KOOLAIR KOOLCOM User manual

series
Motor-driven
fire damper
monitoring systems
KOOLCOM
www.koolair.com

KOOLCOM
KOOLCOM fire damper monitoring system
CONTENTS
Description 2
General system schematic diagram 3
System components 4
KHUK connection schematic diagram 14
Accessories 17
Coding 18
Environment and guarantee 19
1

KOOLCOM
KOOLCOM fire damper monitoring system.
Introduction
KOOLCOM is an electronic control system for re dampers that allows
the condition and functionality of each re damper to be periodically and
automatically monitored and checked. It can also close the dampers
should the re alarm be activated.
While this system is capable of being managed by a BMS (Building
Management System) system, KOOLCOM can also work in Standalone
mode, i.e., operate autonomously without the need for a BMS or any
external maintenance personnel.
HUB Design Concept
KOOLCOM is the only system on the market whose installation
is based on the HUB design concept (a central communications hub).
This allows:
- Control of up to 31,616 re dampers.
- Greater data communication speed (32 times faster than systems
without this arrangement).
- Simple alarm wiring.
Technical specications
- Control electronics for 1 to 4 re dampers (DCU)
- Control electronics for 24 V (AC and DC) and 230 V AC dampers
- Autonomous or interactive with the central re alarm system
- Programmable periodic checks
- Supply fan actuator, congurations for extract fans and smoke
extract by means of an external contact.
- MODBUS Communication. Adjustable velocity. Integrated
bus terminator.
- Alarm input/output. Dry contact.
- Test mode for smoke detectors
- Segregated graphic console.
Graphic console
Communication control unit
KHUK
Fire damper control unit
DCU 1CH
2

KOOLCOM
General schematic diagram of the KOOLCOM
monitoring system.
BMS
MODBUS-USB
Power
DCU1
DCU32
(Possible connections
for 1 to 32 DCUs).
(Possible connections
for 1 to 32 DCUs).
DCU1
DCU32
(Possible connections
for 1 to 32 DCUs).
(Possible connections
for 1 to 247 KHUKs).
Power
DCU1
DCU32
DCU1CH
DCU4CH
CONSOLE
Bus
ModBus
KHUK
Note: If the KHUK alarm input is connected to a re panel, the modbus wiring between KHUK and DCUs, and between
KHUK and the BMS, must be ame retardant.
A - Power Connection-KHUK. 24V. 2 Wires. Observe polarity +24V and GND(-).
B - KHUK-RESET PUSH BUTTON. 24V.2 Wires. Observe polarity RESET and +24V
C - KHUK- INPUT FROM ALARM PANEL. 2 Wires. Observe polarity. +24V and ALARM.
D - KHUK-KHUK. ModBus. 3 Wires. Observe polarity A+, B- and GND.
E - KHUK-DCU. ModBus. 3 Wires. Observe polarity A+, B- and GND.
F - DCU-FIRE DAMPER. 2 Wires contacts + 2 Wire Motor.
G - DCU-SMOKE DETECTOR. 2 Wires.
H - DCU-Power 220V. 2 Wires.
I - KHUK-CONSOLE. 2 Wires. No polarity.
J - KHUK-BMS. ModBus.
K - DCU-GATE. 3 wires + 2 wires Motor.
AWG20 (0.5mm2).
AWG26 (0.13mm2).
AWG26 (0.13mm2).
0.2mm2.
0.2mm2.
Contacts AWG206 (0.13mm2)/ Motor AWG20 (0.5mm2).
AWG20 (0.5mm2).
AWG20 (0.5mm2).
AWG20 (0.5mm2).
0.2mm2.
Contacts AWG206 (0.13mm2) / Motor AWG20 (0.5mm2).
Minimum cross sections for a maximum length of 100m. For longer lengths refer to standard values A.W.G. ModBus:
3 Wires. RS-485 specic cable, minimum 3 conductors + screen. Nominal impedance 100-120 ohms. AWG24 (0.2mm2
section, 0.51mm diameter, twisted).
Note: If the Alarm Input of the DCU is used, use 2 wires AWG26 (0.13mm2).
3

