Komfovent VAV User manual

UAB KOMFOVENT pasilieka teisę atlikti pakeitimus iš anksto neįspėjus
2
LT
VAV-18-11
TURINYS
ĮVADAS............................................................................................................................................ 3
1. SLĖGIO JUTIKLIŲ MONTAVIMAS.............................................................................................. 3
2. VAMZDELIŲ PAJUNGIMAS ........................................................................................................ 3
3. ELEKTRINIS PRIJUNGIMAS PRIE ĮRENGINIO......................................................................... 4
4. SLĖGIO JUTIKLIŲ NUSTATYMAI............................................................................................... 5
5. VAV FUNKCIJOS AKTYVAVIMAS IR NUSTATYMAI................................................................... 6
5.1. C5 automatika....................................................................................................................... 6
5.2. C6 automatika....................................................................................................................... 8
LT Diegimo instrukcija

UAB KOMFOVENT pasilieka teisę atlikti pakeitimus iš anksto neįspėjus 3
VAV-18-11
ĮVADAS
Kintamo oro srauto (toliau „VAV“ – ang.: Variable Air Volume) valdymo režimas – kai vėdinimo įrenginys veikia
atsižvelgiant į besikeičiančius vėdinimo poreikius skirtingose patalpose. Pagal poreikį valdoma vėdinimo sis-
tema užtikrina vėdinimą tik ten kur reikia, todėl toks oro kiekių palaikymo būdas ženkliai sumažina įrenginio
eksploatavimo sąnaudas, taip pat pailgėja jo tarnavimo laikas, mažiau teršiami ltrai.
Sumontavus ir paleidus vėdinimo įrenginį, vadovaujantis žemiau nurodytais punktais reikia atitinkamai pa-
ruošti įrenginį tam, kad VAV režimas veiktų teisingai.
1. SLĖGIO JUTIKLIŲ MONTAVIMAS
VAV funkcijos veikimui reikalingi kanaliniai slėgio jutikliai (komplektuojami kartu su įrenginiu užsakant VAV
funkciją), kuriuos reikia papildomai sumontuoti prie įrenginio: vieną ant tiekiamojo oro ortakio, kitą ant šalina-
mojo. Slėgio jutiklių montavimo reikalavimai:
• jutiklį būtina montuoti ortakio tiesiojoje dalyje, rekomenduojamas tiesiosios atkarpos minimalus atstumas –
dvi įstrižainės stačiakampio ortakio ar du diametrai apvalaus;
• rekomenduojama jutiklį montuoti vertikalioje padėtyje, oro vamzdeliais žemyn;
• jutiklis prisukamas tiesiai prie ortakio dviem skardvaržčiais (žr. 1 pav.).
82
70
1. pav. Slėgio jutiklio matmenys
2. VAMZDELIŲ PAJUNGIMAS
Sumontavus slėgio jutiklius numatytoje vietoje, reikia prijungti vamzdelius, kuriais oro slėgis paduodamas į
jutiklius. Kiekvienam jutikliui reikia prijungti po vieną oro vamzdelį, kurio vienas galas prijungiamas tiesiai prie
jutiklio (žr. 2 pav.), kitas vamzdelio galas, pragręžus kiaurymę ortakyje, praveriamas pro sandariklį ir iškišamas
į ortakio vidų.
Prie jutiklio, pritvirtinto prie tiekiamojo oro ortakio, prijungiamas vamzdelis į ženklu „+“ pažymėtą vietą, kitas
prijungimas „-“ paliekamas atviras. Jutikliui, skirtam šalinamajam orui, vamzdelis prijungiamas atvirkščiai – prie
„-“, o jutiklio prijungimas, pažymėtas „+“, paliekamas atviras.
2. pav. Slėgio jutiklio vamzdelių prijungimas
Rekomenduojama, kad vamzdeliai, jungiantys jutiklius su ortakiais, būtų kuo įmanoma
trumpesni.

UAB KOMFOVENT pasilieka teisę atlikti pakeitimus iš anksto neįspėjus
4
LT
VAV-18-11
3. ELEKTRINIS PRIJUNGIMAS PRIE ĮRENGINIO
Sumontavus slėgio jutiklius, juos reikia prijungti prie įrenginio automatikos. Jeigu norima, kad slėgis būtų pa-
laikomas abejuose oro srautuose, tuomet reikia prijungti du slėgio jutiklius. Priklausomai nuo automatikos tipo,
prijungimas turi būti atliktas griežtai pagal 3a arba 3b schemas.
VAV funkcija taip pat gali veikti tik su vienu slėgio jutikliu. Tuomet bus palaikomas slėgis tik tame oro sraute,
prie kurio prijungtas slėgio jutiklis, o kito oro srauto ventiliatorius bus valdomas lygiagrečiai („master-slave“
kongūracija). Slėgio jutiklis jungiamas prie automatikos gnybtų, kurie atitinka tą srautą, kuriame jis yra su-
montuotas.
Rekomenduojama jutiklius jungti 3×0,5 mm2 ekranuotu laidu.
31
32
33
34
35
36
C5 pagrindinė
plokštė
123
Tiekiamo oro
slėgio jutiklis
123
Šalinamo oro
slėgio jutiklis
28
29
30
31
32
33
C6 valdiklio
plokštė
123
Tiekiamo oro
slėgio jutiklis
123
Šalinamo oro
slėgio jutiklis
31
32
33
34
35
36
C5 main
module
123
Supply air
pressure
sensor
123
Exhaust air
pressure
sensor
31
32
33
34
35
36
C5 главный
модуль
123
Датчик
давления
приточного
воздуха
123
Датчик
давления
вытяжного
воздуха
28
29
30
31
32
33
C6 controller
board
123
Supply air
pressure
sensor
123
Exhaust air
pressure
sensor
28
29
30
31
32
33
Плата
контроллера C6
123
Датчик
давления
приточного
воздуха
123
Датчик
давления
вытяжного
воздуха
3a pav. Slėgio jutiklių prijungimo prie C5 valdiklio schema
31
32
33
34
35
36
C5 pagrindinė
plokštė
123
Tiekiamo oro
slėgio jutiklis
123
Šalinamo oro
slėgio jutiklis
28
29
30
31
32
33
C6 valdiklio
plokštė
123
Tiekiamo oro
slėgio jutiklis
123
Šalinamo oro
slėgio jutiklis
31
32
33
34
35
36
C5 main
module
123
Supply air
pressure
sensor
123
Exhaust air
pressure
sensor
31
32
33
34
35
36
C5 главный
модуль
123
Датчик
давления
приточного
воздуха
123
Датчик
давления
вытяжного
воздуха
28
29
30
31
32
33
C6 controller
board
123
Supply air
pressure
sensor
123
Exhaust air
pressure
sensor
28
29
30
31
32
33
Плата
контроллера C6
123
Датчик
давления
приточного
воздуха
123
Датчик
давления
вытяжного
воздуха
3b pav. Slėgio jutiklių prijungimo prie C6 valdiklio schema

