of destruction. 400 V are shorted when outputs switched in parallel are con-
nected to different outer phase conductors.
The device will be destroyed.
Always connect outputs switched in parallel to the same outer phase conductor.
Delivery state: The outputs can be operated with manual control.
In the "Universal" operating mode, the dimming actuator only calibrates itself again after discon-
nection of the load and also after commissioning using the ETS.
Inductive capacitive mixed load is not permitted.
Connect 600 Watt LED lamps or compact fluorescent lamps at most per 16ampere circuit
breaker. When connecting transformers, observe the data of the transformer manufac-
turer.
Only for "Comfort" version:
Several dimmer outputs can be combined for dimming greater lamp loads. Only utilise
parallel-switched outputs up to 95 % each. Do not connect any compact fluorescent
lamps to dimmer outputs switched in parallel.
5 / 11
82402712 10.07.2020

Dimming actuator, 4-gang
Observe delivery state. Before connecting and switching on, program the dimming actu-
ator to the changed output configuration.
Do not expand parallel-switched dimmer outputs with power packs.
Figure3: Comfort variant of the device connection with dimmer outputs switched in parallel
(connection example)
■ Connect the lamp loads according to the connection example.
5.2 Commissioning
Load physical address and application program
■ Press the programming button.
The programming LED lights up.
■ Load physical address and application program using the ETS.
Safe-state mode
The safe state mode stops the execution of the loaded application program.
Only the system software of the device is still functional. ETS diagnosis functions and pro-
gramming of the device are possible. Manual operation is not possible.
Activating the safe-state mode
■ Switch off the bus voltage or remove the KNX device connection terminal.
■ Wait about 15 s.
■ Press and hold down the programming button.
■ Switch on the bus voltage or attach the KNX device connection terminal. Release the pro-
gramming button only after the programming LED starts flashing slowly.
The safe-state mode is activated.
With a new brief press of the programming button, the programming mode can be
switched on and off as usual also in the safe-state mode. If Programming mode is active,
the programming LED stops flashing.
6 / 11
82402712 10.07.2020

Dimming actuator, 4-gang
Deactivating safe-state mode
■ Switch off bus voltage (wait approx. 15 s) or carry out ETS programming.
Master reset
The master reset restores the basic device setting (physical address 15.15.255, firmware re-
mains in place). The device must then be recommissioned with the ETS. Manual operation is
possible.
During secure operation: A master reset deactivates device security. The device can then be re-
commissioned with the device certificate.
Performing a master reset
Precondition: The safe-state mode is activated.
■ Press and hold down the programming button for > 5 s.
The programming LED flashes quickly.
The device performs a master reset, restarts and is ready for operation again after ap-
prox. 5 s.
Restoring the device to factory settings
Devices can be reset to factory settings with the Gira ETS Service App. This function uses the
firmware contained in the device that was active at the time of delivery (delivery state). Restor-
ing the factory settings causes the devices to lose their physical address and configuration.
6 Technical data
Rated voltage AC 110 ... 230 V ~
Mains frequency 50 / 60 Hz
Power loss max. 7 W
Standby power approx. 0.16W per channel
Ambient temperature -5 ... +45 °C
Storage/transport temperature -25 ... +70 °C
Connected load per channel depends on the connected lamps and the set load type: (Figure 4),
(Figure 5)
ETS parameter load type
UNI universal (with automatic calibration procedure)
LJconv. transformer (inductive / phase cut-on)
|LED (leading edge phase control)
dželectr. transformer (capacitive / trailing edge phase control)
{LED trailing edge phase control
7 / 11
82402712 10.07.2020

Dimming actuator, 4-gang
Figure4: LED lamp loads
Figure5: conventional lamp loads
Inductive capacitive mixed load is not permitted.
Power boosters See power booster instructions
Connection
single stranded 0.5 ... 4 mm²
Finely stranded without conductor sleeve 0.5 ... 4 mm²
Finely stranded with conductor sleeve 0.5 ... 2.5 mm²
Connection torque screw terminals max. 0.8 Nm
Fitting width 72 mm / 4 module
KNX
8 / 11
82402712 10.07.2020

