Lauda RP 3050 C User manual

2SHUDWLQJLQVWUXFWLRQV
352/,1(.U\RPDWV
/RZWHPSHUDWXUH7KHUPRVWDWV
53&53&:
53&53&:
53&53&:
53&53&:


Translation of the original operating instructions
release 11/2018 e
replaces release 10/2018 d, 05/2016 b2, 03/13, 01/09, 06/08
YAUE0007
Valid from:
software control system (Master) version 2.13
software safety system (Master) version 2.07
software operating system (Command) version 3.45
LAUDA DR. R. WOBSER GMBH & CO. KG
Pfarrstraße 41/43
97922 Lauda-Königshofen
Germany
software chilling system version 2.13
software analog IO module version 3.14
software serial IO module version 3.22
software digital IO module version 3.14
software solenoid valve version 3.06
software Ethernet module version 1.23
software EtherCAT module version 1.06
Phone: +49 (0)9343 503-0
Fax: +49 (0)9343 503-222
E-Mail [email protected]
Internet http://www.lauda.de
Operating instructions
PROLINE Kryomats
Low-temperature Thermostats
with SmartCool System
RP 3050 C, RP 3050 CW
RP 4050 C, RP 4050 CW
RP 3090 C, RP 3090 CW
RP 4090 C, RP 4090 CW
Read the instructions before starting work!


Proline Kryomats
YAUE0007 / 10/2/2018 Prefixed safety notes 5
Prefixed safety notes
Before operating the equipment, please read carefully all the instructions and safety
notes in Section 1.
If you have any questions, please phone us!
Follow the instructions on setting up, operation etc. This is the only way to avoid
incorrect operation of the equipment and to ensure full warranty protection.
The master head is supplied with power via the lower section of the unit. After
switching off the head using the switch at the front of the head and/or using the
switch at the back of the head, mains voltage (230 volts) is still present on the
master head.
Switch off the unit by using the rotary switch on the front panel.
Switch off the equipment and pull out the mains plug:
for servicing or repair,
moving the equipment!
Transport the equipment with care!
The unit may NEVER be overturned nor put upside down!
Equipment and its internal parts can be damaged:
by dropping,
by shock.
Technically qualified personnel must only operate the equipment!
Never operate the equipment without the heat transfer liquid!
Do not start up the equipment if ...
it is damaged or leaking,
cable (not only supply cable) is damaged.
Drain the bath before moving the equipment!
Do not carry out any technical changes on the device!
Have the equipment serviced or repaired by properly qualified personnel only!
The Operating Instructions include additional safety notes, which are identified by a triangle
with an exclamation mark. Carefully read the instructions and follow them accurately!
Disregarding the instructions may have serious consequences, such as damage to the
equipment, damage to property or injury to personnel!
We reserve the right to make technical alterations!