UAB KOMFOVENT pasilieka teisę atlikti pakeitimus iš anksto neįspėjus 5
VAV-18-11
4. SLĖGIO JUTIKLIŲ NUSTATYMAI
Kad VAV režimas veiktų teisingai, po jutiklių montavimo, būtina atlikti sekančius nustatymus:
1. Po elektros maitinimo įjungimo esant išjungtam įrenginiui rekomenduojama kiekvieną jutiklį nustatyti į pradi-
nę (nulinę) padėtį. Tam reikia paspausti jo viduje esantį mygtuką „ZERO SET“. Mygtuką reikia išlaikyti nuspau-
dus apie 8sek., kol užsidegs LED indikatoriaus (vėdinimo įrenginys tuo metu turi būti sustabdytas).
Indikacinis LED
Nustatymų trumpikliai
„ZERO“ mygtukas
4. pav. Slėgio jutiklių nustatymai
2. Trumpikliu nustatyti slėgių diapazoną.
Slėgio nustatymo diapazonai:
3. Nustatyti pastovaus oro kiekio palaikymo režimą („CAV“).
4. Įjungti vėdinimo įrenginį.
5. Veikiant įrenginiui, kai oro kiekis pasieks nominalią reikšmę (100 %), reikia ant slėgio jutiklių tarp 2 ir 3 kon-
taktų skaitmeniniu multimetru išmatuoti nuolatinę įtampą (žr. 4 pav.). Jeigu įtampa nepatenka į 3..9V diapazo-
ną, reikia trumpikliais pasirinkti kitą slėgio diapazoną. Rekomenduojama įtampa 6V.
Nustatyti jutiklio slėgio diapazoną galima ir be aukščiau išvardintų punktų. Tam reikia
specialiu prietaisu išmatuoti realų maksimalų slėgį ortakiuose.

UAB KOMFOVENT pasilieka teisę atlikti pakeitimus iš anksto neįspėjus
6
LT
VAV-18-11
5. VAV FUNKCIJOS AKTYVAVIMAS IR NUSTATYMAI
Prieš aktyvuojant VAV funkciją reikia sureguliuoti vėdinimo sistemoje esančius oro paskirstymo bei išleidimo
prietaisus taip, kad oras būtų paduodamas į visas vėdinamas patalpas, t. y. atidaryti visas sistemos atšakas,
kanalus, sklendes ir pan. Taip pat įrenginio valdymo pultelyje reikia padaryti tokius nustatymus.
5.1. C5 automatika
1. Įveskite jutiklių slėgio diapazoną, kurį nustatėte kaip aprašyta 4 skyriuje:
16:30
ECONOMY 1
21,3° C
21,9° C
Temperatūra
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
5s.
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
Meniu
Planavimas
Nustatymai
Apžvalga
Funkcijos
Nustatymai
Vėdinimo įrenginys
Personalizavimas
16:30
ECONOMY 1
21,3° C
21,9° C
Temperatūra
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
5s.
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
Meniu
Planavimas
Nustatymai
Apžvalga
Funkcijos
Nustatymai
Vėdinimo įrenginys
Personalizavimas
16:30
ECONOMY 1
21,3° C
21,9° C
Temperatūra
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
5s.
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
Meniu
Planavimas
Nustatymai
Apžvalga
Funkcijos
Nustatymai
Vėdinimo įrenginys
Personalizavimas
16:30
ECONOMY 1
21,3° C
21,9° C
Temperatūra
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
5s.
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
Meniu
Planavimas
Nustatymai
Apžvalga
Funkcijos
Nustatymai
Vėdinimo įrenginys
Personalizavimas
16:30
ECONOMY 1
21,3° C
21,9° C
Temperatūra
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
5s.
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
Meniu
Planavimas
Nustatymai
Apžvalga
Funkcijos
Nustatymai
Vėdinimo įrenginys
Personalizavimas
16:30
ECONOMY 1
21,3° C
21,9° C
Temperatūra
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
5s.
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
Meniu
Planavimas
Nustatymai
Apžvalga
Funkcijos
Nustatymai
Vėdinimo įrenginys
Personalizavimas
5a pav. Slėgio jutiklių diapazono įvedimas C5.1 pultelyje

