Lamtec BT300 BurnerTronic User manual

www.lamtec.de
Sensors and Systems for Combustion Engineering
Quick Reference for End Users
BurnerTronic BT300
Fault Codes for Software Version 3.9


2
Table of Contents
Table of Contents
1 General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.1 Validity of these Instructions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
1.2 Faults . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2 List of Fault Codes. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
3 Assignment of Configuration Fault 107 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21
4 Assignment of the Programme Monitoring Time - Fault 600 . . . . . . . . . . . . . . . . . . . . . . . 23
5 Assignment of Internal Fault 999 . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 25
6 Assignment of CO/O2 Control Faults or Information . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 27

3
1 General Information
1 General Information
1.1 Validity of these Instructions
This document is a supplement to the Operating Instructions for the appliances listed below.
It is only applicable together with the Operating Instructions for the affected device.
The specifications in this document refer to the software version BT300 v3.9 and UI300 v3.11
/ v4.2 and higher. The following functionalities are not available with software versions <3.0 of
BurnerTronic.
• CO/O
2 control
• Applications with frequency inverter functions (VSM)
The designation UI300 used in the document applies to UI300-LSB, UI300-V1 and UI300-V2.
This document is applicable for the following devices:
1.2 Faults
NOTICE
The LAMTEC burner controls use different methods to detect fault messages between main
processor and watchdog processor:
BT300/ETAMATIC/FMS/VMS/FA1:
The bus transmission does not generally use different fault numbers to distinguish between
watchdog processor and main processor faults. In order to distinguish the main processor fault
messages from the watchdog processor fault messages, an offset of 10000 is added to the
watchdog processor faults. The main processor fault message H002 becomes the watchdog
processor fault message U10002.
CMS:
CMS allocates different fault numbers to main processor and watchdog processor faults.
An offset is not necessary.
•BT320
•BT330
•BT331
•BT335
•BT340
•BT341

4
2 List of Fault Codes
2 List of Fault Codes
Restarts according to TRD (P301 = 0 and P328 > 0) and EN676 (P301 = 2 and P328 > 0):
The restart counter increases automatically at every burner start.
The number of restarts is reset if
• BT300 remains in base fire for 10 s.
• a normal shut down occurs.
• a manual fault reset is triggered.
No. P301 = 0 P301 = 2 Description D1 D2
0 0 0 Unknown fault
– Reset fault
– If the fault still exists:
Send error number and diagnostic code to the technical
support.
– Replace the device
1 0 3 Flame fault
– Check ignition point
– Check spark igniter and pilot burner
– Check flame sensor
– Check flame stability
– Check positioning of the flame sensor
– Check fuel valves
– Check fuel supply
– Check stability of the fuel pressure
– Check grounding of the sensor cable
– Check flame sensor cable for short circuits/broken wire
– Check wiring
– Check parameter 800
2 0 0 Parasitic light detection
– Check parasitic light detection (outside door)
– Check flame sensor settings
– Check positioning of the flame sensor
(glowing parts in boiler)
– Check flame sensor cable for short circuits/broken wire
– Check grounding of sensor cable
– Check spark igniter and pilot burner
– Check parameter 800
– Check fuel supply
– Check wiring
3 0 3 Flame fault during ignition.
This fault occurs without proper ignition settings.
– Check ignition point
– Check spark igniter and pilot burner
– Check flame sensor
– Check flame stability
– Check positioning of the flame sensor
– Check fuel valves
– Check stability of the fuel pressure
– Check fuel supply
– Check grounding of sensor cable
– Check the flame sensor cable for short circuits/broken wire
– Check wiring
– Check parameters 302, 303 and 800

