PAGE 2
OPERATING PARAMETERS:
• Water pressure: 12-125 psi.
• Water temperature: 34°F-120°F.
• pH range: 6.0-9.0.
• Maximum hardness: 25 grains per gallon.
• Hydrogen sulde, iron and manganese must be pretreated.
• Maximum chlorine 3ppm. De-chlorination is recommended.
• Do not exceed recommended ow rates.
• Designed for intermittent ows. For continuous ows please contact Lancaster Water Treatment.
• Additional equipment will be needed if using a tankless water heater. Consult factory.
• Conservative life expectancy of the mineral is 5 years minimum based on meeting the above parameters.
PACKAGING: All systems are shipped from the factory in cartons.
COMPONENTS: Fiberglass mineral tank, in/out head, installation tting package, distributor tube assembly,
mineral.
MODEL
NUMBER
MAXIMUM
SERVICE FLOW
MEDIA
CU.FT. (LBS.)
MINERAL TANK
(DIA. x HT.)
7-UFAS-011 10 GPM 0.11 (5.0) 8”x44”
7-UFAS-016 15 GPM 0.16 (7.6) 10”x54”
7-UFAS-026 25 GPM 0.26 (12.7) 13”x48”
INSTALLATION: Place system in desired location close to water supply inlet keeping far enough away
from walls and other obstructions to allow enough room for servicing the unit.
INSTALL THE ANTI-SCALE SYSTEM AS AN UPFLOW FILTER.
The words “UPFLOW INLET” and “DOWNFLOW INLET” are molded into the in/out head.
ADD MINERAL: Remove the in/out head by turning counter-clockwise. Plug the distributor tube to prevent
mineral from entering and add the mineral. Remove plug from the distributor tube and replace the in/out head.
OPTIONAL BYPASS VALVE: The use of a bypass valve is recommended for ease of maintenance. The
bypass valve connects to the in/out head using nuts that only require hand tightening. Install with red knobs in
the upward position. Press end of bypass valve with o-rings into the in/out head. HAND TIGHTEN NUTS.
Avoid getting primer and solvent cement on any part of the o-rings, bypass valve or in/out head. DO NOT use
pipe dope or any other sealant on threads. Teon tape is not necessary on the caps because of o-ring seal.
DO NOT use Vaseline or other unacceptable lubricants on o-rings. A silicone lubricant may be used on black
o-rings.
FITTING ADAPTER: V3007 1” PVC Male NPT elbow assembly comes standard with each unit. Other
options available (see page 4).
When assembling the installation tting package (inlet and outlet), connect the tting to the plumbing system
rst and then attach the nut, split ring and o-ring. Heat from soldering or solvent cements may damage the nut,
split ring and o-ring. Solder joints should be cool and solvent cements should be set before installing the nut,
split ring and o-ring. Avoid getting primer and solvent cement on any part of the o-rings, split rings, bypass
valve or in/out head.