KOM-STER TIGRA User manual

TABLE OF CONTENTS
1. Application ........................................................................................2
2. Specification .....................................................................................3
3. Connecting external device (feeder, fan, pump ) .............................4
3.1 Connecting remote control panel ................................................5
3.2 Remote panel upply ..................................................................6
3.3 Panel-central unit communication ...............................................7
4. Configuration parameter ..................................................................8
5. Service parameter ............................................................................9
6. Front panel button .............................................................................10
6.1 Diode indicating the operation of external device .....................12
7. Driver handling..................................................................................13
7.1 Fir t run .......................................................................................13
7.2 Changing function parameter in the driver menu........................13
7.3. Burning up to the boiler...............................................................14
8. Operating mode (standby, off, setting fire, regulation, running)...16
9. Alarm depending on temperature .....................................................17
9.1 Water temperature higher than 90 ˚C............................................17
9.2 Water temperature in the range of 80-90 ˚C..................................18
9.3 Screw/feeder' pipe overheating alarm..........................................18
9.4 Temperature drop alarm ...............................................................19
9.5 “Anti-fro t”alarm .........................................................................19
9.6 Thermal alarm (hardware protection)...........................................19
10. Temperature en or failure alarm ......................................................20
(C/H sensor failure, breakdown of: Tfeed, Tflo, Th/w, Tcir)
11. Mode (D/N, ECO, ROOM, NORM, CAL).......................................24
12. Circulation pump handling................................................................24
12.1 Central heating pump..................................................................25
12.2 Hot water pump..........................................................................25
12.3 Hot water container priority................................................26
12.4 Underfloor heating pump............................................................27
12.5 Circulation pump........................................................................28
13. Time and date etting ........................................................................29
14. Time zone upport (calendar and day/night mode)............................30
14.1 Day/night mode..........................................................................30
14.2 Calendar.....................................................................................31
15. Temperature en or ...........................................................................32
16. Explanation of configuration parameter ............................................34
17. U e of the room thermo tat.................................................................38
18. Safe u e of the driver..........................................................................40
1

1. APPLICATION
„TIGRA” i a driver that en ure the maintenance of et water
temperature in a boiler equipped with automatic feeder of olid
fuel. It advanced feature provide economic and automatic
operation of unit a well a full control over central heating
pump, H/W pump, underfloor heating and circulation pump.
Time zone , economic function , day and night etting and
new algorithm of control over the blower en ure fuel aving up
to 20% in compari on to traditional driver . Room thermo tat
output provide convenience and comfort of u e. The
po ibility to connect additional remote control panel (boiler
control from any place in the apartment) make thi driver
pecial among other model available on the market.
Every user can connect up to three additional remote
control panels, identical to the main panel mounted
next to the boiler.
You can ask for the opportunity to buy additional control
panels under the telephone number:
(62) 94 33 04 ; 0 796 793 796
or e-mail biuro@kom-ster.pl
The manufacturer provide additional option uch a connection of WiFi
module, GSM and TV to the driver. In thi ca e, the connector on rear wall of
the hou ing i u ed. The connector allow you to connect three device (for
example, three remote control panel – thi option i already available!). Each
of the device i recognized a an independent unit, o that you can for example
connect two remote panel and one WiFi module that allow the driver control and a
preview of the boiler on the Internet. It will al o be po ible to connect for example
one panel, one WiFi module and one GSM module.
For more information about the additional module premiere , contact u on e-mail:
biuro@kom- ter.pl. Planned introduction of module for ale - November 2013.
2