Proline Kryomats
6Contents YAUE0007/10/2/2018
Contents
Prefixed safety notes ....................................................................................................................................5
1SAFETY INFORMATION.................................................................................................................................9
1.1 SAFETY INFORMATION..................................................................................................................................9
1.2 GENERAL SAFETY INFORMATION................................................................................................................ 10
1.3 OTHER SAFETY INFORMATION.................................................................................................................... 10
1.4 EU CONFORMITY ...................................................................................................................................... 11
2BRIEF OPERATING INSTRUCTIONS ......................................................................................................... 12
2.1 MENU STRUCTURE:MASTER ..................................................................................................................... 13
2.2 MENU STRUCTURE:COMMAND REMOTE CONTROL..................................................................................... 14
3CONTROLS AND FUNCTIONAL ELEMENTS ............................................................................................ 15
4UNIT DESCRIPTION..................................................................................................................................... 20
4.1 ENVIRONMENTAL CONDITIONS ................................................................................................................... 20
4.2 TYPES OF UNIT ......................................................................................................................................... 20
4.3 VARIOFLEX PUMP...................................................................................................................................... 20
4.4 MATERIALS............................................................................................................................................... 21
4.5 TEMPERATURE DISPLAY,CONTROL AND SAFETY CIRCUIT............................................................................. 21
4.6 PROGRAMMER AND RAMP FUNCTION.......................................................................................................... 22
4.7 INTERFACES............................................................................................................................................. 22
4.8 INTERFACE MODULES (ACCESSORIES)........................................................................................................ 22
4.9 REFRIGERATING UNIT................................................................................................................................ 23
4.10 AVOIDANCE OF DEWING......................................................................................................................... 23
4.11 HEATER RATING AND POWER CONSUMPTION FROM THE MAINS................................................................. 23
5UNPACKING................................................................................................................................................. 24
5.1 AFTER UNPACKING.................................................................................................................................... 24
5.2 STANDARD ACCESSORIES......................................................................................................................... 25
5.3 PACKING AND UNPACKING WITH ORIGINAL PACKAGING MATERIAL................................................................. 25
5.3.1 Background..................................................................................................................................... 25
5.3.2 Requirements.................................................................................................................................. 25
5.3.3 Unpacking the device...................................................................................................................... 26
5.3.3.1 Outer cardboard box................................................................................................................ 26
5.3.3.2 Lift device from the pallet......................................................................................................... 27
5.3.4 Repacking with original packing material........................................................................................ 28
5.4 IN-PLANT TRANSPORTWITH HAND PELLET TRUCK OR FORK LIFTER............................................................... 28
5.5 BEFORE PREPARATION.............................................................................................................................. 29
6PREPARATION ............................................................................................................................................ 30
6.1 ASSEMBLY AND SITING.............................................................................................................................. 30
6.2 FILLING AND DRAINING .............................................................................................................................. 32
6.3 CONNECTION OF THE COOLING WATER....................................................................................................... 34
6.4 HEAT TRANSFER LIQUIDS,COOLING WATER AND HOSES .............................................................................. 35
6.5 CONNECTING EXTERNAL LOADS................................................................................................................. 38
7STARTING UP .............................................................................................................................................. 40
7.1 MAINS CONNECTION.................................................................................................................................. 42
7.2 SWITCHING ON ......................................................................................................................................... 42
7.3 SWITCHING OFF /STANDBY........................................................................................................................ 44
7.4 KEY FUNCTIONS........................................................................................................................................ 45
7.4.1 General key functions and pilot lamps............................................................................................ 45
7.4.2 Changing window information......................................................................................................... 48
7.4.3 Locking the keyboard...................................................................................................................... 49

