lapara UPS 1K User manual

Online UPS
1K/2K/3K
Uninterruptible Power Supply System
USER MANUAL
EN

Table of Contents
1. Important Safety Warning ............................................................... 1
1.1. Transportation .................................................................................................... 1
1.2. Preparation ........................................................................................................ 1
1.3. Installation ......................................................................................................... 1
1.4. Operation ........................................................................................................... 1
1.5. Maintenance, service and faults ........................................................................... 2
2. Installation and setup...................................................................... 3
2.1. Rear panel view .................................................................................................. 3
2.2. Setup t e UPS .................................................................................................... 4
3. Operations ....................................................................................... 7
3.1. Button operation ................................................................................................. 7
3.2. LCD Panel .......................................................................................................... 7
3.3. Audible Alarm ..................................................................................................... 9
3.4. LCD display wordings index ................................................................................. 9
3.5. UPS Setting ...................................................................................................... 10
3.6. Operating Mode Description .............................................................................. 13
3.7. Faults Reference Code ....................................................................................... 14
3.8. Warning indicator ............................................................................................. 14
4. Troubleshooting ............................................................................. 15
5. Storage and aintenance .............................................................. 16
6.
Specifications ................................................................................ 17

1
LA
-
ON
-
LCD
-
V.09
1. Important Safety Warning
Please comply with all warnings and operating instructions in this manual strictly. Save this
manual properly and read carefully the following instructions before installing the unit. Do not
operate this unit before reading through all safety information and operating instructions
carefully
1.1. Transportation
Please transport the UPS system only in the original package to protect against
shock and impact.
1.2. Preparation
Condensation may occur if the UPS system is moved directly from cold to warm
environment. The UPS system must be absolutely dry before being installed. Please
allow at least two hours for the UPS system to acclimate the environment.
Do not install the UPS system near water or in moist environments.
Do not install the UPS system where it would be exposed to direct sunlight or near
heater.
Do not block ventilation holes in the UPS housing.
1.3. Installation
Do not connect appliances or devices which would overload the UPS system (e.g.
laser printers) to the UPS output sockets.
Place cables in such a way that no one can step on or trip over them.
Do not connect domestic appliances such as hair dryers to UPS output sockets.
The UPS can be operated by any individuals with no previous experience.
Connect the UPS system only to an earthed shockproof outlet which must be easily
accessible and close to the UPS system.
Please use only VDE-tested, CE-marked mains cable (e.g. the mains cable of your
computer) to connect the UPS system to the building wiring outlet (shockproof
outlet).
Please use only VDE-tested, CE-marked power cables to connect the loads to the
UPS system.
When installing the equipment, it should ensure that the sum of the leakage current
of the UPS and the connected devices does not exceed 3.5mA.
1.4. Operation
Do not disconnect the mains cable on the UPS system or the building wiring outlet
(shockproof socket outlet) during operations since this would cancel the protective
earthing of the UPS system and of all connected loads.
The UPS system features its own, internal current source (batteries). The UPS
output sockets or output terminals block may be electrically live even if the UPS
system is not connected to the building wiring outlet.
In order to fully disconnect the UPS system, first press the OFF/Enter button to
disconnect the mains.
Prevent no fluids or other foreign objects from inside of the UPS system.

2
LA
-
ON
-
LCD
-
V.09
1.5. Maintenance, service and faults
The UPS system operates with hazardous voltages. Repairs may be carried out only
by qualified maintenance personnel.
Caution - risk of electric shock. Even after the unit is disconnected from the mains
(building wiring outlet), components inside the UPS system are still connected to the
battery and electrically live and dangerous.
Before carrying out any kind of service and/or maintenance, disconnect the batteries
and verify that no current is present and no hazardous voltage exists in the terminals
of high capability capacitor such as BUS-capacitors.
Only persons are adequately familiar with batteries and with the required
precautionary measures may replace batteries and supervise operations.
Unauthorized persons must be kept well away from the batteries.
Caution - risk of electric shock. The battery circuit is not isolated from the input
voltage. Hazardous voltages may occur between the battery terminals and the
ground. Before touching, please verify that no voltage is present!
Batteries may cause electric shock and have a high short-circuit current. Please take
the precautionary measures specified below and any other measures necessary
when working with batteries:
remove wristwatches, rings and other metal objects
use only tools with insulated grips and handles.
When changing batteries, install the same number and same type of batteries.
Do not attempt to dispose of batteries by burning them. This could cause battery
explosion.
Do not open or destroy batteries. Escaping electrolyte can cause injury to the skin
and eyes. It may be toxic.
Please replace the fuse only with the same type and amperage in order to avoid fire
hazards.
Do not dismantle the UPS system.

