Leviton D4200 User manual

WARNINGS AND CAUTIONS:
• TOAVOIDFIRE,SHOCKORDEATH:TURNOFFPOWERATMAINCIRCUITBREAKERORFUSEANDTESTTHATTHEPOWERISOFFBEFOREWIRING,
SERVICINGTHEDIMMERORCHANGINGBULBS!
• DONOTCONNECTLINEVOLTAGEWIRESTOLOWVOLTAGETERMINALS.
• TOBEINSTALLEDAND/ORUSEDINACCORDANCEWITHELECTRICALCODESANDREGULATIONS.
• IFYOUARENOTSUREABOUTANYPARTOFTHESEINSTRUCTIONS,CONSULTANELECTRICIAN.
• FORINDOORUSEONLY.
• FORTHEBESTLAMPLIFE,LAMPMANUFACTURERSRECOMMENDTHEIRFLUORESCENTLAMPSSHOULDBEOPERATEDATFULLBRIGHTNESSFORAMINIMUMOF100HOURS
BEFOREDIMMINGISPERMITTED.FORBESTRESULTS,LAMPBRANDSANDTYPESSHOULDNOTBEINTERMIXEDONACIRCUIT.
INTRODUCTION:
ForbestresultsusingtheDimensions4200ArchitecturalLightingController,Followtheserecommendations:
1. Planthesystembeforebeginningtheinstallation
2. Terminatethewiring
3. Testthewiring
4. Connectdimmercabinets
5. PoweruptheStations
6. ProgrameachStation
AssignuniquenetworkIDnumberstostations.
Connectonemasterstation,andthenoneremotecontrolstationatatime.
VerifythattherstD4200canproperlycontrolthedimmersassignedtoit.
Checktheproperoperationofeachstationasitisinstalledwhenmultiplestationsareinvolved.
7. InstallallStations
NOTE:Ifthelightingcontrolfailsorbecomessporadic,rstcheckthewiringornetworkID.
TERMINATINGTHEWIRING:
Luma-Net®III
ControlStationscanbelocatedupto2000ft.fromthedimmingcabinet.Luma-Net®iswiredDaisyChained,stationtostation.Forapplicationswhererunsbecometoolongcontact
TechnicalSupportat1-800-959-6004.Thecableshouldnotpassnearanysourceofelectricalnoisesuchasuorescentcircuitsormotorwiring.AvoidcloseproximitytoanyACwiring.All
control/powerwiringmustbeinconduit.
Luma-Net®WireRecommendations
1.
UseRS485compatiblecableforcommunications.Itisrecommendedthatacablewith2TwistedPair,24AWG(min.),strandedconductorsbeused.Thesparepairisforfutureuses.
2. Capacitanceofwireshallbe15pF/ft.orless.
3. NormalImpedanceofwireshallbebetween100-120ohms.
4. Asecondpairofstrandedwireisrequiredforthepower.
5. Drain/Shieldstobetiedtogether,insulatedandgroundedatonepointonly.
WestronglyrecommendtheuseofeitherBelden9829,Belden9729orBelden1502R/1502PfortheLuma-Net®wireruns.
IfaremoteDCpowersupplyisusedandyouhavemultipleLuma-Net®runs,allDCcommonwiresmustbejoinedatthepowersupply.
Atthelastcontrolstationordimmercabinetonbothendsofrun,asmalljumperwiremustberunfromtheterminallabeled"Rem-"totheterminalmarked"Term"onthatlaststation.
Thisjumperwireproperlyterminatesthedigitalcommunicationslinesatbothendsoftheline.
