3. MOUNTING THE REMOTE KEYPAD
The diagram below illustrates how to mount the remote keypad to a panel. Use
the template in Section 2 to mark the location of the mounting holes on the
panel.
PANEL
REMOTE
KEYPAD
GASKET
MOUNTING
SCREWS
2. SMREMOTEKEYPADTEMPLATE
Hold this page against the panel where the remote keypad is to be mounted,
and use a center punch to mark the location of the holes. The dotted line is the
outline of the remote keypad.
174194.00 - SM SERIES
REMOTEKEYPAD INSTRUCTIONS
The SM Series Remote Keypad option allows the SM Series drive to be
programmed and controlled from up to 8 feet away (typically from the
front of the enclosure that houses the SM drive). When properly mounted,
the remote keypad is rated up to NEMA 4X.
In addition to the functions available on the front of the SM drive, the
remote keypad has Start/Stop and Forward/Reverse functions.
NOTE: The Remote Keypad option will only work with SM drives that
have parameter version “320” or higher. The parameter version appears
momentarily on the drive display when it is powered up, and also appears
on a sticker on the drive’s heatsink.
1. PARTS LIST
The SM Remote Keypad kit includes the following parts:
(1) Remote Keypad (1) Gasket
(2) Self-tapping Mounting Screws (1) Instruction Sheet
(1) Eight foot cable
NOTE: The supplied cable is unshielded and can only be used in low-noise
environments. In high-noise environments, use Belden 9842, Carol C4842, or
equivalent (24 gage minimum) wire only. The maximum cable length that can
be used is 8 feet.
1/8” hole
1/8” hole
1.57”
1.32”
1.38” to 1.5”
hole
3.38”
2.19”
UP
Max Depth = 0.72”
4. WIRING CONNECTIONS
NOTE: The supplied cable is unshielded and can only be used in low-noise
environments. In high-noise environments, use Belden 9842, Carol C4842, or
equivalent (24 gage minimum) wire only. The maximum cable length that can
be used is 8 feet.
WARNING!
Improper wiring may result in damage to the Remote Keypad. Keep the
remote keypad cable away from power wiring.
The Belden and Carol cables specified consist of two twisted pairs. Make
sure one twisted pair is used for connections to 13B and 13E, and the
other is used for connections to 11 and 2. Do not mix connections
between twisted pairs.
REMOTE KEYPAD
(BACK VIEW)
13B
13E
11
2
UP
125 6 11 13A 13B 2513E
Cable included with kit
does not have a shield
WARNING!
If OEM mode is selected (using Parameter 48), and if the OEM Default
settings for Parameters 11, 12, and 14 are not “13”, “21”, and “02” respectively,
the remote keypad will be disabled, and the STOP key WILL NOT work.
Refer to the SM manual for more information on OEM Default settings.
LEESON ElectricLEESON Electric
LEESON ElectricLEESON Electric
LEESON Electric • 2100 Washington St. • Grafton, WI 53024 • Ph: (262) 377-8810 • Fax: (262) 377-9025 • www.leeson.com
8. TROUBLESHOOTING
RF Reverse/Forward key: Selects Forward or Reverse direction.
The R/F key is only active if Parameter 17 - ROTATION is set
to “02” (FORWARD AND REVERSE).
When the R/F key is pressed, the symbol for the opposite
direction will blink on the display. Press the Mkey within four
seconds to confirm the rotation change.
Below are the display symbols used to indicate direction:
FORWARD REVERSE
6. REMOTE KEYPAD FUNCTIONS
The Mkey and the ▲and ▼keys on the remote keypad function the same as
the Mode button and the ▲and ▼buttons on the drive. The other remote
keypad functions are described below:
STOP key: Press STOP to Stop the drive. The STOP key is
active whenever the remote keypad is operational.
RUN key: Press RUN to Start the drive. TB-1 must be closed to
TB-11. See the wiring diagram in Section 4
WARNING!
If the remote keypad display is totally blank or only the decimal points are lit,
or it is displaying a “JF” fault, the STOP key WILL NOT stop the drive. The
remote keypad must be operational in order for the STOP key to be active.
5. SETTINGUPTHESMDRIVE
To set up the SM drive to work with the Remote Keypad, the following
parameters must be programmed:
P11 TB-13B FUNCTION Set to REMOTE KEYPAD (13)
P12 TB-13E FUNCTION Set to REMOTE KEYPAD (21)
P14 CONTROL Set to REMOTE KEYPAD ONLY (02).
When this is done, and the Remote Keypad is connected, only the Remote
Keypad can start the drive and select direction. This results in some functions
of the drive being unavailable. These are explained below:
1. The Dynamic Braking option cannot be used because TB-13E is required
for the Remote Keypad.
2. Settings 05, 06, and 07 on TB-13A (Parameter 10) are disabled. These
settings are related to direction control. Only the Remote Keypad can be
used for direction commands.
Refer to the SM Installation and Operation Manual for more information.
NOTE: Once the drive is set up for Remote Keypad control, the buttons on
the front of the drive are disabled. If they are pressed, the drive display and
Remote Keypad display will show “SE”, indicating that the buttons are disabled.
STOP
RUN
7. REMOTE KEYPAD DISPLAY
The SM Remote Keypad has a three digit display like the SM drive.
The displays below are examples of the drive in RUN mode. On the left, the
drive is running at 43.6 Hz. On the right, the speed has been changed to 52.8
Hz (during speed command changes, the upper left decimal point turns on).
The displays below are examples of problems that will occur if the drive is not
properly programmed or if the keypad is not wired properly to the drive.
Make sure Parameters 11,
12, and 14 are properly
set.
Make sure the keypad is
properly wired to the
drive and the cable is
away from noise.
POSSIBLE CAUSES
RemoteKeypaddisplay
isblank,oronlythe
decimalpointsare
illuminated.
Parameter14-CONTROLissetto“01”
(TERMINAL STRIP ONLY)
Parameter11-TB-13Bisnotsetto“13”.
Parameter12-TB-13Eisnotsetto“21”.
TheRemoteKeypadisnotwiredcorrectlytothe
drive.
RemoteKeypadand/or
SM drive displays “JF” JFisaserialfault,whichindicatesacommuni-
cationproblem.Checkforproperwiringbetween
theremotekeypadandthedrive.
A“JF”faultwillalsooccurifanattemptismade
topowertheremotekeypadandanausiliary
relayfromTB-11.SeeNote2inSection4.
TheR/Fkeydoesnot
worktochangerotation
direction.
TousetheR/Fkeytochangerotationdirection,
theremotekeypadmustbeselectedasthe
controlsource,andParameter17(ROTATION)
mustbesetto“02”(FORWARDAND
REVERSE). RefertoSections4and5.
CONDITION / DISPLA
Y
Doc# SLRK06A