5
2 List of Fault Codes
No. P301 = 0 P301 = 2 Description D1 D2
4 1 1 Flame OFF during operation
– Check curve settings
– Check flame sensor
– Check flame stability
– Check positioning of the flame sensor
– Check fuel valves
– Check fuel supply
– Check stability of the fuel pressure
– Check grounding of sensor cable
– Check the flame sensor cable for short circuits/broken wire
– Check wiring
– Check parameter 800
5 0 3 Flame signal does not appear during the 1st time.
– Check ignition point
– Check spark igniter and pilot burner
– Check flame sensor
– Check flame stability
– Check positioning of the flame sensor
– Check fuel valves
– Check fuel supply
– Check the stability of the fuel pressure
– Check grounding of sensor cable
– Check the flame sensor cable for short circuits/broken wire
– Check wiring
– Check parameters 302,303 and 800
6 0 3 Flame signal is lost during stabilisation time.
– Check ignition point
– Check spark igniter and pilot burner
– Check flame sensor
– Check flame stability
– Check positioning of the flame sensor
– Check fuel valves
– Check fuel supply
– Check the stability of the fuel pressure
– Check grounding of sensor cable
– Check the flame sensor cable for short circuits/broken wire
– Check wiring
– Check parameters 302, 303 and 800
7 0 3 Flame signal is lost during 1st safety time.
– Check ignition point
– Check spark igniter and pilot burner
– Check flame sensor
– Check flame stability
– Check positioning of the flame sensor
– Check fuel valves
– Check fuel supply
– Check the stability of the fuel pressure
– Check grounding of sensor cable
– Check the flame sensor cable for short circuits/broken wire
– Check wiring
– Check parameters 302, 303 and 800

6
2 List of Fault Codes
No. P301 = 0 P301 = 2 Description D1 D2
8 0 3 Flame signal is lost during the 2nd safety time.
– Check ignition point
– Check spark igniter and pilot burner
– Check flame sensor
– Check flame stability
– Check positioning of the flame sensor
– Check fuel valves
– Check fuel supply
– Check the stability of the fuel pressure
– Check grounding of sensor cable
– Check the flame sensor cable for short circuits/broken wire
– Check wiring
– Check parameters 302, 303 and 800
9 0 3 Flame signal does not appear during the safety time.
– Check ignition point
– Check spark igniter and pilot burner
– Check flame sensor
– Check flame stability
– Check positioning of the flame sensor
– Check fuel valves
– Check fuel supply
– Check the stability of the fuel pressure
– Check grounding of sensor cable
– Check the flame sensor cable for short circuits/broken wire
– Check wiring
– Check parameters 302, 303 and 800
10 0 1 Flame signal is lost within 3 s after the safety time exceeds.
If flame OFF appears within 3 s after ignition, fault 10 is indi-
cated; after that, fault 4 is indicated subsequently.
– Check curve
– Check flame sensor
– Check flame stability
– Check positioning of the flame sensor
– Check fuel valves
– Check fuel supply
– Check the stability of the fuel pressure
– Check grounding of sensor cable
– Check the flame sensor cable for short circuits/broken wire
– Check wiring
– Check parameters 800
11 0 0 Monitoring for parasitic light does not last for the required 5 s.
This fault can occur during an internal self-test.
– Reset the fault.
– Switch the mains voltage off and on again if necessary.
– If the fault still exists, replace the device.