Proline Kryomats
YAUE0007 / 10/2/2018 Contents 7
7.5 IMPORTANT SETTINGS................................................................................................................................51
7.5.1 Temperature setpoint setting...........................................................................................................51
7.5.2 Displaying the actual external temperature .....................................................................................53
7.5.3 Setting pump power or standby.......................................................................................................54
7.5.4Activate external pump ....................................................................................................................56
7.5.5 Activating external control................................................................................................................56
7.5.6 Current consumption from the mains...............................................................................................58
7.5.7 Setting the date and time.................................................................................................................59
7.5.8 Display resolution setting.................................................................................................................60
7.6 SPECIAL SETTINGS ....................................................................................................................................61
7.6.1 Defining the type of start mode........................................................................................................61
7.6.2 Defining temperature limits..............................................................................................................62
7.6.3 Setpoint offset operating mode........................................................................................................63
7.6.4 Restoring works settings..................................................................................................................64
7.6.5 Setting the volume of the acoustic signals.......................................................................................65
7.6.6 Entering the offset of the internal temperature probe......................................................................65
7.6.7 Restoring the works setting of the internal temperature-probe offset..............................................66
7.6.8 Entering the offset of the external temperature probe.....................................................................67
7.6.9 Restoring the works setting of the external temperature-probe offset.............................................67
7.7 GRAPHICAL DISPLAY OF TEMPERATURE MEASUREMENTS .............................................................................68
7.8 PROGRAMMER...........................................................................................................................................70
7.8.1 Program example.............................................................................................................................70
7.8.2 Selecting and starting the program (Start, Hold, Stop)....................................................................72
7.8.3 Interrupting, continuing or terminating the program (Hold, Continue, Stop)....................................73
7.8.4 Creating or modifying a program (Edit)............................................................................................74
7.8.5 Defining the number of program loops (Loops)...............................................................................78
7.8.6 Viewing the program sequence as a graph (Graph)........................................................................78
7.8.7 Obtaining information on a program (Info).......................................................................................79
7.9 RAMP FUNCTION........................................................................................................................................80
7.10 TIMER FUNCTION....................................................................................................................................81
7.11 CONTROL PARAMETERS .........................................................................................................................82
7.11.1 Internal control variable (integral measurement probe)...................................................................83
7.11.1.1 Proven settings for control parameters and pump (integral measurement probe)...................83
7.11.2 External control variable (External measurement probe) ................................................................83
7.11.2.1 Steps for setting the control parameters for external control....................................................84
7.11.3 Internal and external control parameter sets ...................................................................................85
7.11.4 Self Adaption....................................................................................................................................87
7.12 ALARMS,WARNINGS AND ERRORS .........................................................................................................89
7.12.1 Overtemperature protection and checking.......................................................................................89
7.12.2 Low-level alarm and low-level checking ..........................................................................................91
7.12.3 High-level settings............................................................................................................................92
7.12.4 High-level warning or alarm.............................................................................................................92
7.12.5 Pump-motor supervision: Overload or blockage..............................................................................93
7.12.6 Pump-motor supervision: Dry running .............................................................................................94
7.12.7 Compressor Overtemp.....................................................................................................................94
7.12.8 Three-phase current ........................................................................................................................94
7.12.9 Fault list „Alarms and Warnings“......................................................................................................95
8INTERFACE MODULES................................................................................................................................98
8.1 INSTALLING OF MODULES ...........................................................................................................................98
8.2 MENU STRUCTURE FOR ALL MODULES.......................................................................................................100
8.3 SERIAL INTERFACE RS-232/485 ..............................................................................................................101
8.3.1 Connecting cables and interface test RS-232 ...............................................................................101
8.3.2 Protocol RS-232.............................................................................................................................102
8.3.3 Connecting cable RS-485..............................................................................................................102
8.3.4 Protocol RS-485.............................................................................................................................103
8.3.5 Write commands (Data commands to the thermostat)..................................................................103
8.3.6 Read commands (Data requested from the thermostat) ...............................................................104

Proline Kryomats
8Contents YAUE0007/10/2/2018
8.3.7 Error messages............................................................................................................................. 107
8.3.8 Driver software for LABVIEW®..................................................................................................... 107
8.4 ANALOGUE MODULE................................................................................................................................ 108
8.5 CONTACT MODULE.................................................................................................................................. 109
8.5.1 Contact module LRZ 915 with three inputs and three outputs ..................................................... 109
8.5.2 Namur-Contact module LRZ 914 with only one input and one output.......................................... 110
9MAINTENANCE.......................................................................................................................................... 111
9.1 DEVICE STATUS...................................................................................................................................... 111
9.1.1 Interrogating the device type......................................................................................................... 111
9.1.2 Software version ........................................................................................................................... 111
9.1.3 Serial numbers.............................................................................................................................. 111
9.1.4 Device data ................................................................................................................................... 111
9.1.5 Fault memory................................................................................................................................ 112
9.2 CLEANING .............................................................................................................................................. 112
9.2.1 Cleaning the surface of the device................................................................................................ 112
9.2.2 Draining the water-cooled condenser........................................................................................... 113
9.3 SERVICING,CLEANING,REPAIR AND DISPOSAL INFORMATION..................................................................... 113
9.3.1 Servicing ....................................................................................................................................... 114
9.3.2 Service intervals............................................................................................................................ 115
9.3.3 Testing the heat transfer liquid...................................................................................................... 115
9.3.4 Cleaning the condenser................................................................................................................ 116
9.3.4.1 Air-cooled condenser............................................................................................................. 116
9.3.4.2 Water-cooled condenser........................................................................................................ 116
9.3.4.2.1 Cleaning the dirt trap.......................................................................................................... 116
9.3.4.2.2 Decalcifying the water cooling circuit ................................................................................. 117
9.3.5 Repair information......................................................................................................................... 117
9.3.6 Remedying faults .......................................................................................................................... 118
9.4 DISPOSAL INFORMATION ......................................................................................................................... 119
9.4.1 Disposal of the refrigerant............................................................................................................. 119
9.4.2 Disposal of the packaging............................................................................................................. 119
9.5 HELP DESK AND ORDERING REPLACEMENT PARTS .................................................................................... 120
10 ACCESSORIES....................................................................................................................................... 121
11 TECHNICAL DATA AND DIAGRAMS.................................................................................................... 122
12 INDEX...................................................................................................................................................... 130
CONFIRMATION

