KSB BACnet MS/TP User manual

BACnet MS/TP Gateway
For Calio
Supplementary Operating
Manual

Legal information/Copyright
Supplementary Operating Manual BACnet MS/TP Gateway
Original operating manual
All rights reserved. The contents provided herein must neither be distributed, copied, reproduced,
edited or processed for any other purpose, nor otherwise transmitted, published or made available to a
third party without the manufacturer's express written consent.
Subject to technical modification without prior notice.
© KSB SE & Co. KGaA, Frankenthal 11/04/2018

Contents
3 of 16
BACnet MS/TP Gateway
Contents
1 General.................................................................................................................................................... 4
2 Storage.................................................................................................................................................... 5
3 Description.............................................................................................................................................. 6
3.1 Compatibility ....................................................................................................................................................6
3.2 General description ..........................................................................................................................................6
3.3 Commissioning..................................................................................................................................................6
3.3.1 Setting jumpers ....................................................................................................................................8
3.3.2 DIL switch .............................................................................................................................................8
3.3.3 Back-up battery....................................................................................................................................8
3.3.4 Error code .............................................................................................................................................9
3.3.5 Technical data ......................................................................................................................................9
4 Related Documents.............................................................................................................................. 11
4.1 Terminal diagram ...........................................................................................................................................11
5 EU Declaration of Conformity............................................................................................................. 12

1 General
4 of 16 BACnet MS/TP Gateway
1 General
This supplementary operating manual accompanies the installation/operating
manual. All information contained in the installation/operating manual must be
observed.
Table1: Relevant operating manuals
Type series Reference number of the operating/installation
manual
Calio 1157.82
Manufacturer's product
literature
For accessories and/or integrated machinery components observe the relevant
manufacturer's product literature.

2 Storage
5 of 16
BACnet MS/TP Gateway
2 Storage
If the ambient conditions for storage are met, the accessories will give reliable service
even after a prolonged period of storage. If stored properly, the product will be
protected for a maximum of 12 months.
Table2: Ambient conditions for storage
Ambient condition Value
Relative humidity 85% max. (non-condensing)
Ambient temperature -10 °C to +70 °C
1. Store the device in dry conditions, if possible in its original packaging.
2. Store the device in a dry room in which the atmospheric humidity is maintained
at a constant level (as far as this is possible).
3. Prevent excessive fluctuations in atmospheric humidity.

3 Description
6 of 16 BACnet MS/TP Gateway
3 Description
3.1 Compatibility
The BACnet PICO Modbus gateway is used to integrate Calio pumps in the BACnet
MS/TP network. Communication with the BACnet MS/TP gateway takes place via the
Modbus interface (COM) at the pump. Do not change the default Modbus settings of
the pump.
The gateway can only be used as a master on the BACnet MS/TP network.
NOTE
Only one Calio pump can be connected via each BACnet MS/TP gateway.
3.2 General description
The device is configured with the following settings at delivery:
Device ID 247000 + gateway serial number
Master node address 1
MS/TP baud rate 38400
The default device ID of the gateway used to identify the device on the BACnet
network is created based on the sum total of 247000 (fixed value) and the last 3
digits of the device’s serial number.
Example: 247000 + SN1220M0010 = 247010
The serial number is located on the side of the housing.
The device ID can be changed during operation via BACnet.
NOTE
The master node address (HW address) must be set differently for all devices on the
BACnet network.
The master node address can be set using DIP switches. (ðSection3.3.2,Page8)
3.3 Commissioning
The MS/TP baud rate and master node address are set via a DIL switch on the printed
circuit board. Open the housing to change the baud rate or master note address.
Remove the printed circuit board.

3 Description
7 of 16
BACnet MS/TP Gateway
Press
Press
Remove
Fig.1: Side view of BACnet MS/TP gateway
DANGER
Live voltage
Danger to life!
▷Only remove the printed circuit board when de-energised.
1
2
3
5
4
Fig.2: Removed electronics
1 MS/TP bus terminator jumper (must be terminated at the last station/
subscriber)
2 Modbus bus terminator jumper (not terminated at delivery)
3 RS232/RS485 mode Modbus (already set to RS485 at delivery)

3 Description
8 of 16 BACnet MS/TP Gateway
4 BACnet parameter DIL switch
5 Back-up battery
3.3.1 Setting jumpers
Only jumper 1 (BACnet MS/TP bus terminator) typically must be set, if required,
during commissioning.
3.3.2 DIL switch
Fig.3: DIL switch 4
DIP switches 1 to 7 code the master node address, and DIP switches 8 to 10 code the
baud rate in the BACnet MS/TP network.
The values are binary coded from right to left.
Table3: DIP switches for master node addressing
DIP switches Master node address
1234567
00000011
00000102
00001004
00010008
001000016
010000032
100000064
The master node address can be set from 1 to 127 using the DIP switches. It may be
necessary to activate several switches to obtain the required address.
NOTE
Master node address 0 is invalid and deletes the current configuration on the
gateway.
Table4: DIP switches for setting the baud rate
DIP switches Baud rate
8 9 10
0 0 0 4800
0 0 1 9600
0 1 0 19200
0 1 1 38400
1 0 0 56700
1 0 1 76800
1 1 0 115200
1 1 1 230400
The baud rate for the BACnet MS/TP network is set to 38400 by default.
3.3.3 Back-up battery
Insert battery of type CR2032 with the positive terminal pointing upwards. The
battery buffers the data and the real-time clock of the gateway during a power
interruption.