2. SPECIFICATIONS
Supply voltage 230 V / 50 hz
Power con umption of the driver 6W
Temperature en or work range 0-100˚C
Work temperature 0-40˚C
Output load ( ecured with a fu e
6,3A)
Feeder- 1,5 A
Central heating pump-
0,8A
H/W Pump - 0,8A
Blower- 1,5 A
Floor pump - 0,8A
Cir. Pump - 0,8A
Circulation pump Anti Stop 1 min every 7 day
Auto pump tart (anti-fro t) Le than 5˚C
External breakdown thermo tat
tart (feeder and fan lock) More than 85˚C
Software ecurity enable More than 90˚C
Number of time zone 24 for each day
Po ibility to connect remote
control YES/ max 4 panel
H/W pump handling YES
Circulation pump handling YES
Floor pump handling YES
Thermal protection (STB
thermo tat) YES
3

3. CONNECTING EXTE NAL DEVICES
(fuel feeder, fan, circulation pumps)
U ing the plug attached to the driver, connect cable according
to the diagram below, and then in ert the plug to the
corre ponding ocket in the driver hou ing.
You should examine wire colors in order to connect
cables to the corresponding places in connectors.
SOCKETS
PLUG IN THE D IVE
Connection on the side of plugs attached to the driver:
1. Connect the green-yellow wire - G OUND to the
central pin (PE ) in the plug.
2. Connect brown and blue wire (N and L 230V) to the pin
according to mark in the picture.
L, brown -PHASE.
N, blue -ZE O, NEUT AL
3. Check whether the connection are correct.
Principle of wire connection on the circulation pumps.
1. Take off the lid of pump teering box
2. Connect the green-yellow wire – G OUND in the
teering box to the zero clamp, marked with PE
4

3. Brown (L) and blue (N) wire hould be connected to the
current terminal block.
4. Check whether the connection are correct and crew
the teering box.
Specific diagram of connecting the wires to circulation
pumps can be found in the pump manual.
Incorrect connection of the wires will cause damage
of the driver or devices connected. Installation can
be made only by authorized staff. Before
connecting the device, remember to remove the driver
power cord from the wall socket!!
3.1 CONNECTING EMOTE CONT OL
PANELS
Driver TIGRA enable connection of FOU remote control
panel marked re pectively 0,1,2,3. Thi number i di played
when turning on the driver by the network button on the pla h
creen. It i al o vi ible on the tally of every panel. “0” panel i
the ba ic (main) panel, crewed to the main hou ing of the
driver or directly connected to the hou ing when the main
panel i mounted on the boiler and upper hou ing, for example,
behind the container or on rear/ ide wall of the boiler. On the
other hand, every additionally mounted panel in the apartment
will be of equential number 1, 2 or 3. There i no po ibility to
connect for example two panel of the ame number. Driver
oftware automatically detect the connected panel and allow
it the control over the whole unit work. Every additional panel
look the ame a the main panel (0) and allow the full
5

regulation of the boiler and view of the heating unit current
work mode. There i an ability to mount the panel for example
on a wall, metal ba e, or in any other place you choo e.
Modern con truction ba ed on two proce or allow
operation of the unit even without the panel. Any time you
can di connect one of the panel (even the “0” panel) and the
driver will work anyway, en uring the full control over work of
the boiler.
3.2 EMOTE PANELS SUPPLY
Each of remote control panel i directly powered from the
driver main hou ing. The device u e a tandard 4-wire cable
with 0,5 cro - ection which provide power upply (red and
blue wire) and data tran mi ion (black and white wire).
De cription of the panel ocket and connection chematic are
placed in every panel on rear wall of the hou ing and in the
manual. De cription of driver' ocket connector can be found
below. There i a po ibility to power the panel from
independent power upply 12V connected to the wall ocket
230V near the device and connect it with the driver central unit
by only a 2-wire cable tran mitting information. Only two
central pin of the panel connector are u ed then (black and
white wire – data tran mi ion).
When connecting more than one remote panel there i no
need to connect each panel with the driver! Ju t connect
for example 3 panel in erie and only one of them
hould be connected by a cable with the main driver.
6