UAB KOMFOVENT pasilieka teisę atlikti pakeitimus iš anksto neįspėjus 7
VAV-18-11
2. Aktyvuokite VAV funkciją ir atlikite jos kalibraciją:
16:30
ECONOMY 1
21,3° C
21,9° C
Temperatūra
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Srauto palaikymas
CAV
VAV
DCV
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Srauto palaikymas
CAV
VAV
DCV
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Pradėti
kalibravimą?
Meniu
Planavimas
Nustatymai
Apžvalga
Funkcijos
Nustatymai
Vėdinimo įrenginys
Personalizavimas
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
16:30
ECONOMY 1
21,3° C
21,9° C
Temperatūra
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Srauto palaikymas
CAV
VAV
DCV
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Srauto palaikymas
CAV
VAV
DCV
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Pradėti
kalibravimą?
Meniu
Planavimas
Nustatymai
Apžvalga
Funkcijos
Nustatymai
Vėdinimo įrenginys
Personalizavimas
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
16:30
ECONOMY 1
21,3° C
21,9° C
Temperatūra
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Srauto palaikymas
CAV
VAV
DCV
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Srauto palaikymas
CAV
VAV
DCV
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Pradėti
kalibravimą?
Meniu
Planavimas
Nustatymai
Apžvalga
Funkcijos
Nustatymai
Vėdinimo įrenginys
Personalizavimas
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
16:30
ECONOMY 1
21,3° C
21,9° C
Temperatūra
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Srauto palaikymas
CAV
VAV
DCV
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Srauto palaikymas
CAV
VAV
DCV
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Pradėti
kalibravimą?
Meniu
Planavimas
Nustatymai
Apžvalga
Funkcijos
Nustatymai
Vėdinimo įrenginys
Personalizavimas
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
16:30
ECONOMY 1
21,3° C
21,9° C
Temperatūra
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Srauto palaikymas
CAV
VAV
DCV
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Srauto palaikymas
CAV
VAV
DCV
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Pradėti
kalibravimą?
Meniu
Planavimas
Nustatymai
Apžvalga
Funkcijos
Nustatymai
Vėdinimo įrenginys
Personalizavimas
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
16:30
ECONOMY 1
21,3° C
21,9° C
Temperatūra
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Srauto palaikymas
CAV
VAV
DCV
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Srauto palaikymas
CAV
VAV
DCV
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Pradėti
kalibravimą?
Meniu
Planavimas
Nustatymai
Apžvalga
Funkcijos
Nustatymai
Vėdinimo įrenginys
Personalizavimas
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
16:30
ECONOMY 1
21,3° C
21,9° C
Temperatūra
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Srauto palaikymas
CAV
VAV
DCV
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Srauto palaikymas
CAV
VAV
DCV
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
Pradėti
kalibravimą?
Meniu
Planavimas
Nustatymai
Apžvalga
Funkcijos
Nustatymai
Vėdinimo įrenginys
Personalizavimas
Temperatūros palaikymas
Vėdinimo įrenginys
Srauto palaikymas
Laikas/Data
Jungiamumas
Atstatyti nustatymus
5b pav. Srauto palaikymo režimų keitimas ir VAV kalibracija C5.1 pultelyje
VAV funkcijos kalibracijos metu, įrenginys pasileis maksimaliu greičiu. Kalibracija trunka apie 3 minutes. Tuo
metu nekeiskite įrenginio nustatymų, neatidarinėkite įrenginio durų ar reguliavimo sklendžių. Po sėkmingos
kalibracijos įrenginys bus paruoštas dirbti VAV režimu. Norėdami išjungti VAV funkciją, pasirinkite kitą srauto
palaikymo režimą (žr. 5b pav.).

UAB KOMFOVENT pasilieka teisę atlikti pakeitimus iš anksto neįspėjus
8
LT
VAV-18-11
5.2. C6 automatika
Funkcija aktyvuojama pasirinkus VAV srauto valdymo režimą ir įvedus jutiklio slėgio diapazoną, kurį nustatėte
kaip aprašyta 4-ame skyriuje:
16:30
IŠJUNGTA
EKO AUTO
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo ...
CAV
VAV
DCV
IŠJUNGTA
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Srauto palaikymas
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Srauto palaikymas
Maks. tiekiamo oro ...
300
0 Pa
1000 Pa
Temperatūros palaikymas
Srauto palaikymas
Valdymo seka
Jungiamumas
Oro kokybės palaikymas
Išplėstiniai nustatymai
1/ 2
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo ...
CAV
VAV
DCV
IŠJUNGTA
Apžvalga
Planavimas
IŠJUNGTI
Nustatymai
Meniu
5s.
16:30
IŠJUNGTA
EKO AUTO
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo ...
CAV
VAV
DCV
IŠJUNGTA
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Srauto palaikymas
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Srauto palaikymas
Maks. tiekiamo oro ...
300
0 Pa
1000 Pa
Temperatūros palaikymas
Srauto palaikymas
Valdymo seka
Jungiamumas
Oro kokybės palaikymas
Išplėstiniai nustatymai
1/ 2
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo ...
CAV
VAV
DCV
IŠJUNGTA
Apžvalga
Planavimas
IŠJUNGTI
Nustatymai
Meniu
5s.
16:30
IŠJUNGTA
EKO AUTO
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo ...
CAV
VAV
DCV
IŠJUNGTA
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Srauto palaikymas
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Srauto palaikymas
Maks. tiekiamo oro ...
300
0 Pa
1000 Pa
Temperatūros palaikymas
Srauto palaikymas
Valdymo seka
Jungiamumas
Oro kokybės palaikymas
Išplėstiniai nustatymai
1/ 2
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo ...
CAV
VAV
DCV
IŠJUNGTA
Apžvalga
Planavimas
IŠJUNGTI
Nustatymai
Meniu
5s.
16:30
IŠJUNGTA
EKO AUTO
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo ...
CAV
VAV
DCV
IŠJUNGTA
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Srauto palaikymas
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Srauto palaikymas
Maks. tiekiamo oro ...
300
0 Pa
1000 Pa
Temperatūros palaikymas
Srauto palaikymas
Valdymo seka
Jungiamumas
Oro kokybės palaikymas
Išplėstiniai nustatymai
1/ 2
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo ...
CAV
VAV
DCV
IŠJUNGTA
Apžvalga
Planavimas
IŠJUNGTI
Nustatymai
Meniu
5s.
16:30
IŠJUNGTA
EKO AUTO
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo ...
CAV
VAV
DCV
IŠJUNGTA
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Srauto palaikymas
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Srauto palaikymas
Maks. tiekiamo oro ...
300
0 Pa
1000 Pa
Temperatūros palaikymas
Srauto palaikymas
Valdymo seka
Jungiamumas
Oro kokybės palaikymas
Išplėstiniai nustatymai
1/ 2
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo ...
CAV
VAV
DCV
IŠJUNGTA
Apžvalga
Planavimas
IŠJUNGTI
Nustatymai
Meniu
5s.
16:30
IŠJUNGTA
EKO AUTO
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo ...
CAV
VAV
DCV
IŠJUNGTA
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Srauto palaikymas
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Srauto palaikymas
Maks. tiekiamo oro ...
300
0 Pa
1000 Pa
Temperatūros palaikymas
Srauto palaikymas
Valdymo seka
Jungiamumas
Oro kokybės palaikymas
Išplėstiniai nustatymai
1/ 2
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo ...
CAV
VAV
DCV
IŠJUNGTA
Apžvalga
Planavimas
IŠJUNGTI
Nustatymai
Meniu
5s.
16:30
IŠJUNGTA
EKO AUTO
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo ...
CAV
VAV
DCV
IŠJUNGTA
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Srauto palaikymas
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Srauto palaikymas
Maks. tiekiamo oro ...
300
0 Pa
1000 Pa
Temperatūros palaikymas
Srauto palaikymas
Valdymo seka
Jungiamumas
Oro kokybės palaikymas
Išplėstiniai nustatymai
1/ 2
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo ...
CAV
VAV
DCV
IŠJUNGTA
Apžvalga
Planavimas
IŠJUNGTI
Nustatymai
Meniu
5s.
16:30
IŠJUNGTA
EKO AUTO
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo ...
CAV
VAV
DCV
IŠJUNGTA
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Srauto palaikymas
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Srauto palaikymas
Maks. tiekiamo oro ...
300
0 Pa
1000 Pa
Temperatūros palaikymas
Srauto palaikymas
Valdymo seka
Jungiamumas
Oro kokybės palaikymas
Išplėstiniai nustatymai
1/ 2
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo režimas
IŠJUNGTA
Srauto palaikymas
Srauto palaikymo ...
CAV
VAV
DCV
IŠJUNGTA
Apžvalga
Planavimas
IŠJUNGTI
Nustatymai
Meniu
5s.
5c pav. VAV srauto palaikymo režimo aktyvavimas ir nustatymai C6.1 pultelyje
Aktyvavus VAV funkciją, vėdinimo režimų nustatymuose srauto matavimo vienetai automatiškai pasikeičia
į Pa. Vėdinimas vykdomas palaikant pastovų pageidaujamą slėgį ortakyje, kuriame sumontuotas slėgio jutiklis.
Norėdami išjungti VAV funkciją, pasirinkite kitą srauto palaikymo režimą (žr. 5c pav.).