KOOLCOM
System components.
Damper Control Unit (DCU 1CH)
DAMPER CONTROL UNIT 1 CHANNEL (DCU 1CH)
DCU 1CH (Damper Control Unit, 1 Channel) are devices used to send commands and
supervise motorised re dampers, which by means of commands sent through the
ModBus allow them to be automated and controlled.
They are integrated in the KOOLCOM re damper control and supervision system. This
system is completed with KHUK units (KoolCom Hub Unit KoolAir), which allow DCUs
(1CH or 4CH) to be grouped in sets of 32 units, and connects the colour, touch screen
consoles.
Each DCU 1CH has:
• 1 input for a conventional smoke detector (zone).
• 1 output for re damper in two available formats:
• Direct connection for Belimo motors.
• Universal motor connection.
• 1 power input.
• 1 ModBus connection.
• Models:
• 24V (AC/DC) - 100-DCK300: For 24V re damper motor.
• 230V AC - 100-DCK400: For 230V power supply damper motor.
The DCU contains the control electronics for the dierent re dampers. KOOLCOM oers two models which allow either 1,
or up to 4 dampers to be controlled by the same device.
Materials:
− Casing: ABS (-40°C | 100°C).
− Cable inlet: Nylon 6/6 and TPE.
Waterproong:
− Box: IP 54
− Cable inlet: IP 67/68
4

KOOLCOM
Specifications (DCU 1CH)
• Maximum load on the damper motor output:
24V (AC/DC) model: 3A
230V AC model: 0.5A
• Maximum load in the detection zone: 100mA
• Maximum power consumption (without detector or damper):
24V (AC/DC) model: 100mA@24V 0.72W
230V AC model: 70mA@230V 0.88W
• Protected against short circuits and ESDs at zone connections, re damper contacts, and ModBus.
• MODBUS:
- Device type: Slave
- ModBus implementation: RTU on RS-485
- Maximum number of DCUs (without repeater): 32
- Default conguration: 9600bps 8E1
- Bus data transfer speed can be congured both on the PCB and via ModBus.
- Integrated termination in PCB, can be activated by jumper.
- Typical response time: <10 ms.
• Installer push-button on the front panel to:
- Perform tests and set up from the front panel.
- Reset alarms from the DCU itself: a laptop is not required to reset alarms if the operator is present at the DCU.
• Zone Connection:
- Protected against short circuits and ESDs.
- Monitored: If there is a wiring failure or the detector is disassembled, monitoring allows the problem to be
detected and highlighted.
- Most smoke detectors are supported, including both those that are self-limiting and those that need current to be
limited in the control panel.
- Automatic detection in the zone: it is not necessary to place a resistance at the terminals or to simulate a fault if
the zone is not in use.
- Smoke detector test mode: allows smoke detectors to be tested without the DCU triggering the re alarms.
• Automatic re damper testing with programmable test intervals.
• Automatic detection of re damper and zone: it is not necessary to bypass the damper or simulate a fault if the zone
is not in use.
• Clearly indicated connections next to each connector.
5

KOOLCOM
Damper Control Unit 1 channel (DCU 1CH)
The universal damper connection is a 5-wire connection:
o Contacts:
- S4+S1: can be connected inside the damper.
- S2 and S6: Are the normally open contacts of the matching limit switches.
o Motor:
- COM: common, negative (or neutral in DCU 230V)
- MOT: positive (or phase in DCU 230V)
MOT: normally not used, it is the same signal as MOT but with inverse logic.
The output connections to the damper motor are not dry contacts, but are already powered to supply the voltage needed
to power the motor: 24V o 230V, as per the DCU model.
Binary ModBus
address
ModBus
termination
activation
Default load
values
Input
24 AC/DC
Smoke
detector
connector
Connection
ModBus
Cable tie
230v Input
230v AC
Direct
connection
Belimo / Siemens
Universal
connection
Motor Contacts
6

KOOLCOM
Damper Control Unit 1 channel connection
(DCU 1CH): two versions (24V / 230V)
Power
24V
100-DCK300 - 24V:
100-DCK400 - 230V:
Power
220V
ModBus IN
ModBus OUT
KHUK
DCUs
DETECTOR
Contacts Motor
DAMPER
Power supply 230V (cable tie is essential) or 24V. 2 wires.
ModBus. 3 wires.
2 Wires.
Contacts 3 wires + motor supply 2 wires.
7

KOOLCOM
System components
Damper Control Unit 4 channel (DCU 4CH)
DCU 4CH (Damper Control Unit, 4 Channel) are devices used to send
commands and supervise up to 4 motor-driven re dampers and 4 smoke
detectors, which, by means of commands sent through the ModBus, allow
them to be automated and controlled
They are integrated in the KOOLCOM system for controlling and supervising
motor-driven re dampers and four smoke detectors (zones). This system is
completed with KHUK units (KoolCom Hub Unit KoolAir), which allow DCUs
to be grouped (1CH or 4CH) in sets of 32 units, in addition to connecting the
colour, touch screen consoles.
Each DCU 4CH has:
• 4 inputs for a conventional smoke detector.
• 4 outputs for re dampers. Direct connection from motors.
• 1 power input.
• 1 ModBus connection.
• 24V (AC/DC) and 230V AC models
• Damper test button
• Dry contact for external alarm input
• Dry contact for supply/extract fan
• Dry contact indicating alarm detected
• Visual indication of the status of all the elements by means of LEDs on the board
8

