KOOLAIR SCFR Series User manual

Fire
protection
www.koolair.com

RPK
SCFR
SCFC
BDK
SMLD
CEVH SCDC GRAPHIC CONSOLE
Rectangular and circular
re dampers
Smoke extract dampers KOOLCOM fire damper
monitoring system
Circular terminal
re damper Smoke extract louvre
Fire protection
Fire protection
CONTENTS
Rectangular and circular fire dampers 2
BDK Circular terminal fire damper 34
Intumescent louvres for air transfer 40
SMLD Smoke extract dampers 44
CEVH Smoke extract dampers 55
RPK Smoke extract louvre 65
SCDC Smoke Extract Dampers 70
KOOLCOM Fire damper monitoring system 78
UL Approved fire dampers and smoke dampers 97
1

Rectangular and circular fire dampers
CONTENTS
Description 3
Declared performance 5
Applications 7
Model and dimensions 9
Accessories 14
Installation 15
Operating Mechanisms 20
Special finishes 23
Technical data 24
Coding 33
Fire protection
2

Rectangular and circular fire
dampers
Description
KOOLAIR rectangular re dampers, models SCFR-PD,
SCFR-GD, SFR3K1GT and circular re dampers, models
SCFC-PD and SCFC-GD, are approved in accordance with
the Technical Building Code according to test standard UNE
EN 1366-2 and classied according to EN 13501-3.
Fire dampers close automatically to prevent re and smoke from
spreading through ventilation ductwork to adjacent re
compartments.
The frame consists of a single sheet of sheet metal with an
internal recess reinforced by a slot sheet metal support that
prevents a thermal bridge.
The blade is made of a heat-resistant material with a
thickness that varies depending on the model, intumescent
joints and a perimeter seal.
Symmetrical dampers are designed to be installed in vertical or
horizontal enclosures irrespective of the direction of the airow.
Damper closure is operated by the breaking or smelting of a
bimetallic fusible link (-TH70) when the temperature exceeds
72 ºC.
It is reset manually in all instances except when incorporating a
servomotor with return spring and a thermoelectric fusible link
calibrated at 72 ºC.
All dampers comply with requirements of the cold smoke
leakage standard (-S).
Operation
The components of the manual operating mechanism are made
of zinc plated steel and are housed in a plastic enclosure (manual
reset).
The operating mechanism acts on the blade through a reverse
pulley and does not act directly on the blade shaft, which serves
only as a pivot. The blade operating mechanism therefore has
greater solidity and reliability.
The mechanism is offset from the blade shaft, allowing access
to the unit for maintenance and testing.
The mechanism housing is evolutive, i.e. all the operating
options can be interchanged without having to send it to the
factory.
Dampers incorporating a TH-70 fusible link and/or shunt or
undervoltage release require a manual “on-site” reset device
that allows the damper to be reset (opening) after it has been
closed. Dampers with electric motors can be reset remotely by
means of an electrical supply (24V or 230V).
SCFR-PD with motor
SCFC-PD with manual operation
with xing strips (optional)
Fire protection 3

Circular fire dampers
Fire protection
Standards
The dampers are approved in accordance with European Test Standard UNE-EN 1366-2 and European
classication standard UNE-EN 13501-3, where:
(E) Integrity
(I) Isolation
(ho) Installed in Horizontal slab. Mounted in horizontal enclosure.
(ve) Installed in wall or stud wall. Mounted in vertical enclosure.
(i ↔ o) Symmetric (independent of airow direction). Suitable for re in both directions (interior-exterior and
exterior-interior)
(S) Airtightness. Leakage through the damper closing blade <200 m3/h*m2
Option for re dampers to be supplied with airtightness C to comply with EN 1751.
Motor-driven re dampers can be integrated into the building management system (BMS) and/or re panel with the
KOOLCOM system from KOOLAIR.
To guarantee the correct re damper operation, it is essential to read and follow the recommendations in the
installation and operation manual. In addition, the installation must comply with all current national standards.
Further information and updates, as well as the installation and operating manual, can be found on our website
(www.koolair.com).
CE Marking
Koolair re dampers carry the CE marking in compliance with RPC-305/2011/EU, according to EN15650:2010.
NF Marking
The SCFR-PD, SCFR-GD, SCFC-PD and SCFC-GD models are certied under NF (NF264 Certication Standard,
NF S 61-937-5 re dampers).
4

L: 200 → 800
H: 100 → 600
d = 150 mm
ρ = 1900 kg/m³
El-120 (ve i↔o) S
(500 Pa)
L: 200 → 800
H: 100 → 600
d = 150 mm
ρ = 2000 kg/m³
EI-180 (ho i↔o) S
(500 Pa)
L: 200 → 800
H: 100 → 600 d ≥ 100 mm EI-120 (ve i↔o) S
(500 Pa)
L: 850 → 1500
H: 200 → 800
d = 150 mm
ρ = 1900 kg/m³
El-120 (ve i↔o) S
(500 Pa)
L: 850 → 1500
H: 200 → 800
d = 150 mm
ρ = 2400 kg/m³
EI-120 (ho i↔o) S
(500 Pa)
L: 200 → 1500
H: 200 → 800
d = 150 mm
ρ = 1900 kg/m³
El-180 (ve i↔o) S
(300 Pa)
SCFR-PD
CPR-2245-16
SCFR-GD
CPR-2591-16
SFR3K1GT
CPR-1493-14
Dimensions
(mm)
Dimensions
(mm)
Construction
details
Construction
details
Installation
location
Installation
location
Installation
location
Installation
Installation
Installation
Classication
Classication
Classication
Mortar
Mortar
Mortar
Mortar
Mortar
Plasterboard
Floor slab
Floor slab
Stud wall
Brick Wall
Brick Wall
Brick Wall
Fire protection
Declared performance
Rectangular re dampers
Dimensions
(mm)
Construction
details
The performance specications of our range of re dampers (rectangular and circular) are shown in the table below.
5