UAB KOMFOVENT we reserve the right to make changes without prior notice 9
VAV-18-11
CONTENT
INTRODUCTION........................................................................................................................... 10
1. PRESSURE SENSORS INSTALLATION .................................................................................. 10
2. PIPES CONNECTION............................................................................................................... 10
3. ELECTRICAL CONNECTION TO THE AHU............................................................................. 11
4. PRESSURE SENSORS SETTINGS ......................................................................................... 12
5. VAV FUNCTION ACTIVATION AND SETTINGS....................................................................... 13
5.1. C5 automation .................................................................................................................... 13
5.2. C6 automation .................................................................................................................... 15
EN Installation Manual

UAB KOMFOVENT we reserve the right to make changes without prior notice
10
EN
VAV-18-11
INTRODUCTION
Variable Air Volume (hereafter called as „VAV“) control mode is when air handling unit operates depending
on changeable ventilation demands in separate premises. By those demands controlled ventilation system
ensures ventilation only where is needed, therefore such air volume control mode signally reduces unit’s ex-
ploitation costs, prolongs unit’s life time, lters are less polluted.
After unit have been installed and commissioned it must be appropriately prepared according to hereunder
description clauses to ensure correct VAV mode operation.
1. PRESSURE SENSORS INSTALLATION
For VAV function operation two duct pressure sensors are needed (they are supplied together with the air han-
dling unit if VAV function is ordered) to be additionally installed with the unit: one on air supply duct, another on
exhaust. Pressure sensors installation requirements:
• sensors must be installed on the straight duct part with recommended minimum distance of two diagonals
for rectangular duct cross-section or two diameters of the circular duct correspondingly;
• it is recommended to install sensor vertically with air pipes directed downwards;
• sensor is screwed directly to the duct (refer to figure 1).
82
70
Fig. 1. Pressure sensor dimensions
2. PIPES CONNECTION
After pressure sensors have been installed in the specied place, air pipes by which air pressure is supplied to
the sensors must be connected. To each sensor one air pipe must be connected in such a way: one pipe end
directly to the sensor (see gure 2.), another pipe end is passed through the gasket of drilled hole in the duct
and inserted inside the duct.
To the sensor which is installed on supply air duct, pipe is connected to the place marked by “+” sign, anoth-
er connection marked by “-“sign remains opened. To the sensor intended for the exhaust air, pipe is connected
conversely, i.e. to “-“sign, and sensor connection marked by “+” is left opened.
Fig. 2. Pressure sensor pipes connection
It is recommended to keep the length of pipes connecting sensors with ducts as short
as possible.