Proline Kryomats
YAUE0007/ 10/2/2018 Safety information 9
1 Safety information
1.1 Safety information
Danger!
Type and source
Consequences of non-compliance
Action 1
Action ...
"DANGER" indicates an immediate dangerous situation which –if the safety
requirements are ignored –may result in fatal or severe, irreversible injuries.
Warning!
Type and source
Consequences of non-compliance
Action 1
Action ...
"WARNING" indicates a possible dangerous situation which –if the safety
requirements are ignored –may result in fatal or severe, irreversible injuries.
Caution!
Type and source
Consequences of non-compliance
Action 1
Action ...
"CAUTION" indicates a possible dangerous situation which –if the safety
requirements are ignored –may result in slight, reversible injuries.
Notice
Type and source
Consequences of non-compliance
Action 1
Action ...
"NOTICE" warns of possible property or environmental damage.
Reference
Refers to further information in other sections.
Note
Here special attention is drawn to some aspect.

Proline Kryomats
10 Safety information YAUE0007 / 10/2/2018
1.2 General safety information
A heating and cooling thermostat heats or cools and circulates heat transfer liquids according to
specified parameters. This involves hazards due to high or low temperatures, fire and general hazards
due to the application of electrical energy.
The user is largely protected by the application of relevant standards.
Further hazard sources may arise due to the type of tempering medium, e.g. by exceeding or
undercutting certain temperature thresholds or by the breakage of the container and reaction with the
heat transfer liquid.
It is not possible to consider all eventualities. They remain largely subject to the judgment and
responsibility of the operator.
The equipment must only be used as prescribed and as described in these operating instructions. This
includes operation by instructed specialist personnel.
The equipment is not rated for use under medical conditions according to DIN EN 60601-1 or
IEC 601-1.
Classification in accordance with EMC requirements of DIN EN 61326-1
Device
Immunity
Emissions class
Customer power supply
Proline Kryomat
Type 2 in
accordance with
DIN EN 61326-1
Emissions Class B
in accordance with
CISPR 11
Only for EU
Domestic connection value
≥100 A
Proline Kryomat
Type 2 in
accordance with
DIN EN 61326-1
Emissions Class B
in accordance with
CISPR 11
Worldwide
No limitation
Only for the USA:
Instructions for Class A digital devices
“This equipment has been tested and found to comply with the limits for Class A digital device, pursuant
to Part 15 of the FCC (Federal Communication Commission) Rules. These limits are designed to
provide reasonable protection against harmful interference when the equipment is operated in a
commercial environment. This equipment generates, uses, and can radiate radio frequency energy and,
if not installed and used in accordance with the instruction manual, may cause harmful interference to
radio communications. Operation of this equipment in a residential area is likely to cause harmful
interference in which case the user will be required to correct the interference at his own expense.”
“This device complies with Part 15 of the FCC (Federal Communication Commission) Rules. Operation
is subject to the following two conditions: (1) This device may not cause harmful interference, and (2)
this device must accept any interference received, including interference that may cause undesired
operation.”
Only for Canada:
“This Class A digital apparatus complies with Canadian ICES-003” (ICES = Interference Causing
Equipment Standards).
« Cet appareil numérique de la Classe A est conforme à la norme NMB-003 du Canada ».
1.3 Other safety information
Only connect equipment to PE grounded mains sockets.
At higher operating temperatures, parts of the bath cover can reach surface temperatures exceeding
70 °C. Be careful when touching it! Danger of burning!
Use suitable hoses (6.3).
Secure hose against slippage with the aid of hose clips. Avoid kinks in the hoses.
Check hoses from time to time for any possible material fatigue.