KOOLCOM
Specifications (DCU 4CH)
• Maximum joint load on the damper motor outputs:
24V (AC/DC) model: 3A
230V AC model: 0.5A
• Maximum load in the detection zone: 100mA per zone / 300 mA combined
• Maximum consumption (without detector or damper):
24V (AC/DC) model: 100mA@24V DC
230V AC model: 70mA@230V AC
• Auxiliary Relays (FAN AND ALARM):
24V (AC/DC) model: 5 A@24V DC
230V AC model: 5 A@230V AC (for resistive loads)
• Protected against short circuits and ESDs at zone connections, re damper contacts and ModBus.
• MODBUS:
- Device type: Slave
- ModBus implementation: RTU on RS-485
- Maximum number of DCUs (without repeater): 32
- Default conguration: 9600bps 8E1
- Bus data transfer speed can be congured both on the PCB and via ModBus.
- Termination integrated in internal PCB, can be activated by jumper.
- Typical response time: <10 ms.
• Installer push-button on the panel to:
- Perform tests and set up.
- Reset alarms from the DCU itself: a laptop is not required to reset alarms if the operator is at the DCU.
• Zone Connection:
- Protected against short circuits and ESDs.
- Monitored: If the wiring fails or the detector is disassembled, monitoring allows problems to be detected and
highlighted.
- Most smoke detectors are supported, including both those that are self-limiting and those that need current to be
limited in the control panel.
- Automatic detection in the zone: it is not necessary to place a resistance at the terminals or to simulate a fault if
the zone is not in use.
- Smoke detector test mode: allows smoke detectors to be tested without the DCU activating the re alarms.
• Automatic re damper testing with programmable test periods.
• Automatic detection of dampers and zones: it is not necessary to bridge or to simulate a fault if the zone is not in use.
9

KOOLCOM
Damper Control Unit 4 channel (DCU 4CH)
The universal damper connection uses 4 wires:
o Contacts:
- S2 and S6: are the normally open contacts of the matching limit switches.
o Motor:
- COM + S4 + S1: common, negative (or neutral in DCU 230V) attached to cables S4 and S1 of the motor
contacts.
- MOTX: positive (or phase in DCU 230V)
MOTX: normally not used, it is the same signal as MOT but with inverse logic.
The output connections to the damper motor are not dry contacts, but are already powered to supply the voltage needed
to power the motor: 24V o 230V, as per the DCU model.
INSTALLER
PUSH BUTTON
INPUT POWER 230V
CONTACTS
DAMPER 2
S2
S6
Model
230V AC
CONTACTS
DAMPER 1
S2
S6
CONTACTS
DAMPER 3
S2
S6
CONTACTS
DAMPER 4
S2
S6
ALR DAMPER DRY
CONTACT
OUTPUT
activated in the event of
an alarm
MODBUS ADDRESS
CONFIGURATION
FAN DAMPER
DRY CONTACT
OUTPUT
supply, can be congured
for extract
SMOKE
DETECTOR 4
SMOKE
DETECTOR 3
SMOKE
DETECTOR 2
SMOKE
DETECTOR 1
MOTOR DAMPER 2
MOT2
COM + S4 +S1
MOTOR DAMPER 1
MOT1
COM + S4 +S1
MOTOR DAMPER 3
MOT3
COM + S4 +S1
MOTOR DAMPER 4
MOT4
COM + S4 +S1
MODBUS
A+
B-
COM
ENTRY OF
EXTERNAL ALARM
(Contact N.C. dry)
10

KOOLCOM
Damper Control Unit 1 channel connection
(DCU 4CH): two models (24V / 230V)
100-DCK600 - 230V AC:100-DCK500 - 24V AC/DC:
Power
230V
Power
24V
Alarm input
Exterior
ModBus
IN
ModBus OUT
DCUs
Contacts
Contacts
Contacts
Contacts
Motor
Motor
Motor
Motor
DETECTORS
DAMPERS DAMPERS
Z1 Z2 Z3 Z4
C1
C2
C3
C4
230V AC or 24V AC/DC supply. 2 wires.
ModBus. 3 wires.
2 wires.
2 wires.
2 wires contacts (S2, S6) + 2 wires motor supply (COM+S4+S1), MOTx.
11