3
LA
-
ON
-
LCD
-
V.09
2. Installation and setup
NOTE: Before installation, please inspect the unit. Be sure that nothing inside the package is
damaged. Please keep the original package in a safe place for future use.
NOTE: There are two different types of online UPS: standard and long-run models. Please
refer to the following model table.
Model Type Model Type
1K Standard 1K-L Long-run2K 2K-L
3K 3K-L
2.1. Rear panel view
1K(L) TOWER 2K(L) TOWER 3K(L) TOWER
1. Programmable outlets: connect to non-critical loads.
2. Output receptacles: connect to mission-critical loads.
3. AC input
4. Input circuit breaker
5. Network/Fax/Modem surge protection
6. Emergency power off function connector (EPO)
7. USB communication port
8. RS-232 communication port
9. SNMP intelligent slot
10.External battery connection (only available for L model)
11.Output terminal
12.Output circuit breaker

4
LA
-
ON
-
LCD
-
V.09
2.2. Setup the UPS
Before installing the UPS, please read below to select proper location to install UPS.
1. UPS should be placed on the flat and clean surface. Place it in an area away from
vibration, dust, humidity, high temperature, flammable liquids, gases, corrosive and
conductive contaminants. Install the UPS indoors in a clean environment, where it is
away from window and door. Maintain minimum clearance of 100mm in the bottom of the
UPS to avoid dust and high temperature.
2. Maintain an ambient temperature range of 0ºC to 45ºC for UPS optimal operation. For
every 5ºC above 45ºC, the UPS will derate 12% of nominal capacity at full load. The
highest working temperature requirement for UPS operation is 50ºC.
3. It’s required to maintain maximum altitude of 1000m to keep UPS normal operation at full
load UPS. If it’s used in high altitude area, please reduce connected load. Altitude derating
power with connected loads for UPS normal operation is listed as below:
4. Place UPS:
It’s equipped with fan for cooling. Therefore, place the UPS in a
well-ventilated area. It’s required to maintain minimum clearance of 100mm
in the front of the UPS and 300mm in the back and two sides of the UPS for
heat dissipation and easy-maintenance.
5. Connect To Transformer
Please do NOT connect transformer to output of the UPS. Otherwise, it will cause UPS
internal fault and force UPS to enter to fault mode. Please connect transformer to input of the
UPS.
6. Connect to External Battery Pack
When connecting external battery packs, please be sure to connect polarity correctly.
Connect positive pole of battery pack to positive pole of external battery connector in UPS and
Transformer Transformer