UAB KOMFOVENT we reserve the right to make changes without prior notice 11
VAV-18-11
3. ELECTRICAL CONNECTION TO THE AHU
When pressure sensors are mounted, they must be connected to the automation of the AHU. If pressure
maintenance is needed in both airows, two pressure sensors must be connected. Depending on the type of
automation, electrical connections must be performed strictly according diagrams 3a or 3b.
VAV function can also run with only one pressure sensor. In that case, pressure will be maintained in the
airow, where pressure sensor is connected and the fan of other airow will follow in parallel (master-slave
conguration). Pressure sensor is connected only to these automation terminals, which corresponds to the
airow where sensor is installed.
For sensor connection it is recommended to use 3×0,5mm2shielded cable.
31
32
33
34
35
36
C5 pagrindinė
plokštė
123
Tiekiamo oro
slėgio jutiklis
123
Šalinamo oro
slėgio jutiklis
28
29
30
31
32
33
C6 valdiklio
plokštė
123
Tiekiamo oro
slėgio jutiklis
123
Šalinamo oro
slėgio jutiklis
31
32
33
34
35
36
C5 main
module
123
Supply air
pressure
sensor
123
Exhaust air
pressure
sensor
31
32
33
34
35
36
C5 главный
модуль
123
Датчик
давления
приточного
воздуха
123
Датчик
давления
вытяжного
воздуха
28
29
30
31
32
33
C6 controller
board
123
Supply air
pressure
sensor
123
Exhaust air
pressure
sensor
28
29
30
31
32
33
Плата
контроллера C6
123
Датчик
давления
приточного
воздуха
123
Датчик
давления
вытяжного
воздуха
Fig. 3a. Pressure sensor connection diagram for C5 automation
31
32
33
34
35
36
C5 pagrindinė
plokštė
123
Tiekiamo oro
slėgio jutiklis
123
Šalinamo oro
slėgio jutiklis
28
29
30
31
32
33
C6 valdiklio
plokštė
123
Tiekiamo oro
slėgio jutiklis
123
Šalinamo oro
slėgio jutiklis
31
32
33
34
35
36
C5 main
module
123
Supply air
pressure
sensor
123
Exhaust air
pressure
sensor
31
32
33
34
35
36
C5 главный
модуль
123
Датчик
давления
приточного
воздуха
123
Датчик
давления
вытяжного
воздуха
28
29
30
31
32
33
C6 controller
board
123
Supply air
pressure
sensor
123
Exhaust air
pressure
sensor
28
29
30
31
32
33
Плата
контроллера C6
123
Датчик
давления
приточного
воздуха
123
Датчик
давления
вытяжного
воздуха
Fig. 3b. Pressure sensor connection diagram for C6 automation

UAB KOMFOVENT we reserve the right to make changes without prior notice
12
EN
VAV-18-11
4. PRESSURE SENSORS SETTINGS
To ensure correct VAV mode operation after sensors installation such settings must be done:
1. After electric power has been supplied to the not switched on unit it is recommended to set each sensor to
initial (zero) position. To do that „ZERO“ button located inside the sensor must be pressed for about 8s (AHU
must be stopped at the moment of initialization).
LED
Settings jumper
“ZERO” button
Pic. 4. Pressure sensors settings
2. Set jumpers located inside the sensor to required pressure range.
Pressure ranges:
3. Set constant air volume control mode („CAV“).
4. Switch on the air handling unit.
5. When the operating unit air ow will reach nominal value (100%), voltage (DC) between 2 and 3 contacts of
pressure sensors (see Pic.4) must be measured by digital multimeter. The voltage must be in range of 3..9V
(recommended – 6V). If voltage is out of range other pressure range must be chosen with jumpers.
Sensor pressure range can be also set without referring to the descriptions presented
above. In order to do that special device for measuring maximum pressure in the ducts
must be used.

UAB KOMFOVENT we reserve the right to make changes without prior notice 13
VAV-18-11
5. VAV FUNCTION ACTIVATION AND SETTINGS
Before activating VAV function, air supply and exhaust devices of the ventilation system must be regulated and
settled to supply air to all ventilated premises, i.e. all ducts, branches, dampers, etc. must be opened. On the
control panel of the AHU following settings should be adjusted.
5.1. C5 automation
1. Enter the same pressure sensor range, that was set as stated in paragraph No. 4:
16:30
ECONOMY 1
21,3° C
21,9° C
Temperature
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
5s.
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
Menu
Scheduling
Settings
Overview
Functions
Settings
Air handling unit
Personalization
16:30
ECONOMY 1
21,3° C
21,9° C
Temperature
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
5s.
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
Menu
Scheduling
Settings
Overview
Functions
Settings
Air handling unit
Personalization
16:30
ECONOMY 1
21,3° C
21,9° C
Temperature
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
5s.
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
Menu
Scheduling
Settings
Overview
Functions
Settings
Air handling unit
Personalization
16:30
ECONOMY 1
21,3° C
21,9° C
Temperature
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
5s.
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
Menu
Scheduling
Settings
Overview
Functions
Settings
Air handling unit
Personalization
16:30
ECONOMY 1
21,3° C
21,9° C
Temperature
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
5s.
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
Menu
Scheduling
Settings
Overview
Functions
Settings
Air handling unit
Personalization
16:30
ECONOMY 1
21,3° C
21,9° C
Temperature
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
5s.
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
Menu
Scheduling
Settings
Overview
Functions
Settings
Air handling unit
Personalization
Fig. 5a. Pressure sensor range setting in the C5.1 control panel

UAB KOMFOVENT we reserve the right to make changes without prior notice
14
EN
VAV-18-11
2. Activate VAV function and perform calibration:
16:30
ECONOMY 1
21,3° C
21,9° C
Temperature
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Menu
Scheduling
Settings
Overview
Functions
Settings
Air handling unit
Personalization
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Flow control
CAV
VAV
DCV
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Flow control
CAV
VAV
DCV
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Start
calibration?
16:30
ECONOMY 1
21,3° C
21,9° C
Temperature
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Menu
Scheduling
Settings
Overview
Functions
Settings
Air handling unit
Personalization
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Flow control
CAV
VAV
DCV
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Flow control
CAV
VAV
DCV
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Start
calibration?
16:30
ECONOMY 1
21,3° C
21,9° C
Temperature
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Menu
Scheduling
Settings
Overview
Functions
Settings
Air handling unit
Personalization
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Flow control
CAV
VAV
DCV
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Flow control
CAV
VAV
DCV
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Start
calibration?
16:30
ECONOMY 1
21,3° C
21,9° C
Temperature
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Menu
Scheduling
Settings
Overview
Functions
Settings
Air handling unit
Personalization
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Flow control
CAV
VAV
DCV
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Flow control
CAV
VAV
DCV
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Start
calibration?
16:30
ECONOMY 1
21,3° C
21,9° C
Temperature
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Menu
Scheduling
Settings
Overview
Functions
Settings
Air handling unit
Personalization
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Flow control
CAV
VAV
DCV
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Flow control
CAV
VAV
DCV
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Start
calibration?
16:30
ECONOMY 1
21,3° C
21,9° C
Temperature
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Menu
Scheduling
Settings
Overview
Functions
Settings
Air handling unit
Personalization
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Flow control
CAV
VAV
DCV
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Flow control
CAV
VAV
DCV
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Start
calibration?
16:30
ECONOMY 1
21,3° C
21,9° C
Temperature
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Menu
Scheduling
Settings
Overview
Functions
Settings
Air handling unit
Personalization
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Flow control
CAV
VAV
DCV
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Flow control
CAV
VAV
DCV
Temperature control
Air handling unit
Flow control
Time/Date
Connectivity
Reset settings
Start
calibration?
Fig. 5b. Flow control mode selection and VAV calibration in the C5.1 control panel
During VAV calibration AHU will run on maximum speed. Calibration duration is approximately 3 minutes.
During this time do not change unit settings, do not open unit door or regulation dampers. After successful
calibration AHU will be ready to run in VAV mode. In order to deactivate VAV function, select any other ow
control mode (see gure 5b).

