KOOLCOM
Specifications (DCU 4CH)
• Maximum joint load on the damper motor outputs:
24V (AC/DC) model: 3A
230V AC model: 0.5A
• Maximum load in the detection zone: 100mA per zone / 300 mA combined
• Maximum consumption (without detector or damper):
24V (AC/DC) model: 100mA@24V DC
230V AC model: 70mA@230V AC
• Auxiliary Relays (FAN AND ALARM):
24V (AC/DC) model: 5 A@24V DC
230V AC model: 5 A@230V AC (for resistive loads)
• Protected against short circuits and ESDs at zone connections, re damper contacts and ModBus.
• MODBUS:
- Device type: Slave
- ModBus implementation: RTU on RS-485
- Maximum number of DCUs (without repeater): 32
- Default conguration: 9600bps 8E1
- Bus data transfer speed can be congured both on the PCB and via ModBus.
- Termination integrated in internal PCB, can be activated by jumper.
- Typical response time: <10 ms.
• Installer push-button on the panel to:
- Perform tests and set up.
- Reset alarms from the DCU itself: a laptop is not required to reset alarms if the operator is at the DCU.
• Zone Connection:
- Protected against short circuits and ESDs.
- Monitored: If the wiring fails or the detector is disassembled, monitoring allows problems to be detected and
highlighted.
- Most smoke detectors are supported, including both those that are self-limiting and those that need current to be
limited in the control panel.
- Automatic detection in the zone: it is not necessary to place a resistance at the terminals or to simulate a fault if
the zone is not in use.
- Smoke detector test mode: allows smoke detectors to be tested without the DCU activating the re alarms.
• Automatic re damper testing with programmable test periods.
• Automatic detection of dampers and zones: it is not necessary to bridge or to simulate a fault if the zone is not in use.
9