5
LA
-
ON
-
LCD
-
V.09
negative pole of battery pack to negative pole of external battery connector in UPS. Polarity
misconnection will cause UPS internal fault. It’s recommended to add one breaker between
positive pole of battery pack and positive pole of external battery connector in UPS to prevent
damage to battery packs from internal fault.
The required specification of breaker: voltage ≧1.25 x battery voltage/set; current ≧50A
Please choose battery size and connected numbers according to backup time requirement
and UPS specifications. To extend battery lifecycle, it’s recommended to use them in the
temperature range of 15ºC to 25ºC.
Step 1: External battery connection (for long-run models only)
Follow below chart to make external battery connection.
Step 2: UPS input connection
Plug the UPS into a two-pole, three-wire, grounded receptacle only. Avoid using extension
cords.
For 208/220/230/240VAC models: The power cord is supplied in the UPS package.
For 110/115/120/127VAC models: The power cord is attached to the UPS. The input plug
is a NEMA 5-15P for 1K and 1K-L models, NEMA 5-20P for 2K and 2K-L models.
Note: For Low voltage models: Check if the site wiring fault indicator lights up in LCD panel. It
will be illuminated when the UPS is plugged into an improperly wired utility power outlet (Refer
to Troubleshooting section).
Step 3: UPS output connection
For socket-type outputs, there two kinds of outputs: programmable outlets and general
outlets. Please connect non-critical devices to the programmable outlets and critical
devices to the general outlets. During power failure, you may extend the backup time to
critical devices by setting shorter backup time for non-critical devices.
For terminal-type input or outputs, please follow below steps for the wiring configuration:
a) Remove the small cover of the terminal block
b) Suggest using AWG14 or 2.1mm
2
power cords. Suggest using AWG12-10 or
3.3mm
2
-5.3mm
2
power cords for NEMA type.
c) Upon completion of the wiring configuration, please check whether the wires are
securely affixed.
d) Put the small cover back to the rear panel.
Step 4: Communication connection
Communication port:
USB port RS-232 port Intelligent slot

6
LA
-
ON
-
LCD
-
V.09
To allow for unattended UPS shutdown/start-up and status monitoring, connect the
communication cable one end to the USB/RS-232 port and the other to the communication
port of your PC. With the monitoring software installed, you can schedule UPS
shutdown/start-up and monitor UPS status through PC.
The UPS is equipped with intelligent slot perfect for either SNMP or AS400 card. When
installing either SNMP or AS400 card in the UPS, it will provide advanced communication and
monitoring options.
PS. USB port and RS-232 port can’t work at the same time.
Step 5: Network connection
Network/Fax/Phone surge port
Connect a single modem/phone/fax line into surge-protected “IN” outlet on the back panel of
the UPS unit. Connect from “OUT” outlet to the equipment with another modem/fax/phone line
cable.
Step 6: Disable and enable EPO function
Keep the pin 1 and pin 2 closed for UPS normal operation. To activate EPO function, cut the
wire between pin 1 and pin 2.
Step 7: Turn on the UPS
Press the ON/Mute button on the front panel for two seconds to power on the UPS.
Note: The battery charges fully during the first five hours of normal operation. Do not
expect full battery run capability during this initial charge period.
Step 8: Install software
For optimal computer system protection, install UPS monitoring software to fully configure
UPS shutdown. You may insert provided CD into CD-ROM to install the monitoring software. If
not, please follow steps below to download and install monitoring software from the internet:
1. Go to the website http://www.power-software-download.com
2. Click ViewPower software icon and then choose your required OS to download the
software.
3. Follow the on-screen instructions to install the software.
4. When your computer restarts, the monitoring software will appear as an orange plug icon
located in the system tray, near the clock.
It’s in closed status for UPS
normal operation.

7
LA
-
ON
-
LCD
-
V.09
3. Operations
3.1. Button operation
Button Function
ON/Mute Button
Turn on the UPS: Press and hold ON/Mute button for at least 2
seconds to turn on the UPS.
Mute the alarm: When the UPS is on battery mode, press and hold
this button for at least 5 seconds to disable or enable the alarm
system. But it’s not applied to the situations when warnings or errors
occur.
Up key: Press this button to display previous selection in UPS setting
mode.
Switch to UPS self-test mode: Press ON/Mute buttons
simultaneously for 3 seconds to enter UPS self-testing while in AC
mode, ECO mode, or converter mode.
OFF/Enter Button
Turn off the UPS: Press and hold this button at least 2 seconds to
turn off the UPS in battery mode. UPS will be in standby mode under
power normal or transfer to Bypass mode if the Bypass enable
setting by pressing this button.
Confirm selection key: Press this button to confirm selection in UPS
setting mode.
Select Button
Switch LCD message: Press this button to change the LCD message
for input voltage, input frequency, battery voltage, output voltage and
output frequency. It will return back to default display when pausing
for 10 seconds.
Setting mode: Press and hold this button for 3 seconds to enter UPS
setting mode when UPS is in standby mode or bypass mode.
Down key: Press this button to display next selection in UPS setting
mode.
ON/Mute + Select
Button
Switch to bypass mode: When the main power is normal, press
ON/Mute and Select buttons simultaneously for 3 seconds. Then
UPS will enter to bypass mode. This action will be ineffective when
the input voltage is out of acceptable range.
Exit setting mode or return to the upper menu: When working in
setting mode, press ON/Mute and Select buttons simultaneously for
0.2 seconds to return to the upper menu. If it’s already in top menu,
press these two buttons at the same time to exit the setting mode.
3.2. LCD Panel