This manual suits for next models

1

Popular Keypad manuals by other brands

AJAX KeyPad quick start guide

AJAX

AJAX KeyPad quick start guide

Channel Vision A0125 instructions

Channel Vision

Channel Vision A0125 instructions

rako WCM-040 instruction manual

rako

rako WCM-040 instruction manual

NAPCO Gemini GEM-K2AS operating guide

NAPCO

NAPCO Gemini GEM-K2AS operating guide

AMX Metreau DAS-MET-6SRC Operation/reference guide

AMX

AMX Metreau DAS-MET-6SRC Operation/reference guide

SI 201576 installation instructions

SI

SI 201576 installation instructions

Bentel Security ALISON/S manual

Bentel Security

Bentel Security ALISON/S manual

Vicon V1411X-DVC Installation & operation manual

Vicon

Vicon V1411X-DVC Installation & operation manual

JAMO KP4.6 Installation & user guide

JAMO

JAMO KP4.6 Installation & user guide

Manaras Opera KEYLESS 042 Programming and installation instructions

Manaras Opera

Manaras Opera KEYLESS 042 Programming and installation instructions

Burg Wächter secuENTRY Entry 7711 operating instructions

Burg Wächter

Burg Wächter secuENTRY Entry 7711 operating instructions

WatchNet WAR-HAK-6HA quick start guide

WatchNet

WatchNet WAR-HAK-6HA quick start guide

Crow FW-KP Installation instructions & user manual

Crow

Crow FW-KP Installation instructions & user manual

Crestron Cameo INET-CBDEX Series Operations & installation guide

Crestron

Crestron Cameo INET-CBDEX Series Operations & installation guide

LEGRAND Vantage Arteor KSS14AR Series Installation

LEGRAND

LEGRAND Vantage Arteor KSS14AR Series Installation

Lincoln LFC 2000 manual

Lincoln

Lincoln LFC 2000 manual

DMP Electronics SC Series Installation and Programming

DMP Electronics

DMP Electronics SC Series Installation and Programming

Meccanica Fadini DGT 61 manual

Meccanica Fadini

Meccanica Fadini DGT 61 manual

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.