UAB KOMFOVENT we reserve the right to make changes without prior notice 15
VAV-18-11
5.2. C6 automation
Function can be activated by selecting VAV ow control mode. It is necessary to enter pressure sensor range,
that was set as stated in paragraph No. 4:
16:30
OFF
ECO AUTO
Srauto palaikymo režimas
IŠJUNGTA
Flow control
Flow control mode
CAV
VAV
DCV
OFF
Flow control mode
VAV
Max. supply pressure
300 Pa
Max. extract pressure
300 Pa
Flow control
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Flow control
Max. supply pressure
300
0 Pa
1000 Pa
Temperature control
Flow control
Control sequence
Connectivity
Air quality control
Advanced settings
1/ 2
Flow control mode
OFF
Flow control
Srauto palaikymo režimas
IŠJUNGTA
Flow control
Flow control mode
CAV
VAV
DCV
OFF
Overview
Sheduling
TURN OFF
Settings
Menu
5s.
16:30
OFF
ECO AUTO
Srauto palaikymo režimas
IŠJUNGTA
Flow control
Flow control mode
CAV
VAV
DCV
OFF
Flow control mode
VAV
Max. supply pressure
300 Pa
Max. extract pressure
300 Pa
Flow control
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Flow control
Max. supply pressure
300
0 Pa
1000 Pa
Temperature control
Flow control
Control sequence
Connectivity
Air quality control
Advanced settings
1/ 2
Flow control mode
OFF
Flow control
Srauto palaikymo režimas
IŠJUNGTA
Flow control
Flow control mode
CAV
VAV
DCV
OFF
Overview
Sheduling
TURN OFF
Settings
Menu
5s.
16:30
OFF
ECO AUTO
Srauto palaikymo režimas
IŠJUNGTA
Flow control
Flow control mode
CAV
VAV
DCV
OFF
Flow control mode
VAV
Max. supply pressure
300 Pa
Max. extract pressure
300 Pa
Flow control
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Flow control
Max. supply pressure
300
0 Pa
1000 Pa
Temperature control
Flow control
Control sequence
Connectivity
Air quality control
Advanced settings
1/ 2
Flow control mode
OFF
Flow control
Srauto palaikymo režimas
IŠJUNGTA
Flow control
Flow control mode
CAV
VAV
DCV
OFF
Overview
Sheduling
TURN OFF
Settings
Menu
5s.
16:30
OFF
ECO AUTO
Srauto palaikymo režimas
IŠJUNGTA
Flow control
Flow control mode
CAV
VAV
DCV
OFF
Flow control mode
VAV
Max. supply pressure
300 Pa
Max. extract pressure
300 Pa
Flow control
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Flow control
Max. supply pressure
300
0 Pa
1000 Pa
Temperature control
Flow control
Control sequence
Connectivity
Air quality control
Advanced settings
1/ 2
Flow control mode
OFF
Flow control
Srauto palaikymo režimas
IŠJUNGTA
Flow control
Flow control mode
CAV
VAV
DCV
OFF
Overview
Sheduling
TURN OFF
Settings
Menu
5s.
16:30
OFF
ECO AUTO
Srauto palaikymo režimas
IŠJUNGTA
Flow control
Flow control mode
CAV
VAV
DCV
OFF
Flow control mode
VAV
Max. supply pressure
300 Pa
Max. extract pressure
300 Pa
Flow control
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Flow control
Max. supply pressure
300
0 Pa
1000 Pa
Temperature control
Flow control
Control sequence
Connectivity
Air quality control
Advanced settings
1/ 2
Flow control mode
OFF
Flow control
Srauto palaikymo režimas
IŠJUNGTA
Flow control
Flow control mode
CAV
VAV
DCV
OFF
Overview
Sheduling
TURN OFF
Settings
Menu
5s.
16:30
OFF
ECO AUTO
Srauto palaikymo režimas
IŠJUNGTA
Flow control
Flow control mode
CAV
VAV
DCV
OFF
Flow control mode
VAV
Max. supply pressure
300 Pa
Max. extract pressure
300 Pa
Flow control
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Flow control
Max. supply pressure
300
0 Pa
1000 Pa
Temperature control
Flow control
Control sequence
Connectivity
Air quality control
Advanced settings
1/ 2
Flow control mode
OFF
Flow control
Srauto palaikymo režimas
IŠJUNGTA
Flow control
Flow control mode
CAV
VAV
DCV
OFF
Overview
Sheduling
TURN OFF
Settings
Menu
5s.
16:30
OFF
ECO AUTO
Srauto palaikymo režimas
IŠJUNGTA
Flow control
Flow control mode
CAV
VAV
DCV
OFF
Flow control mode
VAV
Max. supply pressure
300 Pa
Max. extract pressure
300 Pa
Flow control
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Flow control
Max. supply pressure
300
0 Pa
1000 Pa
Temperature control
Flow control
Control sequence
Connectivity
Air quality control
Advanced settings
1/ 2
Flow control mode
OFF
Flow control
Srauto palaikymo režimas
IŠJUNGTA
Flow control
Flow control mode
CAV
VAV
DCV
OFF
Overview
Sheduling
TURN OFF
Settings
Menu
5s.
16:30
OFF
ECO AUTO
Srauto palaikymo režimas
IŠJUNGTA
Flow control
Flow control mode
CAV
VAV
DCV
OFF
Flow control mode
VAV
Max. supply pressure
300 Pa
Max. extract pressure
300 Pa
Flow control
Srauto palaikymo režimas
VAV
Maks. tiekiamo oro slėgis
300 Pa
Maks. šalinamo oro slėgis
300 Pa
Flow control
Max. supply pressure
300
0 Pa
1000 Pa
Temperature control
Flow control
Control sequence
Connectivity
Air quality control
Advanced settings
1/ 2
Flow control mode
OFF
Flow control
Srauto palaikymo režimas
IŠJUNGTA
Flow control
Flow control mode
CAV
VAV
DCV
OFF
Overview
Sheduling
TURN OFF
Settings
Menu
5s.
Fig. 5c. Activation and settings of VAV ow control mode in the C6.1 control panel
After activation of VAV function, in the settings of the operation mode, air measuring units automatically will
change to Pa. AHU will run maintaining requested pressure in the duct, where pressure sensor is connected.
In order to deactivate VAV function, select any other ow control mode (see gure 5c).