Proline Kryomats
YAUE0007/ 10/2/2018 Safety information 11
Thermal medium hoses and other hot parts must not come into contact with the mains cable.
With the use of thermostats as circulating thermostats hot or cold liquid can be emitted when the hose
breaks, presenting a hazard to persons and material.
If no external load is connected, the pump outflow must be closed (use screw plugs) and the bypass
valve must be set to "internal" (4.3).
Take into account the thermal expansion of the heat transfer oils with increasing bath temperature.
Irritant vapors may develop, depending on the heat transfer liquid and operating mode used. Always
ensure that the vapors are adequately extracted. Use the bath cover.
By changing the heat transfer liquid from aqueous heat transfer liquid to a thermal transfer liquid for
temperatures above 100°C, carefully remove all water residues, including from the hoses and loads.
When doing this, also open the blanking caps of the pump outputs and inputs and blow
compressed air through all the pump outputs and inputs. Danger of scald due to delay in
boiling!
Withdraw the mains plug before cleaning, maintenance or moving the thermostat.
Specialist personnel must only carry out repairs in the control section.
The following action may start the thermostat unintentionally from the standby mode: Previously
activated timer mode (7.10), "Start" command via interfaces (8).
Figures of temperature constancy and display accuracy apply under normal conditions according to
DIN 12876. Electromagnetic high frequency fields may in special cases lead to unfavorable values.
Safety is not impaired.
Only water-cooled devices:
The return hose of the water-cooling must be securely fixed on the outlet port in order to prevent the
hose sliding off uncontrollably, also during pressure surges.
The return hose of the water-cooling must be fixed on the outlet port that hot cooling water cannot
splash out.
It is essential to prevent kinking or squashing of the return hose for the water cooling. Excessive
pressure can cause the cooling water hoses to tear and hot water to escape.
To prevent damages by a leakage of the cooling water system its recommended to use a leak-water
detector with shut-off valve (Aqua Stop).
1.4 EU conformity
The device complies with the basic health and safety requirements outline in
the Directives listed below.
Machinery Directive 2006/42/EC
EMC Directive 2014/30/EU
LAUDA DR. R. WOBSER GMBH & CO. KG –Pfarrstraße 41/43 –
97922 Lauda-Königshofen –Germany
The device does not fall under Pressure Equipment Directive
2014/68/EU because the device is only classified as high as
Category 1 and is covered by the Machinery Directive.

Proline Kryomats
12 Brief operating instructions YAUE0007 / 10/2/2018
2 Brief operating instructions
These brief instructions shall give you the possibility to operate the unit quickly. For safe
operation of the unit, it is necessary to read carefully all the instructions and safety
notes!
1. Assemble unit and add items as appropriate (6.1).
The unit may NEVER be overturned nor put upside down!
Take care of the hose tubing connections (6.3 and 6.5).
2. Fill the unit with corresponding heat transfer liquid (6.3). The units are designed for
operation with non-flammable and flammable liquids to DIN EN 61010-2-010. Take care
of the level of the heat transfer liquid! (6.2).
3. Compare the information on the rating label with the supply details.
4. Connect the unit only to a socket with a protective earth (PE) connection.
5. Check whether the switch at the back of the master control element is in
the "ON = –" position.
6. Check whether the switch at the front of the master control element is in the "ON = l"
position.
7. Set the rotary switch on the front panel to "ON = l". The unit starts
operating.
8. With set the overtemperature cut-off point to a value clearly above room temperature
(7.12.1).
9. Now you see the current bath temperature in the
display, for example:
If instead, a warning or error message is displayed, then refer to Section 7.12.
Bath-temperature
02%32
°C

Proline Kryomats
YAUE0007 / 10/2/2018 Brief operating instructions 13
2.1 Menu structure: Master
These settings and configurations can be entered more easily and in a more clear manner via the
Command remote control. Therefore, for the Master control element they are not explained in more detail
in this operating manual.
Bath temperature
2%32
°C
Pump power.5-8/Standby.0
Pu 8
°C
Setpoint
SEt
°C
Control Intern / Extern
Con 1
°C
Further settings
MNEmv
°C
Configure modules
MNpfv
°C
End
End
°C
Display flashes. Set setpoint
with or . Display
is accepted after 4 sec. or
proceed immediately
with the key:
Control parameters,
setpoint resolution,
setpoint-source input,
calibration, etc.
Protection system,
Command, cooling system,
analog and RS-232 digital
module, etc.
External temperature
2%02
°C
EXT
Display flashes. Set value
with or . Display
is accepted after 4 sec. or
proceed immediately
with the key:
(7.5.3)
(7.5.4)
(7.5.1)