Below you can ee a ocket for remote panel connecting. Two
upper pin are the upply. Two bottom pin – information
tran mi ion, data tran mi ion:
–12V + RED wire
–12V - BLUE wire
–INFO + data tran mi ion, BLACK wire
–INFO - data tran mi ion, WHITE wire
3.3 PANEL- CENT AL UNIT
COMMUNICATION
To enable communication between the panel( ) and the central unit (main
driver), you can u e only two central pin on the ide of panel and two
bottom pin of the connector on the driver hou ing, marked in the picture a
INFO + i INFO – (black and white wire ). In order to upply the panel
directly from the driver, you can u e two additional pin (outer in the panel
and two upper in the connector of the driver, red and blue wire ). Panel can
be al o powered directly from an independent power upply 12V. If the
panel ha an independent upply, you can u e only a 2-wire cable
tran mitting data (INFO+ and INFO-)
No supply means a mistake in cables connection between pins
+12V and -12V. No main screen of the driver (time, mode, set
temperature and operating status) is a mistake in cable
connection between INFO+ and INFO-). A mistake while
connecting the cables may cause damage to the panel or central unit!
7

4. CONFIGU ATION PA AMETE S
FUNCTION Factory
setting Range Unit
Set temperature 60 35-90 ˚C
Night correction - 3 - 10...+10 ˚C
Economic correction - 3 0....-10 ˚C
C/H pump tart
temperature 35 Off.....25-70 ˚C
H/W temperature Off
Detail in the
further part of
the manual
˚C
Time of upplying 15 Off...1-205 S
Feed period 90 1-150 S
Feed count 2 Off...1-20
Blow time 10 Off.....5-59 S
Blow break 10 1-99 Min
Blower level 50 10-100 %
Rotation in the
running tate 50 10-100 %
Driver witch-off
temperature 30 25-35 ˚C
8

5. Service parameters
FUNCTION
Factor
y
setting
Range Unit
Minimal temperature 40 30-55 ˚C
Maximal temperature 80 60-90 ˚C
Hi tere i 1 1-5 ˚C
Minimal blower level 25 20-70 %
Maximal blower level 55 20-70 %
No fuel recovery time 90 Off…-90 Min
Time to top the pump 3 1-250 Min
H/W container priority NO YES / NO
Feeder alarm temp. 70 Off...35-90 ˚C
Clearence time 5 1-30 min
Circulation pump top
temperature OFF OFF- 70 ˚C
FLOOR temperature OFF OFF-50 ˚C
Language POLIS
H
POLISH, CZECH,
ENGLISH
Fire etting time 2 hour 1- 7 Hour
Extinction time 2 hour 1 - 7 Hour
9

The service parameters of MIN and MAX blower level can
be changed only in very untypical fans, if the rotation changing by
means of function BLOWE LEVEL between 10 and 100% are
imperceptible. Unnecessary change of settings may cause improper operation
of the blower mounted next to the boiler.
6. Front panel buttons
- Button i u ed to change the operating mode. In the
function MANUAL OPERATION, it i u ed for the
circulation pump enabling/di abling.
Driver „TIGRA” provides work in one of five following
operating modes:
-NO M- Normal
-D/N – The driver automatically decrea e temperature
at night (11p.m.-6a.m.) by a value et in the menu
(Night Correction)
-ECO- The driver automatically decrea e temperature
independently from the time of day by a value et in the
menu (Economic Correction)
-CAL- Work according to the calendar. The driver in
thi mode implement the program et by it u er. You
can et the temperature correction and
enabling/di abling of the individual pump depending
on the hour. Calendar etting wa de cribed in the
further part of thi manual. (para 14.2)
-OOM – Work with a room thermo tat. The driver
when reaching the et temperature in the room,
witche to forced running and cyclically
enable /di able the central heating pump. The principle
of cooperation with the thermo tat and the choice of
appropriate model wa de cribed in the further part of
the manual (para 17)
10