Dimming actuator, 4-gang
KNX medium TP256
Commissioning mode S-mode
Rated voltage KNX DC 21 ... 32 V SELV
Current consumption KNX 15 mA
Connection mode KNX device connection terminal
7 Troubleshooting
Connected LED lamps or compact fluorescent lamps switch off in the lowest dimming position
or flicker
The set minimum brightness is too low.
Increase minimum brightness.
Connected LED lamps or compact fluorescent lamps flicker
Cause 1: Lamps are not dimmable.
Check manufacturer's instructions.
Exchange lamps for another type.
Cause 2: Dimming principle and lamps do not optimally match.
For HV-LED: Check operation in another dimming principle, reduce connected load as
well if necessary.
For LV-LED: Check the lamp operating device and replace as necessary.
With the "Universal" setting: Define the dimming principle manually.
Connected HV-LED lamps or compact fluorescent lamps in the lowest dimming position are too
bright; dimming range is too small
Cause 1: The set minimum brightness is too high.
Reduce minimum brightness.
Cause 2: HV-LED trailing edge phase control dimming principle does not optimally match the
connected lamps.
Check operation in the "HV-LED leading edge phase control" setting, reduce connected
load as well if necessary.
Exchange lamps for another type.
Output has switched off.
Cause 1: overheating protection has tripped.
Disconnect all outputs from the mains, switch-off the corresponding circuit breakers.
HV-LED trailing edge phase control: Reduce the connected load. Exchange lamps for an-
other type.
HV-LED leading edge phase control: Reduce the connected load. Check the operation in
the "HV-LED trailing edge phase control" setting. Exchange lamps for another type.
Let device cool down for at least 15 minutes. Check installation situation, ensure cooling,
e.g. provide distance from surrounding devices.
Cause 2: Surge protection has triggered.
HV-LED trailing edge phase control: Check the operation in the "HV-LED leading edge
phase control" setting, reduce the connected load as well if necessary.
Exchange lamps for another type.
The response of the surge protection can be signalled by sending a short-circuit telegram
or can be determined by polling the "short-circuit" communication object.
Cause 3: short-circuit in output circuit
Disconnect all outputs from the mains.
Eliminate short-circuit.
9 / 11
82402712 10.07.2020

Dimming actuator, 4-gang
Switch on the mains voltage of the outputs again. Switch the affected output off and on
again.
When a short-circuit occurs the affected output switches off. Automatic restart when short-
circuit is eliminated within 100 ms (inductive load) or 7 seconds (capacitive or ohmic
load). After that lasting switch-off.
When a short-circuit occurs during the calibration process, the load calibrates itself again
after the short-circuit is eliminated.
Cause 4: load failure.
Check load, replace light bulb. For inductive transformers, check primary fuse and replace
if necessary.
Manual control with button field not possible
Cause 1: Manual control has not been programmed.
Program manual control.
Cause 2: Manual control via bus disabled.
Enable manual control.
None of the outputs can be operated.
Cause 1: All of the outputs are disabled-
Cancel disabling.
Cause 2: Manual mode active.
Deactivate manual mode (switch off continuous manual mode).
Cause 3: Application software missing or faulty.
Check programming and correct.
All outputs off and not possible to switch on
Cause 1: bus voltage failure.
Check bus voltage.
Luminaires flicker or buzz, proper dimming not possible, device buzzes
Cause: wrong dimming principle set
Installation or commissioning error. Disconnect device and luminaire, switch off circuit
breaker.
Check installation and correct.
If the wrong dimming principle has been preselected: Set correct dimming principle.
If dimming actuator calibrates itself incorrectly, e.g. with highly inductive mains or long
load cables: preselect correct dimming principle with commissioning.
LED lamp is dimly lit when dimmer is switched off
Cause: LED lamp is not optimally suited for this dimmer.
Use a compensation module, see accessories.
Use another type of LED lamp or an LED lamp of another manufacturer.
8 Accessories
Compensation module LED Order no. 2375 00
9 Warranty
The warranty is provided in accordance with statutory requirements via the specialist trade.
Please submit or send faulty devices postage paid together with an error description to your re-
sponsible salesperson (specialist trade/installation company/electrical specialist trade). They will
forward the devices to the Gira Service Center.
10 / 11
82402712 10.07.2020

Dimming actuator, 4-gang
Gira
Giersiepen GmbH & Co. KG
Elektro-Installations-
Systeme
Industriegebiet Mermbach
Dahlienstraße
42477 Radevormwald
Postfach 12 20
42461 Radevormwald
Deutschland
Tel +49(0)21 95 - 602-0
Fax +49(0)21 95 - 602-191
www.gira.de
11 / 11
82402712 10.07.2020
Other manuals for GIRA
3
This manual suits for next models
2
Table of contents
Other KNX Controllers manuals

KNX
KNX Module SAS-04.16 User manual

KNX
KNX GIRA User manual

KNX
KNX Jung 2304.16 REG HE User manual

KNX
KNX Jung 230011SU User manual

KNX
KNX GIRA 5065 00 User manual

KNX
KNX Iddero Verso User manual

KNX
KNX SATION-DM0101.0210 User manual

KNX
KNX Push Button RF+ User manual

KNX
KNX GIRA User manual

KNX
KNX Berker 7531 40 18 User manual