8
LA
-
ON
-
LCD
-
V.09
Display Function
Backup time information
Indicates the estimated backup time.
H: hours, M: minute, S: second
Configuration and fault information
Indicates the configuration items, and the configuration items are
listed in details in section 3-5.
Indicates the warning and fault codes, and the codes are listed in
details in section 3-7 and 3-8.
Mute operation
Indicates that the UPS alarm is disabled.
Output information
Indicates the output voltage and output frequency.
Vac: AC voltage, Vdc: DC voltage, Hz: frequency
Load information
Indicates the load level by 0-24%, 25-49%, 50-74%, and
75-100%.
Indicates overload.
Indicates the load or the UPS output is short circuit.
Programmable outlets information
Indicates that programmable management outlets are working.
Mode operation information
Indicates the UPS connects to the mains.
Indicates the battery is working.
Indicates the bypass circuit is working.
Indicates the ECO mode is enabled.
Indicates the Inverter circuit is working.
Indicates the output is working.
Battery information
Indicates the Battery level by 0-24%, 25-49%, 50-74%, and
75-100%.
Indicates the battery is fault.
Indicates low battery level and low battery voltage.
Input & Battery voltage information
Indicate the input voltage, input frequency and battery voltage.
Vac: AC voltage, Vdc: DC voltage, Hz: frequency

9
LA
-
ON
-
LCD
-
V.09
3.3. Audible Alarm
Battery Mode Sounding every 5 seconds
Low Battery Sounding every 2 seconds
Overload Sounding every second
Fault Continuously sounding
Bypass Mode Sounding every 10 seconds
3.4. LCD display wordings index
Abbreviation Display content Meaning
ENA Enable
DIS Disable
ESC Escape
HLS
High loss
LLS Low loss
BAT
Battery
BAH BatteryAH
CHA Charger current
CBV Charger boost voltage
CFV Charger float voltage
CF Converter
ON ON
EP EPO
TP Temperature
CH Charger
FU Bypass frequency unstable
EE EEPROM error
FA Fan failure
BR Battery Replacement

10
LA
-
ON
-
LCD
-
V.09
3.5. UPS Setting
There are three parameters to set up the
UPS.
Parameter 1: It’s for program alternatives.
Refer to below table.
Parameter 2 and parameter 3 are the
setting options or values for each
program.
01: Output voltage setting
Interface
Setting
Parameter 3: Output voltage
For 200/208/220/230/240 VAC models, you may choose the
following output voltage:
200: present output voltage is 200Vac
208: present output voltage is 208Vac
220: present output voltage is 220Vac
230: present output voltage is 230Vac (Default)
240: present output voltage is 240Vac
For 100/110/150/120/127 VAC models, you may choose the
following output voltage:
100: present output voltage is 100Vac
110: present output voltage is 110Vac
115: present output voltage is 115Vac
120: present output voltage is 120Vac (Default)
127: present output voltage is 127Vac
02: Frequency Converter enable/disable
Interface
Setting
Parameter 2 & 3:
Enable or disable converter mode. You may
choose the following two options:
CF ENA: converter mode enable
CF DIS: converter mode disable (Default)
03: Output frequency setting
Interface
Setting
Parameter 2 & 3: Output frequency setting.
You may set the initial frequency on battery mode:
BAT 50: present output frequency is 50Hz
BAT 60: present output frequency is 60Hz
If converter mode is enabled, you may choose the following
output frequency:
CF 50: present output frequency is 50Hz
CF 60: present output frequency is 60Hz
Parameter 1
Parameter 2 Parameter 3

