Lehigh E-Flex EFRP User manual

E-Flex Relay Panel (EFRP) Installation Guide
Please Read before Installing
F586 Rev. 2 Lehigh Electric Products Co. 6265 Hamilton Blvd.., Allentown, Pa. 18106 Tel: 610-395-3386 Website: www.lehighdim.com
Control Panel Ratings
Control Power: 120-277VAC 50/60 Hz .60A (120V), .34A(277V)
Load Inputs: 120-277VAC 50/60Hz
Load Outputs: 120-277VAC 16A per output
0-10V Outputs: 80mA sink per zone (H2800, H2810, H2814, and H2815 only)
Operating environment: 32oF to 104oF (0oC to 40oC)
24V Supply Power: Limit 13UL (UL = 50mA) for external devices, use LPS-20UL external supply for additional
loading.
Model Numbers
E-FLEX-4-E (4-ckt, DMX, 0-10V)
E-FLEX-8-E (8-ckt, DMX,0-10V)
E-FLEX-4-D (4-ckt, DMX)
E-FLEX-8-D (8-ckt, DMX)
E-FLEX-4-E-TC (4-ckt, DMX, 0-10V, Timeclock)
E-FLEX-8-E-TC (8-ckt, DMX, 0-10V, Timeclock)
Step 1: Mounting the unit
For indoor use only on a vertical surface!
Remove the panel cover.
Remove the internal high voltage shield which is held in place by two screws on the
left side of the shield.
Mount the panel in an accessible location to allow for end use programming or relay
bypassing.
Install in accordance with all national and local electrical codes.
Mechanical Dimensions
All dimensions shown as inches
E-Flex 4 - 12 in. X 10.5 in.
E-Flex 4 - Keyhole centers 10 in. X 8.5 in.
E-Flex 8 - 12 in. X 16.5 in.
E-Flex 8 –Keyhole centers 10 in. X 14.5 in.
Step 4: 0-10V load wiring
Up to eight IEC SELV/NEC Class 2 isolated 0-10V outputs with 50mA sinking only capability are provided.
These outputs conform to IEC 60929.
Warning:
RISK OF DEATH OR ELECTRIC SHOCK! Before wiring or servicing the unit, make
sure upstream source of power is off via a circuit breaker.
If the high voltage shield is removed, the panel must be accessed by a certified technician following local
codes.
#20-12 AWG wires, strip length –¼ in., torque –3.5 lbs.
Connect only to NEC Class 2 circuits. Follow all national and local codes for separation
requirements.
Limit distance run for analog control wiring from controller to last driver. Limiting to a voltage
drop of .3V maximum will help ensure meeting IEC 60929 Annex E standard for minimum light
level at 1V.
E-Flex 4 Example Shown
Step 5: Input bank wiring
Four input banks are provided with a connection for an occupancy sensor, daylight sensor, NEC Class2/PELV
dry contact switch, and E-Flex CapT station. Refer to the instruction sheets provided with the devices.
Warning:
RISK OF DEATH OR ELECTRIC SHOCK! Before wiring or servicing the unit, make sure
upstream source of power is off via a circuit breaker.
If the high voltage shield is removed, the panel must be accessed by a certified technician following local
codes.
Input Bank Wiring:
#20-12 AWG wires, strip length –¼ in., torque –3.5 lbs.
CapT station –cable run limit 150 ft. maximum.
Multiple occupancy sensors controlling the same zones must be tied to the same input bank.
DO NOT CONNECT the 24V between two or more panels sharing the same control signals!
Step 6: Switch Configuration –Daylight and Occupancy Sensor Inputs
Two dip switches provide hardware configuration for the daylight and occupancy sensor inputs.
SW1 –Daylight Sensor Inputs
SW1 Position
Daylight Sensor
Active Low* (default)
Active High**
1
Day 1
ON
OFF
2
Day 2
ON
OFF
3
Day 3
ON
OFF
4
Day 4
ON
OFF
SW2 –Occupancy Sensor Inputs
SW2 Position
Occupancy Sensor
Active Low
Active High (default)
1
Occ 1
ON
OFF
2
Occ 2
ON
OFF
3
Occ 3
ON
OFF
4
Occ 4
ON
OFF
*0V reports max light, **10V reports max light.