7
2 List of Fault Codes
No. P301 = 0 P301 = 2 Description D1 D2
13 1 0 Flame signal appears too early during ignition (pilot burner).
If parameters 302 and 303 are set to value 3 or 4, only the
ignition flame may be present during ignition (up to the begin-
ning of the second safety time). If the main flame is detected
during this period, fault 13 is indicated.
– Check main fuel valves.
– Check positioning of the main flame sensor.
– Check main flame sensor.
– The main flame sensor must detect only the main flame
and not the pilot flame.
– Check grounding of sensor cable.
– Check the flame sensor cable for short circuits or broken
wire.
– Check wiring.
103 0 0 Invalid miscellaneous data.
This fault can occur during an internal self-test.
– Reset fault and switch mains voltage OFF and ON again.
– Restore the actual data set (not protected) to the
device using UI300 or LSB Remote Software
– Check the restored data set.
– A Restart is required.
– The fault is still present: Replace device
105 Optional 0 Curve data are invalid or not available. Curve set /
Fuel number
A fault was detected while trying to save the curve or while
checking the redundant curves.
– Is a curve available?
If there is none, configure a curve.
– If a curve exists, repeat the programming and reset the
fault.
– If the data set was stored with the LSB Remote Software or
the UI300, restore the data set to the device and reset the
fault.
– The fault is still present: Replace device.
106 0 0 Difference in parameter value between main processor and
watchdog processor
Parameter
no.
Possible cause of error:
A normal (unprotected) data set was uploaded and an error
occurred during the data transfer.
The dataset was not saved correctly.
– Reload dataset.
– Save the protected dataset with LSB Remote Soft ware or
from the UI300 into the device.
– If this is not possible:
Change the reported parameters manually for one time
and reset the fault. Reset and switch the mains voltage
OFF and ON again
– If the fault still exists: change the device
107 0 0 Invalid configuration
– Check and correct the configuration according to the
specifications in chapter 3 Assignment of Configuration
Fault 107.
– Reset fault

8
2 List of Fault Codes
No. P301 = 0 P301 = 2 Description D1 D2
120 1 1 Different operation modes on both controllers
Main processor and watchdog processor detect the digital
input signal at slightly different times. A signal change is hap-
pening only for such a short time that only one of the two pro-
cessors detects it.
– Check the signal sequence.
– Reset fault and switch mains voltage OFF and ON again.
121 0 0 Correction is out of range. Channel
The watchdog processor checks whether the current correc-
tion values lie within the adjusted range.
– Check the correction range.
– Reset fault
– If the fault occurs continuously, replace the device
141 0 0 Variation of speed feedback is to big. Channel
The parameter set is based on an old, invalid factory setting.
Password level 2 is required.
– Save data set (not protected).
– Restore default data set of the software version of the
affected BT300 (protected data set) into the device.
– Restore the previously saved data set (not protected) to
the device.
– Reset the device
151 Optional 3 Recirculation damper is still OPEN 240 s after recirculation
release is OFF.
Channel
number
Actuator failure.
– In the event of stiffness, clean the damper and make it run
smoothly.
– Check the function of the actuator without damper and
replace if necessary.
D2:
0 = 120 s (main processor) or 150 s (watchdog processor)
after removing the recirculation terminal, the recirculation
channel has not reached the CLOSED position
1 = Recirculation channel should run to position CLOSED,
but runs to position OPEN
2 = Recirculation channel should run to curve position OPEN,
but runs outside the position
152 0 0 Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the technical
support.
– Replace the device
170 0 0 Short circuit of LDR flame scanner
– Check wiring
– Replace flame scanner

9
2 List of Fault Codes
No. P301 = 0 P301 = 2 Description D1 D2
191 1 1 1st Monitoring band exceeded for too long. Channel
– Check the damper for ease of movement.
In the event of stiffness, clean the damper and make it
smooth-running.
– Check the function of the actuator without damper and
replace if necessary.
– For analogue output (VSM), check the ramp speed of the
frequency inverter and adjust if necessary.
– Adjust the positioning speed in P 453 (reduce value).
201 1 1 1st Monitoring band has been fallen short for too long. Channel
– Check the damper for ease of movement.
In the event of stiffness, clean the damper and make it
smooth-running.
– Check the function of the actuator without damper and
replace if necessary.
– For analogue output (VSM), check the ramp speed of the
frequency inverter and adjust if necessary.
– Adjust the positioning speed in P 453 (reduce value).
211 0 0 2nd Monitoring band has been exceeded for too long. Channel
– Check the damper for ease of movement.
In the event of stiffness, clean the damper and make it
smooth-running.
– Check the function of the actuator without damper and
replace if necessary.
– For analogue output (VSM), check the ramp speed of the
frequency inverter and adjust if necessary.
– Adjust the positioning speed in P 453 (reduce value).
221 0 0 2nd monitoring band has been fallen short for too long. Channel
– Check the damper for ease of movement.
In the event of stiffness, clean the damper and make it
smooth-running.
– Check the function of the actuator without damper and
replace if necessary.
– For analogue output (VSM), check the ramp speed of the
frequency inverter and adjust if necessary.
– Adjust the positioning speed in P 453 (reduce value).
231 Optional 3 Electronic ratio control is blocked. Channel
The firing rate controller changes its direction too fast.
– Check and correct PID parameters.
– Reset fault.
241 0 0 A servo motor does not move, i.e. there is no position feed-
back available.
Channel Direction:
P 2 =
0 backward,
1 forward
– Check the air damper and gas damper for jamming.
– Replace affected actuator