Ø: 100 → 355 d = 150 mm
ρ = 1900 kg/m³
El-120 (ve i↔o) S
(500 Pa)
Ø: 100 → 355 d = 150 mm
ρ = 2000 kg/m³
EI-180 (ho i↔o) S
(500 Pa)
Ø: 100 → 355 d ≥ 100 mm EI-120 (ve i↔o) S
(500 Pa)
Ø: 400 → 800 d = 150 mm
ρ = 2000 kg/m³
El-180 (ve i↔o) S
(500 Pa)
Ø: 200 → 630 d = 150 mm
ρ = 2100 kg/m³
EI-180 (ho i↔o) S
(500 Pa)
SCFC-PD
CPR-2244-16
SCFC-GD
CPR-2592-16
Declared performance
Circular re dampers
Details of supporting structure, tested on Stud wall (plasterboard):
• Fire resistance rating: EI 90.
• 2 sheets of laminated reproof plasterboard ref. KNAUF cortafuego DF thickness 12.5 mm.
• Rock wool panel ref. ProRox SL960 (ROCKWOOL).
• 2 sheets of laminated reproof plasterboard ref. KNAUF cortafuego DF thickness 12.5 mm.
• 48 mm U-shaped channels and uprights in 400 mm modules.
Key
L: Length
H: Height
Ø: Diameter
d: Wall thickness
p: Density
Construction
details
Installation
location Installation Classication
Mortar
Mortar
Mortar
Mortar
Plasterboard
Brick
Wall
Brick
Wall
Floor slab
Floor slab
Stud wall
Dimensions
(mm)
Construction
details
Installation
location Installation Classication
Dimensions
(mm)
Fire protection
6

L (mm)
200 300 400 500 600 700 800 900 1000 1100 1200 1300 1400 1500
200
300
400
500
600
700
800
H (mm)
SFR3K1GT
L (mm)
200 300 400 500 600 700 800 850 900 1000 1100 1200 1300 1400 1500
100
200
300
400
500
600
650
700
800
H (mm)
SCFR-PD
SCFR-GD
SCFR-GD
L (mm)
200 300 400 500 600 700 800
100
200
300
400
500
600
H (mm)
SCFR-PD
Applications
FIXED WALL EI-180 EI-180 (ve i↔o) S (RECTANGULAR)
FIXED WALL EI-120 (ve i↔o) S (RECTANGULAR)
The length and height of all models of rectangular re dampers increases in 50mm increments.
STUD WALL EI-120 (ve i↔o) S (RECTANGULAR)
Fire protection 7

L (mm)
200 300 400 500 600 700 800 850 900 1000 1100 1200 1300 1400 1500
100
200
300
400
500
600
650
700
800
H (mm)
SCFR-PD
(EI-180-S)
SCFR-GD
(EI-120-S)
Ø (mm)
100 125 160 200 250 315 355
SCFC-PD
Ø (mm)
100 125 160 200 250 315 355 400 450 500 560 630 650 700 710 750 800
SCFC-GD (EI-120-S)
SCFC-PD (EI-120-S)
SCFC-GD (EI-180-S)
Ø (mm)
100 125 160 200 250 315 355 400 450 500 560 630
SCFC-PD SCFC-GD
Applications
SLAB EI-120 (ho i↔o) S / EI-180 (ho i↔o) S (RECTANGULAR)
STUD WALL EI-120 (ve i↔o) S (CIRCULAR)
FIXED WALL EI-120 (ve i↔o) S / EI-180 (ve i↔o) S (CIRCULAR)
SLAB EI-120 (ho i↔o) S / EI-180 (ho i↔o) S (CIRCULAR)
Fire protection
8

H S1 S2
100 --
150 --
200 --
250 - -
300 -14
350 -39
400 -64
450 -89
500 -114
550 10 139
600 35 164
1 1 1
2
2
2
3
3
3
4
4
4
5
5
5
6
6
6
SCFR-PD Model and dimensions
SCFR-PD re dampers are available in standard sizes (duct size) with a length (L dimension) from 200 to 800 mm
increasing in 50mm increments and a height (dimension H) from 100 to 600 mm increasing in 50mm increments.
1- Galvanised steel frame
2- Damper blade
3- Mechanism/motor housing
4- Intumescent seal
5- Fixing lug for installing in slab oor (optional)
6- 30 mm ange
Drive shaft
Fire protection 9
This manual suits for next models
7
Table of contents
Other KOOLAIR Fan manuals
Popular Fan manuals by other brands

ELTA FANS
ELTA FANS H03VV-F installation guide

Hunter
Hunter 20714 Owner's guide and installation manual

Emerson
Emerson CARRERA VERANDA CF542ORB00 owner's manual

Hunter
Hunter Caraway Owner's guide and installation manual

Panasonic
Panasonic FV-15NLFS1 Service manual

Kompernass
Kompernass KH 1150 operating instructions