Step 2: Control power wiring
The E-flex panel operates at 120-277VAC. Use following instructions to wire line voltage to the unit.
Warning:
RISK OF DEATH OR ELECTRIC SHOCK! Before installing input power to the
controller, make sure upstream source of power is off via a circuit breaker.
1. Use 14 to 12 AWG conductors (depending on breaker rating) to feed the control power wiring. The E-
flex controller draws less than .60A at 120V and
less than .34A at 277V.
2. The unit power supply has a black (Hot) and white
(Neutral) wire. Wire nut the Hot and Neutral of the
power feed to these wires as shown.
3. A stud is provided to land the ground wire.
4. Note: Alternately the unit control power can be
wired from the zone 1 feed rather than a separate
feed. This is especially true if UL924 is applied as
the unit must be powered by the
normal/emergency feed with zone 1 as the first
emergency zone.
Step 3: Line Voltage load wiring
The E-flex panel operates at 120-277VAC. Use following instructions to wire line voltage loads to the unit.
Warning
:
RISK OF DEATH OR ELECTRIC SHOCK! Before installing power to the power feeds,
make sure upstream source of power is off via a circuit breaker.
E-Flex is a feed-through device; this means that each switched output requires Line and Load wires.
Feed-Through Example –4-circuits, Individual Feeds
Load Wires: Two (2) 14 AWG to 12 AWG. Strip length –3/8 in., torque –7 in-lbs.
Neutral and Ground Wires: Wire nut each from feed to load.
Feed-Through Example –4-circuits, Normal/Emergency, 120V and 277V
Feeds
Voltage Barriers: Separate Normal/Emergency, 120V, and 277V. The voltage barrier is an accessory,
sold separately. Order Lehigh part number A1678.

E-Flex Relay Panel (EFRP) Installation Guide
Please Read before Installing
F586 Rev. 2 Lehigh Electric Products Co. 6265 Hamilton Blvd.., Allentown, Pa. 18106 Tel: 610-395-3386 Website: www.lehighdim.com
Scan for EFRP configuration programming videos.
Step 7: Timeclock/Demand response, Emergency Contact closure Inputs
Warning:
RISK OF DEATH OR ELECTRIC SHOCK! Before wiring or servicing the unit, make sure
upstream source of power is off via a circuit breaker.
If the high voltage shield is removed, the panel must be accessed by a certified technician following local
codes.
Wiring for both inputs is NEC Class 2/PELV. Follow all national and local electrical codes. The inputs must be
used with a dry contact closure device.
#24-12 AWG wires, strip length –¼ in., torque –3.5 lbs
If the Emergency input is open, the E-Flex panel will enter Emergency mode. All outputs that are assigned to
this input will turn on, 0-10V outputs will be driven to 100% and local control from sensors or other inputs
will be disabled.
Emergency Enable/Disable (EMERG-J12)
Jumper J12 (EMERG) is used to enable or disable the emergency input. To enable, position the jumper across
J12 pins 1-2. To disable (default) position the jumper across J12 pins 2-3.
DMX Port Wiring
E-Flex provides a DMX512 (ANSI E1.11-2008) input and thru ports with RDM (ANSI E1.20-2010) support.
Recommend Liberty 24-2P-P485-WHT, Belden 9841 or 9842.
Warning:
RISK OF DEATH OR ELECTRIC SHOCK! Before wiring or servicing the unit, make sure
upstream source of power is off via a circuit breaker.
If the high voltage shield is removed, the panel must be accessed by a certified technician following local
codes.
#24-22 AWG wires, strip length –¼ in., torque –1.7 lbs.
Total distance should not exceed 1500 ft. (450m).
