
Product characteristics
Front view Rear view
* Normally open versions : Red on 30 mA
Normally closed versions : Black on 30 mA
Features common to all versions :
1. Related operating voltage 230-250 V AC,
50/60 Hz frequency.
2. Double pole contacts with a minimum separation of 3mm
ensuring isolation of Live and Neutral supply.
3. Maximum current rating 13 A on single outlets
and a combined maximum of 16 A on twin outlets.
4. Conforms to BS 7288.
Features specific to normally open devices
(electrical latching) :
Tripping of the device will occur in the event of one or more of
the following circumstances : -
1. Detection of a residual current fault of a magnitude appropriate
to sensitivity of the RCD mechanism (30mA).
2. Depression of the test button.
3. Interruption of the Neutral supply.
4. Detection of pulsating DC fault currents.
5. Failure of the mains power supply for a period longer than
60 milliseconds. The tripping mechanism operates in the nor-
mal fashion before this current reaches 30mA.
Features specific to normally closed devices
(mechanical latching) :
Tripping of the device will occur in the event of one or more of
the following circumstances : -
1. Detection of a residual current fault of a magnitude
appropriate to sensitivity of the RCD mechanism (30 mA).
2. Depression of the test button.
4. Detection of pulsating DC fault currents.
Set(on) button
Test (off) button *
Red flag
Installation procedures
All flush mounting Legrand RCD safety sockets can be instal-
led in 35 mm depth backboxes.
Before commencing installation, ensure the main power
supply is safely disconnected at the consumer unit in order
to isolate the circuit. In the interests of safety, this device
should be installed by a qualified electrician according to
the latest I.E.E. Wiring Regulations. As a precautionary
measure, have the condition of the existing tails checked
if retro-fitting and rewire as necessary. The rating of the
fuse/MCB protection must not exceed 32 A, the normal ring
circuit rating.
Test procedures
With the device fixed to its wall box, verification of the safety
socket operation can commence.
After reconnecting the mains supply, press the transparent
“ON/SET” button which will result in the socket being switched
on. Confirmation of live status is achieved by the appearan-
ce of the red flag visible through the “ON/SET” button.
Pressing the “OFF/TEST” button* will cause the device to
trip and the red flag to disappear. If the flag remains red
after depression of the “TEST” button (and the mains supply
has been confirmed present), the unit must not be used as
this is
symptomatic of a fault in the device.
Under such circumstances, do not use the socket and
seek the advice of a qualified electrician as soon as
possible.
Assuming correct operation of the device, resetting is simply
a matter of pressing the red set button again. We recom-
mend that the device be tested (as above) prior to use or at
least once a month.
* Normally open versions : Red on 30 mA
Normally closed versions : Black on 30 mA
Important :
Disconnect this safety socket before wiring insulation tests
are carried out otherwise false readings will be obtained.
No attempt must be made to repair a safety socket suspec-
ted of being faulty. There are no user serviceable parts
within and evidence of tampering or other intervention will
invalidate the manufacturer’s guarantee.
Technical data summary
Nominal voltage : 230-250 AC, 50/60 Hz
Max. operating current : 16 A (combined total in
case of twin)
Rated trip current : 30 mA
Trip speed : < 200 milliseconds
at rated trip current
< 40 milliseconds
at 5 x rated trip current
Contacts : Double pole
(3 mm minimum gap)
Terminal capacity : 6 mm2
Short circuit withstand current : 1500 A
Conforms to BS 7288.
Trouble shooting
Safety socket
trips
Unplug
appliance
Safety socket
resets
Safety socket
won’t reset
Faulty appliance
or
lead connection
Repair or
replace as
necessary
Return
safety socket
to Legrand
Fault in
safety socket
Supply
fault
Seek assistance
of qualified
electrician
Normally open
versions only
Black
(neutral conductor)
Red
(live conduc
tor)
Green/ yellow (earth conductor)
2
2
3
3
4
4