Proline Kryomats
14 Brief operating instructions YAUE0007 / 10/2/2018
2.2 Menu structure: Command Remote Control
Menu
Display
Sounds Master
Sounds Command
Language
Master-Mode
Autostart
Current Consumpt.
Pump
Settings
Clock
Graph
Programmer
Interfaces 1
Control
Limits
Pump Level 0, 5…8
External pump
Start unfill condense.
Calibration
Works settings
Resolution
Device status
Display data
Basic settings
Overlevel handling
Set time
Set data
Timer 1
Timer 2
Format of date
Program 1
Program 2
Program 3
Program 4
Program 5
Ramp function
Serial Command
2serial Master /
Profibus
Analog interfaces
Switching contact
Smart Cool
Control parameters
Control para. sets
Tv manual/auto
Self Adaption
Correction limitation
Control variable
Control parameters
Setpoint offset
Max. Fan [%] 60
Brightness
Contrast
intern Pt100
extern Pt100
Device type
Software Version
Serial numbers
Device data
Error store
Mode
Baud rate
RS485 address
internal
external Pt100
Analog interface
RS232/485
Calibration
Default
Alarm
Warning
all default
Basic window
Standard window
Super window
Edit
Default
T il (min)
T ih (max)
Xp
Tn
Tv (auto)
Td (auto)
Kpe
Tne
Tve (auto)
Tde (auto)
Xpf
Prop_E(a)
Automatic
Manual
Status
Setpoint
Identification
Actual Parameters
off
external Pt100
RS-232
Status
Edit
Loops
Graph
Info
Start / Stop
Hold / continue
Modify
Erase
Show chart
Offset source
Setpoint offset
All Modules
Master
Command
Cool
Other connected
modules
English
Deutsch
Français
Español
All default
Only control par. int.
Only control par. ext.
Only miscellaneous
Display
Settings
Mode
Displayed value
Legend
Sample Time
Time axis
Time base
Temp. scale
Temp. limits
off
on
automatic
none
Warning
Warn. + Heater off
Alarm
Status
Temp. Change
Time
Time unit
18.2
2no menu in
Command
on
off
on

Proline Kryomats
YAUE0007 / 10/2/2018 Controls and functional elements 15
3 Controls and functional elements
1
2
3 and 4
5
6
7
8
9
1 Command remote control (see page 15)
2 Master control element
3 Pump connection on the side:
Pump outflow or pressure output
Suction nozzle (return to bath)
4 Bypass valve (see illustration on this page).
5 Bath cover
6 Rotary switch for power supply
7 Front cover (closed)
8 Grille (on both sides)
9 Four steering transport rollers, two off them with
stoppers
1
2
3
Pump connection on the side:
1 Suction nozzle (return to bath)
Pump outflow or pressure output
(closed off with screw plug)
refer to housing for label
2 Bypass valve
(in "external" position)
3 Pump outflow, pressure output
Suction nozzle (return to bath)
(closed off with screw plug)
refer to housing for label

Proline Kryomats
18 Controls and functional elements YAUE0007 / 10/2/2018
1
2
3
4
5
6
7
8
9
1 Command remote control (see next page)
2 Covers for the two module slots
3 Connection socket 10S
for the external Pt100 temperature probe
4 Connection socket 70S (LAUDA internal bus
(LiBus)) for bus suitable for unit and to which the
refrigerating lower section and Command remote
control are connected
5 Mains switch
6 Connection socket 51H
7 Air intake for electronic head
8 Pump connection rear and on the side:
Suction nozzle (return to bath) & pump outflow
or pressure output
refer to housing for label
9 Mains connecting lead