KOOLCOM
System components.
KHUK (HUB)
The KHUK is a Modbus hub device that occupies a single address, allows up to 128 re
dampers and 128 smoke detectors (32 DCU-4CH units) to be managed.
Each KHUK has:
- 1 connection to the Koolcom console.
- Direct connection to re panel:
• Alarm activation input.
• Alarm reset input.
• NO alarm relay output (Max 8Amp).
- 1 24V DC power input.
- Maximum consumption: 100–UCK000: 125mA@24v
- 1 ModBus connection on RS485 for DCUs.
- 1 ModBus connection on RS485 for BMS.
- ModBus:
Type of device going to DCUs: Master
Type of device going to the BMS: Slave
ModBus implementation: ModBus RTU on RS-485
Maximum number of DCUs: 32
Default conguration: 9600bps 8E1
The KHUK is always powered by a 24V DC power supply.
12

KOOLCOM
System components. Graphic console
The KOOLCOM graphic console allows monitoring and control of DCUs connected to the associated KHUK,
facilitating the monitoring and control of re dampers and smoke detectors (zones).
The console allows information on the overall status of the system and each connected DCU to be displayed, as well as
the basic parameters to be congured and managed. (* Only available in installations that include KHUKs).
KOOLCOM Graphic Console with 3.2” display. Surface mounted version. Specic ush mounted box available
for ush mounting.
CHARACTERISTICS:
- Surface mounted or ush (optional)
- Powered from the KHUK (No external power supply required).
- Dimensions: 79x119x16 mm.
- TFT 3.2” display. 65,536 colours. 4R resistant touch panel.
- Resolution: 400x240 pixels.
- Testing, control and monitoring of up to 128 re dampers and 128 smoke detectors (32 No. DCU 4CH).
- Autonomous or integrated with the central re alarm system
- Programmable periodic checks
- Global and localised indication of the state of the zones (smoke detectors) and the re dampers.
13

KOOLCOM
KHUK connection schematic
One KHUK has connections for up to 32 DCUs (maximum 128 dampers and 128 detectors), the wall mounted graphic
console and a BMS. It can interact with the central re alarm system with external alarms going to the KHUK and detected
alarm coming from the KHUK.
CONSOLE
Power
supply
FIRE PANEL N.O. ALARM
OUTPUT MODBUS TO BMS
MODBUS TO THE DCU
Alarm activation
Reset alarm
MODBU-USB
1-32 DCUs
BMS
14

KOOLCOM
KHUK AND DCUs
Three wires with polarity that connect exclusively to the DCUs. The KHUK contains the MODBUS termination. By inserting
the MBUS TERM bridge into the furthest DCU, the two necessary terminations are achieved. Dierent DCU models (DCU-
1CH and DCU-4CH) can be mixed in the same bus.
For the modbus wiring, RS-485 cable must always be used; available from various manufacturers.
DCU 32
DCU 4CH
DCU 1
KHUK
DCU 1CH
ModBus to DCUs
Connect the DCUs one
to another. Maximum 32
DCUs per KHUK.
The furthest DCU must have
The MBUS TERM bridge inserted
1 - 32 DCUs
MOD-BUS Topology
Daisy Chain topology must be used wherever possible. If this is not feasible at any point, a Backbone with stubs can also
be used.
In cases where backbone with stubs topology is used, the stubs should be as short as possible and never exceed 10
meters.
15

C RELE
ON RELE
KOOLCOM
KHUK and alarms
Fire Alarm and Reset Input: When the +24V from the
source is received at the alarm input, the KHUK considers
there to be a re alarm external to the system (not activated
by the smoke detectors). It will activate the alarm input on
each DCU connected to the KHUK, resulting in the closing
of all connected dampers.
N.O. Alarm Relay Output: Volt-free contacts with a
maximum switching capacity of 8Amp, which are closed
when any DCU informs the KHUK of the occurrence of an
alarm. They are usually connected to the central re alarm
system, which awaits the closure of these contacts.
CENTRAL
FIRE ALARM
N.O. Alarm
Output
KHUK
CENTRAL
FIRE ALARM
KHUK
Power supply
Alarm activation
Reset
alarm
Three wires with polarity that are connected to a PC that contains an available RS485 port. The third wire COM (Ref.) is the
negative of the KHUK supplier (GND).
KHUK and BMS
KHUK
BMS
USB-MODBUS
16