10
2 List of Fault Codes
No. P301 = 0 P301 = 2 Description D1 D2
251 0 0 A servo motor cannot find the reference position. Channel
– Check the damper’s smooth-running to the reference
position. (see chapter Adjusting of the Actuators in the
BT300 manual print no. DLT1201).
– Check if the actuator type is adjusted properly (P455 -
P457) and correct if necessary.
– A restart is required
– If the fault cannot be resolved, replace the affected
actuator.
261 Optional 3 A servomotor returns an invalid position Channel
Too large deviation to target position.
– Check servomotor type (P455 - 457)
– Is the servomotor housing closed?
– For servomotors with 0,8 Nm and 9 Nm an external torque
must not exceed 0.2 Nm (for a motor with 0.8 Nm) or 1 Nm
( for a motor with 9 Nm).
– A restart is required.
– Replace affected actuator.
271 Optional 3 The servo motor feedback remains constant for too long,
even when the servo motor has moved.
Channel
– Check wiring
– The servomotor is blocked
– The servomotor was opened without permission.
281 1 1 The feedback signal of at least 1 servo motor is invalid. channel
To identify the servomotor’s direction of rotation two pulse
form signals, offset 90 degrees, are returned by the servomo-
tor. If fault 281 occurs, these signals are not identified cor-
rectly.
Cause of error:
– Back lash
– For servomotors with 0,8 Nm and 9 Nm an external torque
must not exceed 0.2 Nm (for a motor with 0.8 Nm) or 1 Nm
(for a motor with 9 Nm).
291 Optional 3 A servo motor does not reach the final position, because of
mixed-up detection.
Channel
Servomotors are mixed up while reconnecting. The test for
recognising this fault is described in the manual of the BT300
– print no. DLT1201 in chapter Detection of Servomotors with
Transposed Connections .
351 1 1 Invalid fuel change while burner is running
Parameter set is based on an old, invalid factory setting.
AL2 required.
– Save data set (not protected)
– Default data record of the software version of the affected
BT300 (protected data set) into the device.
– Restore the previously saved data set (not protected) to
the device.
– Reset the device.
360 0 0 Shut-down by the O2 trim due to lack of air
At first the time set in P113 ’O2 trim is active after ignition’
expires then a fault is triggered.
– Check and correct curve set.

11
2 List of Fault Codes
No. P301 = 0 P301 = 2 Description D1 D2
361 0 0 Maximum permissible CO voltage exceeded CO Probe
voltage
+1V Offset
Cold start may have been interrupted Probes not yet
ready for use
– Remove probe and check in air:
Replace the probe if necessary
– Burner is in air deficiency:
Check and correct curve set
362 0 0 Fault shut-down due to a missing burner maintenance
A reset of the maintenance counter occurs due to a change of
parameter 10 or 11. AL2 is required.
363 1
until v3.6
1
until v3.6
O2 value falls below the smallest, valid value.
0
from
v3.7
0
from
v3.7
O2 trim does not work on this burner.
– Check electronic ratio control curve
364 0 0 Maximum permissible COe value exceeded CO-actual
value
– Burner is in air deficiency Check and correct curve set
– Flame is cooled down too much:
Too much excess air: check and correct curve set
– Flame touches the combustion chamber:
adjust flame geometry
391 0 0 Curve set has changed during programming.
The fault is only indicated during curve set programming.
– Make sure that during the curve set programming no fuel
change takes place.
P812 2
– Reset fault
393 0 0 A remote shut-down is triggered.
Can be triggered by:
Clicking the BACK key for too long
Clicking the ENTER key and BACK key simultaneously.
Disconnecting the LSB Remote Software in SETTING mode
(after a waiting time of 45 s)
Clicking the icon in the LSB Remote Software
– Reset the fault.
394 0 0 Burner ON/OFF signal from the control unit has dropped with-
out permission.
– A restart is required.
451 1 1 Ignition position was left in ignition mode. Channel
With continuous output:
– Check position and speed of the channel displayed in D1.
– Speed and position are in good conditions:
Check EMC influences by spark igniter
– Speed and position are not in good conditions:
Check the frequency inverters settings (analogue output)
– Check the ease of movement of the control dampers.