11
LA
-
ON
-
LCD
-
V.09
04: ECO enable/disable
Interface
Setting
Par
ameter 3:
Enable or disable ECO function. You may choose
the following two options:
ENA: ECO mode enable
DIS: ECO mode disable (Default)
05: ECO voltage range setting
Interface
Setting
Parameter 2 & 3:
Set the acceptable high voltage point and low
voltage point for ECO mode by pressing Down key or Up key.
HLS: High loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from +7V to +24V of the nominal voltage.
(Default: +12V)
For 100/110/115/120/127 VAC models, the setting range in
parameter 3 is from +3V to +12V of the nominal voltage.
(Default: +6V)
LLS: Low loss voltage in ECO mode in parameter 2.
For 200/208/220/230/240 VAC models, the setting range in
parameter 3 is from -7V to -24V of the nominal voltage. (Default:
-12V)
For 100/110/115/120/127 VAC models, the setting voltage in
parameter 3 is from -3V to -12V of the nominal voltage. (Default:
-6V)
06: Bypass enable/disable when UPS is off
Interface
Setting
Parameter 3:
Enable or disable Bypass function. You may
choose the following two options:
ENA: Bypass enable
DIS: Bypass disable (Default)
07: Bypass voltage range setting
Interface
Setting
Parameter 2 & 3:
Set the acceptable high voltage point and
acceptable low voltage point for Bypass mode by pressing the
Down key or Up key.
HLS: Bypass high voltage point
For 200/208/220/230/240 VAC models:
230-264: setting the high voltage point in parameter 3 from
230Vac to 264Vac. (Default: 264Vac)
For 100/110/115/120/127 VAC models:
120-132: setting the high voltage point in parameter 3 from
120Vac to 132Vac. (Default: 132Vac)
LLS: Bypass low voltage point
For 200/208/220/230/240 VAC models:
170-220: setting the low voltage point in parameter 3 from
170Vac to 220Vac. (Default: 170Vac)
For 100/110/115/120/127 VAC models:
85-115: setting the low voltage point in parameter 3 from 85Vac
to 115Vac. (Default: 85Vac)

12
LA
-
ON
-
LCD
-
V.09
08: Bypass frequency range setting
Interface
Setting
Parameter 2 & 3:
Set the acceptable high frequency point and
acceptable low frequency point for Bypass mode by pressing the
Down key or Up key.
HLS: Bypass high frequency point
For 50Hz output frequency models:
51-55Hz: setting the frequency high loss point from 51Hz to
55HZ(Default: 53.0Hz)
For 60Hz output frequency models:
61-65Hz: setting the frequency high loss point from 61Hz to
65Hz(Default: 63.0Hz)
LLS: Bypass low Frequency point
For 50Hz output frequency models:
45-49Hz: setting the frequency low loss point from 45Hz to
49HZ(Default: 47.0Hz)
For 60Hz output frequency models:
55-59Hz: setting the frequency low loss point from 55Hz to
59Hz(Default: 57.0Hz)
09: Programmable outlets enable/disable
Interface
Setting
Parameter 3:
Enable or disable programmable outlets.
ENA: Programmable outlets enable
DIS: Programmable outlets disable (Default)
10: Programmable outlets setting
Interface
Setting
Parameter 3:
Set up backup time limits for programmable
outlets.
0-999: setting the backup time limits in minutes from 0-999 for
programmable outlets which connect to non-critical devices on
battery mode. (Default: 999)
11: Autonomy limitation setting
Interface
Setting
Parameter 3:
Set up backup time on battery mode for general
outlets.
0-999: setting the backup time in minutes from 0-999 for general
outlets on battery mode.
DIS: Disable the autonomy limitation and the backup time will
depend on battery capacity. (Default)
Note: When setting as “0”, the backup time will be only 10
seconds.
12: Battery total AH setting
Interface
Setting
Parameter 3:
Set up the battery total AH of the UPS.
7-999: setting the battery total capacity from 7-999 in AH. Please
set the correct battery total capacity if external battery bank is
connected.