SW6 –DMX Termination
Default OFF, set to ON for each end of line device. Should only be two end-of-line devices in a system.
DMX512 Start Address, Assign Zones
The start address and zone assignment are set using the on-board user interface or E-Flex Flextool
Configurator software. See the E-Flex user manual for more information.
FlexNet Link Wiring
FlexNet link interconnects up to 100 devices on a single network. Each device is programmed with a unique
ID (1-100). Recommend Alpha 6455 or equivalent. If necessary a shielded data cable along with discrete
power (18 to 12 AWG) can be used for powered devices.
Warning:
RISK OF DEATH OR ELECTRIC SHOCK! Before wiring or servicing the unit, make sure
upstream source of power is off via a circuit breaker.
If the high voltage shield is removed, the panel must be accessed by a certified technician following local
codes.
FlexNet Wiring
#24-22 AWG (data), 24-14 AWG (power) wires, strip length –¼ in., torque –1.7 lbs.
Cable distance is limited by data wire size and number of devices on a link segment. Using 22
AWG, the total distance is 1000 ft. (300m). Using 24 AWG data the total distance is 650 ft. with
100 devices. Number of powered devices will also limit length. Request wiring specification from
factory for more detailed information.
FlexNet Topology and Device Termination
The diagram below shows daisy-chained link segment wiring and end of line termination between EFRPs. NO
T-TAPS or STAR connections ALLOWED.
Device ID
The device ID is set using the on-board user interface or E-Flex Flextool Configurator software. See the E-Flex
user manual for more information.
Impress Link Wiring
E-Flex can be configured to operate with Solitaire Impress remote wall stations to recall presets and provide
partitioned room control when each room has its own E-Flex Panel. The DMX input port is used for Impress
Link mode operation.
Recommend Belden 9729 or 9842 data cable with two twisted pairs.
Warning:
RISK OF DEATH OR ELECTRIC SHOCK! Before wiring or servicing the unit, make sure
upstream source of power is off via a circuit breaker.
If the high voltage shield is removed, the panel must be accessed by a certified technician following local
codes.
FlexNet Wiring
#24-22 AWG wires, strip length –¼ in., torque –1.7 lbs.
Total distance should not exceed 1500 ft. between remote stations.
Wiring Diagram as End of Line
Wiring Diagram as Not End of Line
Configure Impress Link Mode, Assign Area and Zones
Impress Link mode, area, and zone assignment are set using the on-board user interface or E-Flex Flextool
Configurator software. Set area entry for (1-8) to enable this mode. See the E-Flex user manual for more
information.
EFRP Power Up Checklist
Warning:
RISK OF DEATH OR ELECTRIC SHOCK! Before powering up the unit for verification
checklist, make sure the high voltage shield in re-installed. Otherwise the panel
must be accessed by a certified technician.
This assumes the front cover is off the unit and the high voltage shield has been re-installed.
Verify the dip switch settings for occupancy and daylight sensors are correct.
Verify that DMX and FlexNet port termination is enabled or disabled as required for end of line
termination.
Verify that the emergency enable jumper is in the correct position if emergency contact closure
input is being used.
Turn on power from the circuit breaker(s) feeding the panel.
Ensure the power LED on the main controller board is lit. It is just to the left of the first zone relay.
FlexNet device ID setting –Setup per the E-Flex user manual and record on the ID label on the
front cover.
EFRP Configuration Chart
Input
Zn1
Zn2
Zn3
Zn4
Zn5
Zn6
Zn7
Zn8
Pol
Mode
Preset(s)
Area
occ1
/
N/A
occ2
/
occ3
/
occ4
/
day1
N/A
day2
day3
day4
cci1
/
cci2
/
cci3
/
cci4
/
cap1
N/A
cap2
cap3
cap4
Emerg
N/A
N/A
TC/DmdResp
Dmd Rsp %
N/A
DMX
N/A
Impress Link
Load Type
N/A
N/A
High Trim
Low Trim
This manual suits for next models
6
Other Lehigh Relay manuals