12
2 List of Fault Codes
No. P301 = 0 P301 = 2 Description D1 D2
600 0 0 Program monitoring time (FAT) exceeded. Indication
number
Description see chapter 4 Assignment of the Programme
Monitoring Time - Fault 600
601 0 0 A fault occurs during valve leakage test: Gas pressure is still
present.
Main valve 1 is leaking (see manual BT300 DLT1205 chapter
Valve leakage test for main valves.
– Check the function of the gas pressure switch.
– Is main valve 2 opened during the test?
If no: Check the valve and replace if necessary.
Check wiring.
– Outlet pressure at the main valves during venting of the
test line:
If the outlet pressure is higher than the adjusted gas
pressure at the pressure switch, carry out the following
measures:
– Re-adjust the pressure switch and check the detected
leakage rate. (observe local standards and guidelines).
– Reduce the aperture of the ventilation damper.
– If the fault is still present: Replace valve 1.
602 0 0 A fault occurs during valve leakage test: Gas pressure is
missing.
Main valve 2 is leaking (see BT300 manual, print no.
DLT1205 chapter Valve leakage check of main valves)
BT300 software version < 3.3:
– Check gas inlet pressure.
– Is the gas pressure less than the adjusted gas pressure at
the pressure switch?
Check the function of the gas pressure switch.
– Does valve 1 open when actuated?
Yes: Gas valve 2 is leaking. Replace gas valve 2.
603 0 0 Manual venting of the gas line required!
The Parameter set is based on an old, invalid factory setting.
AL2 is required.
– Save data set (not protected).
– Restore default data set of the software version of the
affected BT300 (protected data set) into the device.
– Restore the previously saved data set (not protected) to
the device.
– Reset the device
606 0 0 CPI/POC signal is in an unexpected state.
– Check the CPI/POC contacts of the main valves.
– Check the functions of the main valves.

13
2 List of Fault Codes
No. P301 = 0 P301 = 2 Description D1 D2
608 1 *1) 1 *1) Invalid drop of the safety interlock chain system
– Check contacts and wiring of the safety interlock chain.
609 1 *1) 1 *1) Invalid drop of the safety interlock chain gas
– Gas pressure is too high/low.
– Check contacts and wiring of the safety interlock chain.
610 Optional
1)
3 1) Invalid drop of the safety interlock chain oil
– Oil pressure is too high/low.
– Check contacts and wiring of the safety interlock chain.
611 Optional 3 Gas pressure is too low.
– Check gas pressure.
– Check gas pressure switch.
– Make sure that gas is available.
613 0 0 Air pressure signal is missing.
– Check air pressure switch.
– Check fan
617 1 1 The continuous pilot flame signal drops during operation.
– Check curve settings
– Check flame sensor
– Check flame stability
– Check positioning of the flame sensor
– Check fuel valves
– Is fuel pressure stable
– Check fuel supply
– Check earthing of the sensor cable
– Check sensor cable for short circuits/broken wire
– Check wiring
– Check parameters 800
*1) The restart is only carried out when the condition of the fault (i.e. the dropped safety interlock chain or the low voltage) has been eliminated.