WirethePhoenixConnector
1. Connectleadsperwiringdiagram(seeLuma-Net®WireConnections).
2. Twiststrandsofeachleadtightly(makingsurethattherearenostraystrands)andpushrmlyintoappropriateplugconnectorlocation.
3. Tightenthescrewsontheplugconnector-makingsurethatnobareconductorisshowing.
4. TietheDrain/Shieldwirestogetherandinsulateusingasmallpieceofheatshrinktubing.
5. Installterminationjumpersasrequired.RememberaterminationjumperisrequiredatthetwoendsoftheLuma-Net®run.
D4200A/VInterface
+9-24Vdc,50mA@12V,25mA@24V
DI-000-D42AV-00BAR2691
Drain/Shield - Insulated & tied together
(Ground at one point only - probably an end)
2 #12AWG
2 #12AWG
Phoenix Connector
Black (Common)
Red (+V)
Up to 1 #12AWG
Luma-Net
®
Wire Connections
REM+
REM -
COM
TERM
N/C
+V
1
2
3
4
5
6
56
1
234
Termination
Jumper
Phoenix Connector
Luma-Net
®
Termination Jumper Locations
REM+
REM -
COM
TERM
N/C
+V
1
2
3
4
5
6
56
1
234
A-2000
DIMMER RACK
MASTER CONTROL STATION
MASTER CONTROL STATION
LUMA-NET HUB
BUTTON STATION
BUTTON
STATION
Figure 3 - Allowed star topology (with Luma-Net Hub only)
A-2000
DIMMER RACK
MASTER CONTROL STATION
MASTER CONTROL STATION
BUTTON
STATION
BUTTON STATION
Figure 2 - Dis-allowed star topology (DO NOT USE)
A-2000
DIMMER RACK
MASTER CONTROL STATION
MASTER CONTROL STATION
BUTTON
STATION
BUTTON
STATION
Figure 1 - Typical Daisy Chain wiring scenario

DI-000-D42AV-00BAR2691©2011LevitonMfg.Co.,Inc. ForTechnicalAssistanceCall:1-800-959-6004oremail:LMST[email protected](U.S.A.Only)
LimitedWarranty
LEVITONLIGHTINGANDENERGYSOLUTIONSADIVISIONofLevitonManufacturingCoInc.warrantsitsDimmerSystemsandControlstobefreeofmaterialandworkmanshipdefectsforaperiodoftwoyearsafter
systemacceptanceor26monthsaftershipment,whichevercomesrst.ThisWarrantyislimitedtorepairorreplacementofdefectiveequipmentreturnedFreightPre-PaidtoLevitonLightingControlDivisionat20497
SWTetonAve.,Tualatin,Oregon97062,USA.Usershallcall1-800-959-6004andrequestareturnauthorizationnumbertomarkontheoutsideofthereturningcarton,toassurethatthereturnedmaterialwillbeproperly
receivedatLeviton.AllequipmentshippedbacktoLevitonmustbecarefullyandproperlypackedtoavoidshippingdamage.Replacementsorrepairedequipmentwillbereturnedtosenderfreightprepaid,F.O.B.factory.
Levitonisnotresponsibleforremovingorreplacingequipmentonthejobsite,andwillnothonorchargesforsuchwork.Levitonwillnotberesponsibleforanylossofusetimeorsubsequentdamagesshouldanyof
theequipmentfailduringthewarrantyperiod,butagreesonlytorepairorreplacedefectiveequipmentreturnedtoitsplantinTualatin,Oregon.ThisWarrantyisvoidonanyproductthathasbeenimproperlyinstalled,
overloaded,shortcircuited,abused,oralteredinanymanner.NeitherthesellernorLevitonshallbeliableforanyinjury,lossordamage,directorconsequentialarisingoutoftheuseoforinabilitytousetheequipment.This
Warrantydoesnotcoverlamps,ballasts,andotherequipmentwhichissuppliedorwarrantieddirectlytotheuserbytheirmanufacturer.LevitonmakesnowarrantyastotheFitnessforPurposeorotherimpliedWarranties.
TESTINGTHEWIRING:
Toassureproblem-freestart-up,itisimportanttocheckthesystemwiring,priortohookingupanycontrolstations,forproperconnections,shortsandopens.
Thefollowingprocedureisrecommended:
Step1:Testthefollowingwirepairsforshortsateachstationlocation,usinganohmmeterorothercontinuitytester.