KOOLCOM
Accessories
This section describes the accessories that may be necessary during installation.
Cable MODBUS
This depends on the specic conditions of each installation,
especially the level of electrical noise in the zones which the wiring
passes through, the distance to be covered and the chosen connection
speed. We recommend that RS-485-specic cable always be used.
In general the cable specications will comply with:
- be twisted pair (or pairs) cable.
- have at least three conductors + screen.
- nominal impedance: 100-120 ohms
- AWG24 (section 0.2mm2, diameter 0.51mm)
- screened
MODBUS Extender/Isolator
Optical MODBUS Extender / Isolator. In cases with long cable runs,
or even to facilitate easy fault detection in the installation, this allows
the connection wiring between the KHUK and the dierent DCUs to be
expanded and isolated.
USB-MODBUS Interface
Allows the KOOLCOM system and a computer to be connected if
there is no integrated RS485 port.
17

KOOLCOM
Accessories
CODE DESCRIPTION
100-UCK000 KOOLCOM HUB
100-TCK000 KOOLCOM GRAPHIC DISPLAY
100-DCK500 DAMPER CONTROL UNIT KOOLCOM, 4 DAMPERS, 24V (AC/DC)
100-DCK600 DAMPER CONTROL UNIT KOOLCOM, 4 DAMPERS, 230V AC
100-DCK300 DAMPER CONTROL UNIT KOOLCOM, 1 DAMPER, 24V (AC/DC)
100-DCK400 DAMPER CONTROL UNIT KOOLCOM, 1 DAMPER, 230V AC
100-MBUS00 CABLE MODBUS TWISTED KOOLCOM, 3 CONDUCTORS+MESH
100-MBUS01 KOOLCOM SYSTEM OPTICAL ISOLATOR / EXTENDOR
100-MBUS02 MODBUS INTERFACE TO KOOLCOM USB
100-TCK001 KOOLCOM GRAPHIC CONSOLE BACK BOX
Graphic console back box
Non-standard back box for installations where the graphic console is to
be ush mounted instead of surface mounted.
Coding
18

KOOLCOM
Environment, guarantee and safety.
ENVIRONMENT
Never dispose of this equipment together with household waste. Electrical and electronic products contain substances that
can be harmful to the environment if not disposed of properly. The symbol of a crossed out rubbish bin indicates the special
collection of electrical appliances, diering from other urban rubbish. For correct environmental disposal, they should be
taken to specially designed collection centres at the end of their useful life. Their constituent parts are recyclable. Therefore,
observe the applicable environmental protection regulations.
You must return them to your dealer if they are being replaced by another, or dispose of them at a specialised collection
centre.
Violators are subject to the sanctions and measures established by the Law on environmental protection.
GUARANTEE
This product is covered by a legal guarantee; please contact your seller for more information.
KOOLCOM guarantees the products will conform to the technical specications for a period of 2 years, including parts and
labour, from the date of purchase included on the purchase document. The user can put the guarantee into eect at the
distributor or point of sale or by calling the customer service number. The nonconforming part or product will be repaired or
replaced by an equivalent piece or product at no cost to the customer. Any part or product changed becomes the property
of KOOLCOM. The remedied defect of the repaired product is guaranteed for a period of 6 months from the date of repair.
However, this guarantee does not apply in the following cases:
Installation or use that is not in accordance with the instructions given in this manual; incorrect connection or improper
use of the product, in particular, with accessories not designed for the purpose; abnormal wear; failure to comply with
the technical and safety standards in force in the geographical area of use; products that have received shocks or falls:
products damaged by lightning, electrical overloads, heat sources or radiation, water damage, exposure to excessive
humidity or any other outside cause; misuse or negligence; intervention, modication or repair by any person not approved
by the manufacturer or distributor CONDITIONAL TO THE LEGAL PROVISIONS, ALL WARRANTIES DIFFERENT FROM
THOSE DESCRIBED IN THIS SECTION ARE SPECIFICALLY EXCLUDED.
19
Table of contents
Popular Control System manuals by other brands

Aveo Systems
Aveo Systems Mira Connect 10 Quick install guide

Interspace Industries
Interspace Industries TheatreCue user manual

WPM
WPM 0792 Instructions for installation and operation

A1S Group
A1S Group Evo1-MCP 1 Technical manual

MUELLER CO.
MUELLER CO. Hydro-guard Operating instructions manual

Visonic
Visonic POWERMAX - quick guide