14
2 List of Fault Codes
No. P301 = 0 P301 = 2 Description D1 D2
624 Optional 3 Oil pressure is too low.
– Make sure that oil is available.
– Check oil pressure.
– Check oil pressure switch.
– Check oil filter
– Check oil regulator
711 0 0 Invalid change of the operation mode
Fault during an internal self-test. Main processor and watch-
dog processor detect the digital input signals at slightly differ-
ent times. This can cause an incorrect change of the
operating modes.
– Check the signal sequence.
– Reset fault and switch mains voltage OFF and ON again.
713 0 0 Invalid signal combination in operating mode BURNER OFF
Fault during an internal self-test. Main processor and watch-
dog processor detect the digital input signals at slightly differ-
ent times. This can trigger an incorrect signal combination.
– Check the signal sequence.
– Reset fault and switch mains voltage OFF and ON again.
714 0 0 Invalid signal combination in operating mode BURNER
READY
Fault during an internal self-test. Main processor and watch-
dog processor detect the digital input signals at slightly differ-
ent times. This can trigger an incorrect signal combination.
– Check the signal sequence.
– Reset fault and switch mains voltage OFF and ON again.
715 0 0 Invalid signal combination in operating mode PRE-PURGE
Fault during an internal self-test. Main processor and watch-
dog processor detect the digital input signals at slightly differ-
ent times. This can trigger an incorrect signal combination.
– Check the signal sequence.
– Reset fault and switch mains voltage OFF and ON again.
716 0 0 Invalid signal combination in operating mode IGNITION
POSITION
Fault during an internal self-test. Main processor and watch-
dog processor detect the digital input signals at slightly differ-
ent times. This can trigger an incorrect signal combination.
– Check the signal sequence.
– Reset fault and switch mains voltage OFF and ON again.
717 0 0 Invalid signal combination in operating mode IGNITION
Fault during an internal self-test. Main processor and watch-
dog processor detect the digital input signals at slightly differ-
ent times. This can trigger an incorrect signal combination.
– Check the signal sequence.
– Reset fault and switch mains voltage OFF and ON again.
719 0 0 Internal fault
– Reset fault
– If the fault still exists:
Send error number and diagnostic code to the technical
support.
– Replace the device

15
2 List of Fault Codes
No. P301 = 0 P301 = 2 Description D1 D2
720 0 0 Spark igniter is on for too long.
Up to version 3.8.0.0, the maximum switch-on time is
calculated from different parameters of the BT300.
From version 3.9.0.0, this time is set in parameter 338.
721-
729
0 0 Internal fault
– Reset fault
– If the fault still exists:
Send error number and diagnostic code to the technical
support.
– Replace the device
730 0 0 Adjustment mode is active without pilot burner.
This mode is specially integrated for setting the pilot burner.
Activation is only permitted with a pilot burner.
P730 = 0: Adjustment mode is OFF.
731 0 0 Internal fault
– Reset fault
– If the fault still exists:
Send error number and diagnostic code to the technical
support.
– Replace the device
732 0 0 Invalid signal combination during operation.
Fault during an internal self-test. Main processor and watch-
dog processor detect the digital input signals at slightly differ-
ent times. This can trigger an incorrect signal combination.
– Check the signal sequence.
– Reset fault and switch mains voltage OFF and ON again.
734 0 0 Internal fault
– Reset fault
– If the fault still exists:
Send error number and diagnostic code to the technical
support.
– Replace the device
739 0 0 Internal fault
– Reset fault
– If the fault still exists:
Send error number and diagnostic code to the technical
support.
– Replace the device.

