3.4 Additional requirements relating to type BN4xxx pres-
sure switches and type BP4xxx pressure limiters
The evaluation unit and downstream control current circuit are not part of our scope of sup-
ply.The following evaluation units conform to the requirements of the Association of Tech-
nical Inspection Agencies (VdTÜV) Fact Sheet No. 100.
Pepperl+Fuchs, switching amplifier:
Type KHA6-SH-Ex1, PTB 00 ATEX 2043
Type KFD2-SH-Ex1, PTB 00 ATEX 2042
The use of alternative evaluation units is within the responsibility of the operator. The oper-
ator is also responsible for the control current circuit and the locking switch required with
pressure limiters, that comply with the Association of Technical Inspection Agencies
(VdTÜV) Fact Sheet No. 100.
4 Operation
During operation, take care that the device remains within its intended pressure and tem-
perature ranges. No other monitoring is necessary.
The permissible ambient and media temperature depends on the type of device and its de-
sign. This information can be found in the relevant data sheet.
Restricted ambient conditions may apply in explosion protected environments (see XA_013,
XA_014, XA_016 or XA_021).
4.1 Zero-point correction
Zero point deviations can occur due to the mounting, the installation position or due to the
type and duration of use. Measuring devices with micro controll position pointers can be
corrected in a depressurised state by means of the adjusting screw on the pointer hub (see
figure 6).
Figure 6: Zero-point correction
4.2 Maintenance / Service
When properly installed in accordance with applicable specifications, this device is mainte-
nance-free. However, we recommend an annual recalibration of the device.