- „UP” button. Thi button i u ed to move up (back) in
the menu, a well a to return from the menu to the
main creen. During the work in the manual mode, it is used
to enable/disable the fan.
- Thi button ha three meaning :
1. Enter the menu and croll the individual creen
2. Increa e the parameter of function up
3. In the manual operation mode, when the fan is
enabled, this button is used to increase its
rotations.
- Thi button ha three meaning
1. Enter the menu and croll the individual creen
2. Decrea e the parameter of function down
3. In the manual operation mode, when the fan is
enabled, this button is used to decrease its
rotations.
ENTER, thi button i u ed to accept
- witch to edition mode of the function you want to
change
- accept entered change ( aving)
Thi button cau e witching to OFF mode when the
boiler i enabled. Fan and feeder are di abled
independently from the temperature. Circulation pump
keep working, dependently on temperature of their
enabling/di abling. When pre ed, in cription – OFF
appear in the main creen. Pre ing again cau e
witching to RUNNING mode, if the temperature of the
boiler i higher than the et temperature, or to FIRE
SETTING mode when the temperature of the boiler i
11

lower than the et temperature.
Thi button and OFF mode i often u ed during opening the
door to en ure that the feeder or fan will not be enabled. OFF
mode i often u ed during burning up on additional grate when
you want circulation pump to work, not the feeder not fan. In
the manual operation mode it is used to enable/disable the
fuel feeder.
Explanations of the use of buttons for changing the calendar
functions and changing the time are described in the further
part of the manual (para 6)
6.1 DIODES INDICATING THE
OPE ATION OF EXTE NAL DEVICES
FEEDE
FAN
CENT AL HEATING PUMP
H/W PUMP
UNDE FLOO HEATING PUMP
CI CULATION PUMP
Additionally, the panel is equipped with:
- I a diode indicating temperature et on the room
thermo tat, reached in the room in the THER mode.
- ALA M. A diode indicating an alarm mode of the
device.
12

7 D IVE HANDLING
Plea e contact u if there are any problem with the driver
handling or the proce of burning, once you read thi
in truction. Technical ervice number i given on the title page
of thi manual. Our erviceman will help you with handling
and etting the device.
7.1. First run
The driver can be enabled by the power witch on the left ide of the
driver upper hou ing. Current temperature of the central heating boiler
will be di played on the red di play. Set temperature (T et) will be
di played on the LCD and the operating mode of the driver- (OFF).
The current time and operating mode are al o di played (factory
etting – NORM, more detail de cription of operating mode in para
11).
In the OFF mode, you can make any change in menu, becau e the
driver i in “ tandby” - fan and fuel feeder are not active.
The device can be witched to BURNING UP operating mode u ing
the button - in cription BURNING UP will be then di played.
Pre ing again thi button will cau e a return to the “ tandby” mode –
OFF.
7.2 Changing the function parameters in the
driver menu
Any function parameter changes can be done in the same way:
U ing button or you witch to menu and then find the function
of your intere t, the value of which you want to change.
Select the function, and then u ing thi button you witch to the
edition creen (green color of the di play).
U ing again button or you can make change that hould be
confirmed by thi button . The creen will be blue again. The change
wa accepted. U ing thi button you can witch to the main creen.
13

In the summer season, when the boiler is not used, the driver
should be in the “OFF” mode. Only then the ANTI STOP
function of the central heating circulation pump is on. This
function enables the central heating pump cyclically once a week,
eliminating that way the phenomenon of the pump getting stiff. You
can also enable the driver using the power switch or remove the
plug from the power socket, just remember to turn on the central
heating pump in the manual mode for a moment once a week.
7.3 Burning up in the boiler
In order to et fire to the boiler, you hould witch to the function
MANUAL OPE ATION.
Using the buttons:
or you hould find the creen MANUAL OPE ATION.
U ing thi button you can accept and turn on the manual
operation. The creen will change it color to green. It indicate that
the manual operation function i enabled. From that moment you can
enable/di able the following receiver :
–fan (button )
–fuel feeder (button )
–central heating circulation pump (button )
U ing thi button you can enable the feeder to upply the fuel.
While in the manual mode, you can al o tart the blower and central
heating pump at any moment u ing the e button on the keyboard.
By enabling/di abling the blower and feeder, reach the temperature of
about 40 ˚C.
It is recommended that the circulation pump should work
while setting fire in the manual mode.
After etting fire and reaching the appropriate temperature - 40 ˚C,
you can exit the MANUAL CONTROL u ing thi button and
14