16
2 List of Fault Codes
No. P301 = 0 P301 = 2 Description D1 D2
740 0 0 Valve leakage test: Main gas valve 1 is leaking.
Main valve 1 is leaking (see BT300 manual DLT1205 chapter
Valve leakage check of main valves).
– Check the function of the gas pressure switch.
– Is main valve 2 opened during the test?
If no: Check the valve and replace if necessary.
Check wiring
– Outlet pressure at the main valves during the venting of the
test line:
If the outlet pressure is higher than the adjusted gas pres-
sure at the pressure switch, take the following measures:
– Re-adjust the pressure switch and recalculate the
detected leakage rate (observe local standards and
guidelines).
– Reduce the aperture of the air damper for venting.
– The fault is still present: Replace device
741 0 0 Internal fault
– Reset fault
– If the fault still exists:
Send error number and diagnostic code to the technical
support.
– Replace the device
742 0 0 Valve leakage test: Main gas valve 2 is leaking.
Main valve 2 is leaking (see instructions BT300 DLT1205
Chapter Valve tightness control main valves).
– BT300 software version > 3.3: Check gas inlet pressure.
Is the gas pressure lower than the adjusted gas pressure
at the pressure switch?
– Check gas pressure switch for function.
– Does valve 1 open when actuated?
Yes: Gas valve 2 is leaking. Replace gas valve 2.
743 0 0 Flame monitoring: Flame burns for too long after shutdown.
– A Restart is required.
– Check fuel valves for tightness.
– Check flame sensor.
– Check positioning of the flame sensor.
– Check wiring.
– Post-combustion time (P326) is set too short (AL2).
745 0 0 Program monitoring time exceeded.
746 0 0 Internal fault
– Reset fault
– If the fault still exists:
Send error number and diagnostic code to the technical
support.
– Replace the device
747 0 0 Internal fault
– Reset fault
– If the fault still exists:
Send error number and diagnostic code to the technical
support.
– Replace the device

17
2 List of Fault Codes
No. P301 = 0 P301 = 2 Description D1 D2
759 0 0 BT300 leaves SETTING mode automatically after 24 hours.
The BT300 has a hard coded time out of 24 hours for setting
the burner. This Timeout has expired.
– Reset fault.
– Enter SETTING again.
763 0 0 Internal fault
– Reset fault
– If the fault still exists:
Send error number and diagnostic code to the technical
support.
– Replace the device
764 1 1 CO-controller - internal fault Curve set
– Reset fault
– If the fault still exists:
Send error number and diagnostic code to the technical
support.
– Replace the device
800 0 0 Invalid parameter Parameter
no.
– Re-enter the parameter.
– Restore the protected data set in the device using the LSB
Remote Software or the UI300.
– If this is not possible, change the reported parameter
manually and reset the fault.
– Switch power OFF and ON
– If the fault is still present: Replace device.
801 0 0 Internal fault Channel
– Reset fault
– If the fault still exists:
Send error number and diagnostic code to the technical
support.
– Replace the device
802 1 1 Integration of a channel into the electronic ratio control needs
too much time.
Channel
This fault only affects the recirculation channel.
Possible causes:
Recirculation valve is sluggish or blocked.
The physical path of the damper is too long.
– When switching on the recirculation damper, run the
recirculation channel with a lower burner firing rate.
– Adjust curve
803 0 0 Channel is out of 1st monitoring band for too long. Channel
– Check the damper for ease of movement.
In case of sluggish operation, clean the damper and make
it run smoothly again.
– Check the function of the servomotor without damper and
replace if necessary.
– For analogue output (VSM), check the ramp speed of the
frequency inverter and adjust it if necessary.
– Adjust the positioning speed in P 453 (reduce value).
Note:
Fault will be fixed with software version 3.9