Proline Kryomats
YAUE0007 / 10/2/2018 Controls and functional elements 19
Control element: Master
Control element: Command
Error signal (red LED is blinking)
Bath controlled by external
temperature source (green LED
is lit)
The temperature of an external
source is displayed
(EXT is lit green)
Cooler active (blue LED is lit)
Overtemperature set point to
check or set Tmax
Select and Enter keys
Graphical display,
here in the standard window displaying the values:
Actual temperature Tint of internal bath temperature probe
Setpoint temperature Tset
Actual temperature Text of the external temperature probe
Bath level
Pump level
Five soft-key duo-keys –their
associated functions are
shown in the display.
Enter key
Cursor key
Decimal point or "-" symbol
Standby key,
brings the thermostat into
the idle mode. Heater,
refrigerating machine and
pump are switched off
Escape key to quit a
window without any
changes
EXT
Heater active (yellow LED is lit)
Mains On
(green LED is lit)
RS-232/485-socket
(hidden on the back of Command)
Yellow Stand-By LED

Proline Kryomats
20 Unit description YAUE0007 / 10/2/2018
4 Unit description
4.1 Environmental conditions
The operation of the thermostats is only allowed under the following conditions as specified in
DIN EN 61010-2-010:2003 and DIN EN 61010-1:2001:
Indoor use only.
Altitude up to 2000 m above sea level.
Foundation must be dense, even, non-slippery and non-flammable.
Keep clear distance (6.1 Assembly and siting).
Ambient temperatures range (11 Technical data).
Use only within this range for an undisturbed operation.
Mains supply voltage fluctuations (11 Technical data).
Relative humidity (11 Technical data).
Transient over voltage according to Installation Categories (Over voltage Categories) II.
Pollution degree: 2.
4.2 Types of unit
The type designation of the Proline Kryomats comprises the prefix R (to designate the refrigeration
machine), a P for Proline, the bath volume in liters and the lowest bath temperature (guide figure
without arithmetic sign).
The designation is supplemented with a "C" which indicates the presence of the Command remote
control.
For units with water-cooling, the type designation is supplemented with a "W".
Examples: RP 4090 CW is a low-temperature thermostat with 40-liter bath and -90 °C lowest
temperature. The unit has a Command remote control and is water-cooled.
4.3 Varioflex pump
All units are fitted with a Varioflex pump with a 4-stage variable drive (pump level 5 to 8). The pump
power can therefore be optimally matched to the relevant task. In order to achieve optimum
temperature homogeneity in the heat transfer liquid in the bath, it is recommended to select the pump
level in dependence of the viscosity of the heat transfer liquid; therefore at higher viscosity to increase
the pump level.
Be cautious at higher bath levels to avoid liquid to slop over the bath edge.
The user cannot set the pump levels 1 to 4, because there is no sufficient temperature homogeneity in
the bath vessel. With pump level 0 the unit goes into the standby mode. It should be noted that the
heat input of the pump into the bath increases with increasing pump level.
With the Varioflex pump, open containers can be operated at a constant level when a level controller
(accessory LCZ 0660) is used.
At the right-hand side and at the back of the unit outflow and inflow nozzles of the pump are fitted for
external loads. This means that up to two external loads can be directly connected without a
distributor. Pump connections, which are not required, must be closed off with the supplied caps and
union nuts.
A bypass valve can subdivide the total volume flow variably between the bath (internally) and the
connected load (externally). Attention: the external application must not block the volume flow. If no
load is connected to the pump connector, the bypass valve must be set to the “internal”position for
the best bath circulation. All pump connections must be closed off with the supplied caps and union
nuts.
This manual suits for next models
7
Table of contents
Other Lauda Thermostat manuals

Lauda
Lauda Integral T 1200 User manual

Lauda
Lauda IN 550 XT User manual

Lauda
Lauda RCS 5 User manual

Lauda
Lauda RP 845 User manual

Lauda
Lauda RE 1050 G User manual

Lauda
Lauda RE 104 User manual

Lauda
Lauda P 10 User manual

Lauda
Lauda ECO Silver E 4 S User manual

Lauda
Lauda RA 12 User manual

Lauda
Lauda IN 130 T User manual

Lauda
Lauda Integral XT 150 User manual

Lauda
Lauda L 100 User manual

Lauda
Lauda PROLINE P 5 C User manual

Lauda
Lauda PTT User manual

Lauda
Lauda RE 212 J User manual

Lauda
Lauda Alpha User manual

Lauda
Lauda PROLINE Kryomats Series User manual

Lauda
Lauda LOOP 100 User manual

Lauda
Lauda Ecoline RE 320 User manual

Lauda
Lauda Proline RP 845 C User manual