13
LA
-
ON
-
LCD
-
V.09
13: Charger maximum current setting
Interface
Setting
Parameter 3:
Set up the charger maximum current.
1/2/4/6/8: setting the charger maximum current 1/2/4/6/8* in
Ampere. (Default: 8A)
*Note: This setting is only available for super charger.
14: Charger Boost voltage setting
Interface
Setting
Parameter 3:
Set up the charger boost voltage.
225-240: setting the charger boost voltage from 2.25 V/cell to
2.40V/cell. (Default: 2.36V/cell)
15: Charger Float voltage setting
Interface
Setting
Parameter 3:
Set up the charger float voltage.
220-233: setting the charger float voltage from 2.20 V/cell to
2.33V/cell. (Default: 2.28V/cell)
00: Exit setting
3.6. Operating Mode Description
Operating mode Description LCD display
Online mode When the input voltage is within acceptable
range, UPS will provide pure and stable AC
power to output. The UPS will also charge the
battery at online mode.
ECO mode Energy saving mode:
When the input voltage is within voltage
regulation range, UPS will bypass voltage to
output for energy saving.
Frequency
Converter mode When input frequency is within 40 Hz to 70
Hz, the UPS can be set at a constant output
frequency, 50 Hz or 60 Hz. The UPS will still
charge battery under this mode.
Battery mode When the input voltage is beyond the
acceptable range or power failure and alarm is
sounding every 5 seconds, UPS will backup
power from battery.

14
LA
-
ON
-
LCD
-
V.09
Bypass mode When input voltage is within acceptable range
but UPS is overload, UPS will enter bypass
mode or bypass mode can be set by front
panel. Alarm is sounding every 10 second.
Standby mode UPS is powered off and no output supply
power, but still can charge batteries.
Fault mode When a fault has occurred, the ERROR icon
and the fault code will be displayed.
3.7. Faults Reference Code
Fault event Fault code
Icon Fault event Fault code
Icon
Bus start fail 01 x Inverter output short 14
Bus over 02 x Battery voltage too high 27
Bus under 03 x Battery voltage too low 28
Inverter soft start fail 11 x Over temperature 41
x
Inverter voltage high 12 x Over load 43
Inverter voltage Low 13
x
C arger failure
45
x
3.8. Warning indicator
Warning Icon (flashing) Alarm
Low Battery
Sounding every 2 seconds
Overload
Sounding every 2 seconds
Battery is not connected
Sounding every 2 seconds
Over Charge
Sounding every 2 seconds
Site wiring fault
Sounding every 2 seconds
EPO enable
Sounding every 2 seconds
Over temperature
Sounding every 2 seconds
Charger failure
Sounding every 2 seconds
Battery fault
Sounding every 2 seconds
(At this time, UPS is off to remind
users something wrong with battery)
Out of bypass voltage range
Sounding every second
Bypass frequency unstable
Sounding every 2 seconds
EEPROM error
Sounding every 2 seconds
Fan failure
Sounding every 2 seconds
Battery replace
Sounding every 2 seconds
NOTE: “Site Wiring Fault” function can be enabled/disabled via software. Please check
software manual for the details.