18
2 List of Fault Codes
No. P301 = 0 P301 = 2 Description D1 D2
804 0 0 Internal fault Channel
– Reset fault
– If the fault still exists:
Send error number and diagnostic code to the technical
support.
– Replace the device
805 0 0 Directly controlled channel runs to an invalid position Channel +
set point
position
The fault is due to a channel which is not deactivated or con-
trolled by the electronic ratio control (i.e. in pre-purge or post-
purge).
The fault occurs during an internal self-test.
– Reset fault and switch mains voltage OFF and ON again.
– If the fault still exists: Replace the device
806 0 0 Implausible channel setpoint Channel
+ set point
position
+ actual
value
+ program-
ming
tolerance
– Check data in curve table and program defective curve
points again.
– Restore the data set (not protected) with LSB Remote
Software or UI300 to the device.
807 1 1 Timeout of an LSB message LSB
message
no.
Cause of
VSM100
fault
Possible cause of error :
– Connection between VSM/LCM GND and protective
earth PE is defective.
– Feedback of the speed variation was too fast
– Fault of VSM
– Fault on the LSB (red LED flashes or is permanently ON)
D1:
185 = VSM100
D2:
0 = Unknown cause
1 = Fault in FlashCRC
2 = DIP switch is inconsistent for input selection
(Namur/3-wire/current, the high byte contains the DIP
switch position).
3 = Like 2, but with a different code position
4 = Like 2, but with a different code position
5 = SRAM fault, high byte contains the code position
6 = Stack error
7 = Fault in CPU self test
8 = RAM error
9 = Delta-T-error. Fixed with VSM version 1.2.0.0.
10 = Fault in reference voltage, the upper 12 bits contain the
values of the reference voltage.
11 = Other fault/crash
12 = PowerOn, the device was shut OFF

19
2 List of Fault Codes
No. P301 = 0 P301 = 2 Description D1 D2
808-
810
0 0 Internal fault
– Reset fault
– If the fault still exists:
Send fault number and diagnostic code to the technical
support.
– Replace the device
889 0 0 The time gap between two remote fault resets is too short.
EN 14459 allows only 4 remote fault resets every 15 min.
The fault reset is monitored by LSB Remote Software, UI300,
LAMTEC SYSTEM BUS and field bus. Exceeding the num-
ber of fault resets causes the fault shot-down 889 and further
remote fault resets are ignored. After a delay time another
remote fault reset is possible.
The fault shut-down H889 also occurs, if a fault reset is sent
without any reason.
A reset by terminal is always possible.
How to reset this fault:
– Wait for 15 minutes until you try to reset the fault again.
– Cut off the power supply from BT300 for an instant,
reconnect it and reset the fault subsequently.
921-
929
0 0 Internal fault
– Reset fault
– If the fault still exists:
Send error number and diagnostic code to the technical
support.
– Replace the device
985 0 0 VSM diagnosis fault
Possible cause of the fault:
BurnerTronic expects a VSM module but the exchange of
diagnosis data with the module fails.
– A restart is required.
– Check wiring of the LSB
– Replace VSM
986 0 0 Dynamic range test detected an invalid feedback. Channel Actual value
– Check the damper for ease of movement.
If sluggish, clean the damper and make it run smoothly
again.
– Check servomotor function without damper and replace if
necessary.
– For analogue output (VSM), check ramp speed of the
frequency inverter and adjust if necessary.
– Adjust the positioning speed in P 453 (reduce value).
– Reset fault and switch mains voltage off and on again.
– If the fault still occurs, replace the device.
Other manuals for BT300 BurnerTronic
3
Table of contents
Other Lamtec Industrial Equipment manuals
Popular Industrial Equipment manuals by other brands

tornos
tornos DECO 20 Headstock Revision DESCRIPTION - PROCEDURES

ABB
ABB HT562485 Operation manual

Tyco Electronics
Tyco Electronics 1752786-1 instruction manual

Siemens
Siemens SIMOTICS S-1FK2 Service manual

Leroy-Somer
Leroy-Somer Nidec Mb 3101 Maintenance manual

Siemens
Siemens SIMATIC HMI IWP10F Quick install guide

ABB
ABB UA16 RA Series operating instructions

IC
IC P-1610 installation instructions

Posch
Posch AutoSplit 415 operating instructions

ABB
ABB A140-M56 original operation manual

Modine Manufacturing
Modine Manufacturing ElectroFin quick start guide

INOXPA
INOXPA MM-1 Installation, service and maintenance instructions