UAB KOMFOVENT оставляет себе право производить изменения заранее об этом не предупредив
16
RU
VAV-18-11
СОДЕРЖАНИЕ
ВВЕДЕНИЕ................................................................................................................................... 17
1. МОНТАЖ ДАТЧИКОВ ДАВЛЕНИЯ.......................................................................................... 17
2. ПРИСОЕДИНЕНИЕ ТРУБОК................................................................................................... 17
3. ЭЛЕКТРИЧЕСКОЕ ПОДКЛЮЧЕНИЕ К ВЕНТ. УСТАНОВКЕ ................................................. 18
4. НАСТРОЙКИ ДАТЧИКОВ ДАВЛЕНИЯ.................................................................................... 19
5. АКТИВАЦИЯ И НАСТРОЙКИ ФУНКЦИИ VAV ........................................................................ 20
5.1. Автоматика C5................................................................................................................... 20
5.2. Автоматика C6................................................................................................................... 22
RU Инструкция по установке

UAB KOMFOVENT оставляет себе право производить изменения заранее об этом не предупредив 17
VAV-18-11
ВВЕДЕНИЕ
Режим управления переменным расходом возду ха ( да лее VAV – англ.: Variable Air Volume) – когда венти-
ляционная установка работает в зависимости от изменяющихся потребностей вентиляции в различных
помещениях. По потребности управляемая вентиляционная система обеспечивает вентиляцию только
там, где это необходимо, поэтому такой способ поддержания расходов воздуха значительно снижает
эксплуатационные расходы установки, продлевает срок ее службы, меньше загрязняются фильтры.
После монтажа и запуска вентиляционной установки необходимо соответственно, руководствуясь
нижеследующими пунктами, подготовить установку к тому, чтобы режим VAV работал надлежащим
образом.
1. МОНТАЖ ДАТЧИКОВ ДАВЛЕНИЯ
Для работы функции VAV необходимы канальные датчики давления (комплектуются вместе с установкой
при заказе функции VAV), которые необходимо дополнительно смонтировать на установке: один на воз-
духоводе приточного воздуха, другой – вытяжного воздуха. Требования к монтажу датчиков давления:
• датчик необходимо монтировать на прямой части воздуховода, рекомендуемая минимальная дли-
на прямого отрезка – две диагонали прямоугольного воздуховода или два диаметра круглого;
• рекомендуется монтировать датчик в вертикальном положении, воздушными трубками вниз;
• датчик прикручивается прямо к воздуховоду двумя винтами для жести (см. рис. 1);
82
70
Рис. 1. Габариты датчика давления
2. ПРИСОЕДИНЕНИЕ ТРУБОК
После того, как датчики давления смонтированы в предусмотренных местах, необходимо присоединить
трубки, по которым воздушное давление подается на датчики. Для каждого датчика необходимо присоеди-
нить по одной трубке, один конец которой присоединяется непосредственно к датчику (см. рис. 2), второй
конец трубки, просверлив отверстие в воздуховоде, проталкивается через уплотнение внутрь воздуховода.
Для датчика, прикрепленного к воздуховоду приточного воздуха, трубка присоединяется в месте,
обозначенном знаком «+», второе присоединение «-» оставляется открытым. Для датчика, предна-
значенного для вытяжного воздуха, трубка присоединяется наоборот – в обозначенном «-», а присо-
единение датчика, обозначенное «+», оставляется открытым.
Рис. 2. Присоединение трубок датчика давления
Рекомендуется, чтобы трубки, соединяющие датчики с воздуховодами, были как
можно короче.

UAB KOMFOVENT оставляет себе право производить изменения заранее об этом не предупредив
18
RU
VAV-18-11
3. ЭЛЕКТРИЧЕСКОЕ ПОДКЛЮЧЕНИЕ К ВЕНТ. УСТАНОВКЕ
Когда датчики давления смонтированы, их нужно подключить к автоматике установки. Если нужна
поддержка давления в обоих потоках воздуха – нужно подключить два датчика давления. Датчики
подключаются строго по схеме 3а или 3b, в зависимости от типа автоматики установки.
Функция VAV также может работать только с одним датчиком давления. В таком случае поддержи-
ваться будет давление только того воздушного потока, в котором смонтирован датчик, а вентилятор
другого потока будет управляться параллельно (конфигурация «master-slave»). Датчик давления под-
ключается ко клеммам автоматики, которые соответствуют тому потоку где он смонтирован.
Для подключения датчика рекомендуется использовать экранированный кабель 3×0,5 мм2.
31
32
33
34
35
36
C5 pagrindinė
plokštė
123
Tiekiamo oro
slėgio jutiklis
123
Šalinamo oro
slėgio jutiklis
28
29
30
31
32
33
C6 valdiklio
plokštė
123
Tiekiamo oro
slėgio jutiklis
123
Šalinamo oro
slėgio jutiklis
31
32
33
34
35
36
C5 main
module
123
Supply air
pressure
sensor
123
Exhaust air
pressure
sensor
31
32
33
34
35
36
C5 главный
модуль
123
Датчик
давления
приточного
воздуха
123
Датчик
давления
вытяжного
воздуха
28
29
30
31
32
33
C6 controller
board
123
Supply air
pressure
sensor
123
Exhaust air
pressure
sensor
28
29
30
31
32
33
Плата
контроллера C6
123
Датчик
давления
приточного
воздуха
123
Датчик
давления
вытяжного
воздуха
Рис. 3a. Схема подключения датчиков давления к автоматике C5
31
32
33
34
35
36
C5 pagrindinė
plokštė
123
Tiekiamo oro
slėgio jutiklis
123
Šalinamo oro
slėgio jutiklis
28
29
30
31
32
33
C6 valdiklio
plokštė
123
Tiekiamo oro
slėgio jutiklis
123
Šalinamo oro
slėgio jutiklis
31
32
33
34
35
36
C5 main
module
123
Supply air
pressure
sensor
123
Exhaust air
pressure
sensor
31
32
33
34
35
36
C5 главный
модуль
123
Датчик
давления
приточного
воздуха
123
Датчик
давления
вытяжного
воздуха
28
29
30
31
32
33
C6 controller
board
123
Supply air
pressure
sensor
123
Exhaust air
pressure
sensor
28
29
30
31
32
33
Плата
контроллера C6
123
Датчик
давления
приточного
воздуха
123
Датчик
давления
вытяжного
воздуха
Рис. 3b. Схема подключения датчиков давления к автоматике C6