15
LA
-
ON
-
LCD
-
V.09
4. Troubleshooting
If the UPS system does not operate correctly, please solve the problem by using the table
below.
Symptom
Possible cause
Remedy
No indication and alarm even
though the mains is normal. The AC input power is not
connected well. Check if input power cord
firmly connected to the
mains.
The AC input is connected
to the UPS output. Plug AC input power cord
to AC input correctly.
The icon and the warning
code flashing on LCD
display and alarm is sounding
every 2 seconds.
EPO function is activated. Set the circuit in closed
position to disable EPO
function.
The icon and flashing on
LCD display and alarm is
sounding every 2 seconds.
Line and neutral
conductors of UPS input
are reversed.
Rotate mains power
socket by 180° and then
connect to UPS system.
The icon and flashing
on LCD display and alarm is
sounding every 2 seconds.
The external or internal
battery is incorrectly
connected.
Check if all batteries are
connected well.
Fault code is shown as 27 and
the icon is lighting on
LCD display and alarm is
continuously sounding.
Battery voltage is too high
or the charger is fault. Contact your dealer.
Fault code is shown as 28 and
the icon is lighting on
LCD display and alarm is
continuously sounding.
Battery voltage is too low
or the charger is fault. Contact your dealer.
The icon and is
flashing on LCD display and
alarm is sounding every second.
UPS is overload Remove excess loads
from UPS output.
UPS is overloaded.
Devices connected to the
UPS are fed directly by the
electrical network via the
Bypass.
Remove excess loads
from UPS output.
After repetitive overloads,
the UPS is locked in the
Bypass mode. Connected
devices are fed directly by
the mains.
Remove excess loads
from UPS output first.
Then shut down the UPS
and restart it.
Fault code is shown as 43 and
the icon is lighting on
LCD display. Alarm is
continuously sounding.
The UPS shut down
automatically because of
overload at the UPS
output.
Remove excess loads
from UPS output and
restart it.

16
LA
-
ON
-
LCD
-
V.09
Symptom
Possible cause
Remedy
Fault code is shown as 14 and
the icon is lighting on
LCD display and alarm is
continuously sounding.
The UPS shut down
automatically because
short circuit occurs on the
UPS output.
Check output wiring and if
connected devices are in
short circuit status.
Fault code is shown as 01, 02,
03, 11, 12, 13 and 41 on LCD
display and alarm is continuously
sounding.
A UPS internal fault has
occurred. There are two
possible results:
1. The load is still
supplied, but directly from
AC power via bypass.
2. The load is no longer
supplied by power.
Contact your dealer
Battery backup time is shorter
than nominal value Batteries are not fully
charged Charge the batteries for at
least 5 hours and then
check capacity. If the
problem still persists,
consult your dealer.
Batteries defect Contact your dealer to
replace the battery.
The icon and the warning
code flashing on LCD
display and alarm is sounding
every 2 seconds.
Fan is locked or not
working Check fans and notify
dealer!!
Fault code is s own as
45
on LCD
display. At t e same time, alarm is
continuously sounding.
T e c arger does not ave
output and battery voltage
is less t an 10V/PC.
C
o
ntact
your dealer
.
5. Storage and Maintenance
Operation
The UPS system contains no user-serviceable parts. If the battery service life (3~5 years
at 25°C ambient temperature) has been exceeded, the batteries must be replaced. In this
case, please contact your dealer.
Storage
Before storing, charge the UPS 5 hours. Store the UPS covered and upright in a cool, dry
location. During storage, recharge the battery in accordance with the following table:
Storage Temperature Recharge Frequency Charging Duration
-25°C - 40°C Every 3 months 1-2 hours
40°C - 45°C Every 2 months 1-2 hours
Be sure to deliver the spent battery to a recycling facility or ship it to your
dealer in the replacement battery packing material.