3 Description
9 of 16
BACnet MS/TP Gateway
CAUTION
Operation without back-up battery
System malfunction!
▷Never operate the device without a back-up battery.
3.3.4 Error code
In the event of a malfunction, the red LED indicates the respective operating
condition. If no malfunctions are present, the red LED illuminates continuously.
Otherwise, there are 3 fault statuses that are displayed with the following flash
codes:
Approx. 1 - 3 sec.
No communication with BACnet
Modbus fault (exception, timeout, broken line)
Gateway without valid configuration
When Modbus communication between the gateway and pump is interrupted, the
gateway automatically attempts to re-establish the connection every 3 minutes.
3.3.5 Technical data
Characteristic Value
Power supply 9 - 30V DC, approx. 20mA at 24V DC
Enclosure IP20
Housing design DIN rail assembly
Weight Approx. 0.1 [kg]
Dimensions W x H x D: 18 x 90 x 115 [mm]
Table5: Object list
Type-Instance Object name Value Read/Write Description
AI-1 Backup_Battery [V] R Replace battery on falling below
2.0V
AI-2 Calio_Head [m] R Head
AI-3 Calio_Flow [m³/h] R Flow rate
AI-4 Calio_Speed [rpm] R Speed
AI-5 Calio_OpHours [h] R Operating hours
AI-6 Calio_Power [W] R Power
AI-7 Calio_PumpLoad [%] R Load between 0-100%
AV-1 Calio_Setpoint [%] R/W Setpoint between 0-100%
BI-1 Calio_FaultE01 Normal / Fault R Temperature limit
BI-2 Calio_FaultE02 Normal / Fault R Overcurrent
BI-3 Calio_FaultE03 Normal / Fault R Internal fault
BI-4 Calio_FaultE04 Normal / Fault R Rotor locked
BI-5 Calio_FaultE05 Normal / Fault R Overload / adjusted speed
BI-6 Calio_FaultE06 Normal / Fault R Supply voltage too high/low
BI-7 Calio_FaultE08 Normal / Fault R Motor fault
BI-8 Calio_PumpStatus Operate / Stop R Status
BV-1 Calio_StartStop Start / Stop R/W Switch Start/Stop

3 Description
10 of 16 BACnet MS/TP Gateway
Type-Instance Object name Value Read/Write Description
DEV-xxxxxx Device_xxxxxx - R KSB Calio BACnet
FI-1 Config File CSV - R/W CSV Config File ASCII plain text
FI-2 Config Data BIN LHZ - R BINARY DATA file compressed
FI-3 Config Data SRAM - R SRAM DATA buffer
FI-4 P-BASIC File LHZ - R Pico BAS program file
compressed
FI-5 P-BASIC File - R/W Pico program file
MI-1 Modbus_Status Online / Error R FP:19200,'E',8,1,'B',1000,1000
PRG-1 P-BASIC Program Running / Halted R/W KSB Calio adaption (c)
V20150805 HHO-uha
MV-1 Calio_OpMode Eco-Mode
Const-Pr
Propor-Pr Boost
R/W Selecting the operating mode
All describable properties (see PICs) with the exception of PresentValue are
permanently saved in the gateway’s flash memory.
To ensure that values are written to the pump as required, PRG-1 P-Basic Program
must display the value “Running”.
AV-1 Calio_Setpoint, BV-1 Calio_Start/Stop and MV-1 Calio_OpMode can only write
values to the pump if Modbus is activated at the pump.
The gateway checks this periodically every 3 minutes.

4 Related Documents
11 of 16
BACnet MS/TP Gateway
4 Related Documents
4.1 Terminal diagram
1
2
3
4
5
6
Fig.4: Terminal diagram
1 Modbus RTU terminals
2 BACnet MS/TP terminals
3 Status, BACnet communication
4 Status, operation or fault
5 Service terminal terminals
6 Power supply 9 - 30 V DC
A-
B+
GND
A
B
G
Calio
Tx
Rx
GND
Modbus
RS485
NC
-
+
0-30VDC 9-30VDC
B+
A-
GND
MS/TP
NO
COM
NC
R
O
Uin
0
Run
External
0-10V
0-10V
COM
Alert
3
2
1
1
2
3
1
3
2
1
2
3
Console Service
interface
N
L
BACnet MS/TP gateway
BACnet MS/TP
provided by
customer
Fig.5: BACnet MS/TP gateway
NOTE
Always wire only one Calio pump to the gateway in a point-to-point connection.

5 EU Declaration of Conformity
12 of 16 BACnet MS/TP Gateway
5 EU Declaration of Conformity
Manufacturer: KSB SE & Co. KGaA
Johann-Klein-Straße 9
67227 Frankenthal (Germany)
The manufacturer herewith declares that the product:
BACnet MS/TP gateway
Serial number range: 2018w01 to 2019w52
▪is in conformity with the provisions of the following Directives as amended from time to time:
–Electromagnetic Compatibility Directive 2014/30/EU
The EU Declaration of Conformity was issued in/on:
Frankenthal, 1 February 2018
Joachim Schullerer
Head of Product Development Pump Systems and Drives
KSB SE & Co. KGaA
Johann-Klein-Straße 9
67227 Frankenthal




KSB SE & Co. KGaA
Johann-Klein-Straße 9 • 67227 Frankenthal (Germany)
Tel. +49 6233 86-0
www.ksb.com
1157.87/04-EN
Table of contents
Other KSB Gateway manuals