return to the main creen. The di play will change it color form green
to blue.
The driver will automatically et fire in the boiler and reach the
temperature et by the u er.
U ing thi button you elect the operating mode – FIRE
SETTING. While etting fire, you adju t the parameter FEED TIME,
FEED PERIOD and BLOWER LEVEL according to the clue ( ).
Minimal temperature that can be set on the boiler
depends on the manufacturer's suggestions of the
boiler. More information on that issue can be found
in the technical specification of the device. Not
following the manufacturer's suggestions and burning in
lower temperatures may cause the central heating boiler
warranty expire.
Automatic fire setting is indicated by BURNING UP message on the main
display. When the boiler reaches the set temperature, inscription
RUNNING appears.
During automatic burning up, you should properly
choose the parameters FEED TIME, FEED PERIOD
and BLOWER LEVEL to maintain the appropriate
level of heat on the feeder's head and the best possible
flame while burning up. During burning up, the user has
only two parameters to use – FEED TIME and BLOWER
LEVEL. It is recommended that the feed period was set to 90
sec. Such feed period is the most optimal for boilers of 1 -
60KW.
15

8. OPE ATING MODES
( tandby, top, etting fire, regulation, running)
After witching off the device u ing the power witch, the
di play will how the in cription OFF. You can adju t the
parameter , but in thi mode, the driver doe not control the
fuel feeder and fan. Circulation pump work according to the
etting depending on temperature.
After pre ing the burning up tart , and word BU NING
UP appear – the feeder and fan tart. When the et temperature
i reached, the driver witche to the UNNING mode. Only
blow work, in order not to extinct. Depending on etting the
value FEED COUNT, the feeder tart . (ie, count set to 3
enables the feeder every third blow, count set to 2 starts the
blower every second blow, etc. Feed count set to OFF causes
that in the running mode the fuel will not be supplied). When
temperature drop below the et (minu the value of hi tere i ),
the drive witche to the EGULATION operating mode. A
do e of fuel i automatically upplied and blower tart . In the
EGULATION mode, it i enabled with a frequency et by
u ing the function FEED TIME and FEED PERIOD. Fan
work all the time, increa ing the heat to achieve the et
temperature again. The drive will witch to EXTINCTION
mode if there i no fuel left in the container, then the lynchpin
will be broken at the drive of the feeder or when the upply
y tem will be broken or when the temperature drop below the
value of REGULATOR TURN OFF TEMPERATURE. When
for example the regulator turn off temperature i et to 35
degree and the current temperature at the boiler drop to 34
degree , after 5 minutes – extinction tart , which la t for 2
hour (factory etting, po ibility of change). After 2 hour , the
driver witche to the STANDBY mode. The feeder and fan
witch off.
16

The u er i informed about the EXTINCTION tart (after 5
minute delay) by a hort beep when the current boiler
temperature drop below the DRIVER SWITCH-OFF
TEMPERATURE. 5 min. later the extinction proce will tart.
To witch again to the BURNING UP mode, pre until the
me age BURNING UP i di played on the di play.
9. ALA MS DEPENDING ON
TEMPE ATU E
Driver „TIGRA” equipped with many protection inform the
u er about the following alarm :
9.1 Water temperature higher than 90 ˚C
A very important alarm informing about dangerou ly high
water temperature in the boiler that lead to boiling the fluid in
the central heating in tallation. The alarm i enabled at more
than 90 ˚C. The driver di play color change to RED. Red
diode ALARM light up and enable the ound alarm. During
the alarm (temperature more than 90 ˚C) the feeder and fan are
witched off. Circulation pump are enabled in the afe mode
in order to cool the central heating in tallation.
Thi alarm ten la t until the temperature drop to 89 ˚C.
During this alarm, there is the inscription C ITICAL
TEMP. on the display
17