UAB KOMFOVENT оставляет себе право производить изменения заранее об этом не предупредив 19
VAV-18-11
4. НАСТРОЙКИ ДАТЧИКОВ ДАВЛЕНИЯ
Чтобы режим VAV работал надлежащим образом, после монтажа датчиков необходимо выполнить
следующие настройки:
1. После включения электропитания при выключенной установке рекомендуется каждый датчик уста-
новить в начальное (нулевое) положение. Для этого необходимо нажать находящуюся внутри него
кнопку ZERO SET. Кнопку нужно удерживать в нажатом состоянии около 8 сек., пока не загорится
индикатор LED (вент. установка должна быть выключена во время настройки начального положения
датчика).
Индикатор LED
Замыкатели настроек
Кнопка ZERO
Рис 4. Настройки датчиков давления
2. С помощью замыкателя установить диапазон давлений.
Диапазоны настройки давления:
3. Установить режим поддержания постоянного расхода воздуха (CAV).
4. Включить вентиляционную установку.
5. При работающей установке, когда расход воздуха достигнет нормального значения (100 %), необ-
ходимо на датчиках давления между 2 и 3 контактом цифровым мультиметром измерить постоянное
напряжение (см. рис. 4). Если напряжение не попадает в диапазон 3..9 V, необходимо с помощью за-
мыкателей выбрать другой диапазон давления. Рекомендуемое напряжение – 6 V.
Установить диапазон датчика давления можно и без вышеупомянутых пунктов.
Для этого надо специальным прибором измерить реальное максимальное дав-
ление в воздуховодах.

UAB KOMFOVENT оставляет себе право производить изменения заранее об этом не предупредив
20
RU
VAV-18-11
5. АКТИВАЦИЯ И НАСТРОЙКИ ФУНКЦИИ VAV
Перед тем как активировать функцию VAV, необходимо отрегулировать имеющиеся в вентиляционной
системе устройства распределения и выпуска воздуха таким образом, чтобы воздух поступал во все
вентилируемые помещения, т.е. открыть в системе все отводы, каналы, заслонки и проч. На пульте
управления вент.установки сделайте следующие настройки.
5.1. Автоматика C5
1. Введите тот диапазон датчика давления, который установили по описанию в разделе 4:
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
16:30
ECONOMY 1
21,3° C
21,9° C
Температура
Меню
Планирование
Настройки
Обзор
Функции
Настройки
Вентустановка
Персонализация
Температурнуй режим
Вентустановка
Режим упр. потоком
Время/Дата
Соединения
Сбросить настройки
5s.
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
16:30
ECONOMY 1
21,3° C
21,9° C
Температура
Меню
Планирование
Настройки
Обзор
Функции
Настройки
Вентустановка
Персонализация
Температурнуй режим
Вентустановка
Режим упр. потоком
Время/Дата
Соединения
Сбросить настройки
5s.
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
16:30
ECONOMY 1
21,3° C
21,9° C
Температура
Меню
Планирование
Настройки
Обзор
Функции
Настройки
Вентустановка
Персонализация
Температурнуй режим
Вентустановка
Режим упр. потоком
Время/Дата
Соединения
Сбросить настройки
5s.
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
16:30
ECONOMY 1
21,3° C
21,9° C
Температура
Меню
Планирование
Настройки
Обзор
Функции
Настройки
Вентустановка
Персонализация
Температурнуй режим
Вентустановка
Режим упр. потоком
Время/Дата
Соединения
Сбросить настройки
5s.
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
16:30
ECONOMY 1
21,3° C
21,9° C
Температура
Меню
Планирование
Настройки
Обзор
Функции
Настройки
Вентустановка
Персонализация
Температурнуй режим
Вентустановка
Режим упр. потоком
Время/Дата
Соединения
Сбросить настройки
5s.
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500 Pa
Advanced flow control
Nominal supply pressure
0 Pa
0 Pa
Nominal exhaust pressure
Supply boost (+15%)
Exhaust boost (+15%)
VAV sensor range
500
100 Pa
5000 Pa
16:30
ECONOMY 1
21,3° C
21,9° C
Температура
Меню
Планирование
Настройки
Обзор
Функции
Настройки
Вентустановка
Персонализация
Температурнуй режим
Вентустановка
Режим упр. потоком
Время/Дата
Соединения
Сбросить настройки
5s.
Рис. 5a. Установка диапазона датчика давления на пульте C5.1
Table of contents
Languages:
Other Komfovent Controllers manuals
Popular Controllers manuals by other brands

Helios
Helios KWL-BE operating instructions

maxon motor
maxon motor ESCON Module 50/4 EC-S Hardware reference

National Instruments
National Instruments PXI NI PXI-8105 user manual

SMC Networks
SMC Networks ITV1000-IL Series Operation manual

Black & Decker
Black & Decker BDJS450IAU instruction manual

Sensibo
Sensibo Sensibo Air manual