17
LA
-
ON
-
LCD
-
V.09
6. Specifications
MODEL
LA
-
ON
-
1K
-
LCD
-
V.09 (L*)
LA
-
ON
-
2K
-
LCD
-
V.09 (L*)
LA
-
ON
-
3K
-
LCD
-
V.09 (L*)
CAPACI
TY
**
1000 VA / 900 W 2000 VA / 1800 W 3000 VA / 2700 W
INPUT
Nominal Voltage 230 VAC or 120 VAC
Voltage Range 110 - 300 VAC ± 5% or 55 - 150 VAC ± 5% @ 50% load
160 - 300 VAC ± 5% or 80 - 150 VAC ± 5% @ 100% load
Frequency Range 40Hz ~ 70 Hz
Phase Single phase with ground
Power Factor
≧
0.99 @ nominal voltage (100% load)
THDi
≦
5% @ 205-245 VAC or 100-130 VAC
THDU < 1,6% @ linear load and full battery load
OUTPUT
Output Voltage 200/208/220/230/240 VAC or 100/110/115/120/127 VAC
AC Voltage Regulation (Batt.
Mode) ± 1%
Frequency Range
(Synchronized Range) 47 ~ 53 Hz or 57 ~ 63 Hz
Frequency Range (Batt. Mode) 50 Hz ± 0.1 Hz or 60 Hz ± 0.1 Hz
Current Crest Ratio 3:1
Harmonic Distorsion
≦
2 % THD (Linear Load)
≦
4 % THD (Non-linear Load)
Transfer
Time
AC Mode to Batt.
Mode Zero
Inverter to Bypass 4 ms (Typical)
Waveform (Batt. Mode) Pure Sinewave
EF
FICIENCY
AC Mode 90% 91% 91%
ECO Mode 97%
Battery Mode 89% 89% 90%
B
AT
T
E
RY
Standard
Model
Battery Type 12V / 7AH 12V / 7AH 12V / 9AH
Numbers 3 6 6
Typical Recharge
Time 4 hours recover to 90% capacity
Charging Current
(máx) 1.5 A (max.)
Charging Voltage
41.0 VDC ± 1% 82.1 VDC ±1%
Long-run
Model
Battery Type Depending on the capacity of external batteries
Charging Current
(máx) 1/2/4/6/8 A (Selectable via LCD setting)
Charging Voltage
41.0 VDC ± 1% 82.1 VDC ±1%
CONNECTORS
Current outputs 4xIEC 8xIEC 6xIEC + Terminal Block
Comunication ports 1xUSB + 1xRS232 + 1xIntelligent Slot SNMP
PHYSICAL
Dimension, D x W x H (mm) 397 X 145 X 220 421 X 190 X 318
Net Weight
(Kgs) Standard Model 12,5 25,8 27
Long-run Model 5,8 12 13,2
ENVIRONMENT
Humidity 20-95 % RH @ 0- 40°C (non-condensing)
Noise Level < 50dB @ 1 Meter
MANAGEMENT
Smart RS-232 & USB Supports Windows 2000/2003/XP/Vista/2008/7/8, Linux, Unix and Mac
Optional SNMP Power management from SNMP manager and web browser
* L states for long-run model
** Derate capacity to 95% when the output voltage is adjusted to 115VAC, derate capacity to 90% when the output voltage is
adjusted to 110VAC and derate capacity to 80% when the output voltage is adjusted to 100VAC/200VAC/208VAC
Note: Product specifications are subject to change without further notice.

SAI Online
1K/2K/3K
Sistema de Alimentación Ininterrumpida
anual de usuario
ES
This manual suits for next models
5
Table of contents
Other lapara UPS manuals

lapara
lapara LA-VST-1000-LCD User manual

lapara
lapara LA-ON-DC User manual

lapara
lapara LA-VST-650LCD User manual

lapara
lapara LA-ITR-800-LCD User manual

lapara
lapara LA-GL-ON-1K-LCD User manual

lapara
lapara 6KR User manual

lapara
lapara 1K User manual

lapara
lapara LA-VST-650 User manual

lapara
lapara 1K User manual

lapara
lapara 1K User manual
Popular UPS manuals by other brands

Lowell power
Lowell power UPS-XBPA Series User & installation manual

Xtreme Power Conversion
Xtreme Power Conversion M90S Series User & installation manual

Digitus
Digitus DN-170013 instruction manual

CyberPower
CyberPower Smart App Sinewave Series user manual

Eaton
Eaton BladeUPS none user guide

TECHWARE
TECHWARE ERA LCD 0.65 Rack Mount user manual