9.2 Water temperature in the boiler in the
range of 80-90 ˚C
When water temperature in the boiler exceed the value of 80
˚C but doe not exceed 90 ˚C, information alarm about the
incoming danger i activated – CRITICAL TEMP. alarm,
which i activated a de cribed above – at more than 90 ˚C.
The di play in the range of 80-90 ˚C tart blinking red, cyclic
ound alarm i activated, but burning in the boiler goe on
normally. This alarm is only an information one and does
not interrupt the process of burning.
While the alarm, there i the in cription
OVE HEATING on the di play
9.3 SC EW/FEEDE 'S PIPE
OVE HEATING ALA M
Feeder' en or (appropriately a embled, in a pecial bu hing
intended for thi purpo e) control the temperature of the crew
in the pipe up to peed. When omehow the heat goe back
toward the container, warming the crew to a dangerou ly
high temperature, (factory etting 70 ˚C, po ibility of change)
the driver enable the alarm. The di play tart blinking red.
The ound alarm i activated. For afety, the driver enable the
feeder for a pecific time et in the driver menu (CLEARENCE
TIME). Factory etting i 5 minute , po ibility of change.
Emergency tart of the feeder i to pu h out the heat from the
crew pipe and cool the y tem, o that the fuel doe not burn
in the upplier. When the feeder witche off after an
emergency tart and temperature of the pipe i lower than the
value et u ing the function FEEDER OVERTEMPER.
ALARM, ituation i afe again. Due to the afety i ue , the
18

alarm can not be interrupted. You can only witch off the ound
alarm u ing any button.
9.4 TEMPE ATU E D OP ALA M
Driver „TIGRA” control the ratio of current temperature to et
temperature up to peed. U ing the function NO FUEL
RECOVERY TIME you can elect the time of mea uring the
drop of temperature below the et. Factory etting i 90
minute . If during 90 minute the temperature will continue to
decrea e, the driver will inform about it by the ound alarm and
changing di play color. Additionally, the in cription
TEMPERATURE DROP appear . You can define the time after
which the driver i to indicate uch a drop. It can be any value
depending on the u er need .
Set the parameter of function NO FUEL ECOVE Y
TIME to OFF when you do not want the driver to
inform you about the temperature drop.
9.5 “ANTI-F OST” ALA M
The driver automatically enable circulation pump during
temperature drop below +5 ˚C in order to mix water in the
in tallation and prevent the fluid olidification.
During the alarm, the di play change color to navy blue.
Additionally, ound alarm i activated.
9.6 THE MAL ALA M (HA DWA E
P OTECTION)
The driver i equipped with independent thermal protection –
the o-called emergency thermostat (additional temperature
en or, independent from the C/H en or). It witche off the
19
Table of contents
Popular Boiler Supplies manuals by other brands

Immergas
Immergas 3.030323 quick start guide

oventrop
oventrop Regumat DN32 Installation and operating instructions

AFRISO
AFRISO PrimoBox ACB 910 Operation and installation manual

Bosch
Bosch 7738003218 installation instructions

TriangleTube
TriangleTube PSRKIT80 quick start guide

Beretta
Beretta 20067668 instruction manual

Xylem
Xylem McDonnell & Miller 47 Series instruction manual

Thermia
Thermia Diplomat Duo Optimum G2 Maintenance Instruction

Immergas
Immergas Victrix TT Series Instruction and warning book

Bosch
Bosch Worcester 15SBi Installation & operating instructions

oventrop
oventrop Regumat-180 plus Installation and operating instructions

BOSSCO
BOSSCO BCONDP installation instructions