1-2Open
2-3Open
3-4Open
Step2:Repairanyshortcircuitsbeforecontinuing.
Step3:InstallwirejumperstothePhoenixConnector(notsupplied)oneitherendofthecablerunbetweenpins3-4.
Step4:Retesteachofthefollowingwirepairsateachconnector:
1-2Open
2-3Open
3-4Short
Step5:Makeanynecessaryrepairsandremovewirejumpersbeforecontinuing.
STATIONADDRESSING:
AddresstheA/Vinterfacebetween1and127.IfastationaddressissettoZeroitwillnotparticipateonthenetwork.
TheswitchissettothebinaryrepresentationoftheIDnumber.Thebinary1’scolumnisleft-most(leverlabeled"1").
Theswitchleversarenumbered1-8,theserepresentthefollowing:
Lever=Value
1=1 2=2
3=4 4=8
5=16 6=32
7=64 8=SelectscodeV1.x(ON)orV2.x(OFF)
Addthevalueofeachleverinthe"ON"positiontodeterminetheIDnumber(decimalform).
Forexample:
Tosettheaddressto39,thefollowingswitchesneedtobeinthe"ON"position:1,2,3,6=1+2+4+32=39
INSTALLATION:
Securelymounttheentrystationusingthescrewsprovided.
Ifyouareusingascrewlesssnaponplate,removethecentertabsofthestrapasshowninthegure.
PROGRAMMING/OPERATION:
TheD42AVrespondstoASCIIcontrolcommandswhichcanbeissuesthroughacommonRS-232terminalconnection.
ForconnectingtotheA/Vinterface,usethefollowingparameters
• BaudRate(BPS):9600
• DataBits:8
• StopBits:1
• Parity:None
• FlowControl:None
• Fortestingpurposes,aterminalprogramlikeHyperTerminal,TerraTerm,orotherserialterminalcommunicationprogramcanbe
used.
ASCIICommands
Youcaninitiatethefollowingcommands(leadingzerosarenotrequired):
Note:LegacycommandrequiredforusewheninterfacingwitholderD4200networkcontrolstationsorwhenneedingtorecall
MAX/OFFcommands.NewerversionsD4200supportbothD4200andD8000buttonpresscommands.D8000buttonpress
commandscanbeusedwithD4200,D8000,andtheCombineClosures(KCLCM)interface.
D4200Preset/Scenebutton
Pxx@yyy=sendD4200scenebutton.
Pscene@netide.g.P18@53
xx=1to2digitscenenumber1-16,17=Max,18=Off.
D8000buttonpress
K_xx@_yyy=sendD8000buttonpress.
K=button@netid
xx=2digitswitchnumber01-15
e.g.K9@101
Dimmer@Level
Ddddd@lll=senddimmerlevel.
Ddimmer@levele.g.D81@128
dddd=dimmernumber,1-2048.
lll=3digitlevelnumber,0-255.
SetDimmerFaderate
Fxxx=setfaderatefor'D'.
Ffaderatee.g.F5
xxx=faderate,0-60seconds,above60isminutes.
0-59=seconds
60-239=1to180minutes
253=PhotocellCaptureorrecord(a-2000)
254=PhotcellOn(a-2000)
255=StopfadingnoworStopFade
Followthesimpleformulaof:Totalminutes+59=entry
Eample:For65minutesenter124(65+59=124)
DimmertoMax
Rxxxx=sendraisedimmer1-2048toMax.e.g.R22
DimmertoOff
Lxxxx=sendlowerdimmer1-2048toOff.e.g.L22
DimmerStop
Sxxxx=sendstoptodimmer1-2048.e.g.S22
O
F
F
1 + 2 + 4 + 8 + 16 + 32 + 64 + 128
Net ID
(Line indicates the silkscreen under the dipswitch)
1 2 3 4 5 6 7 8
O N
Std. 3-1/2" back box
Use Steel City
#GW135G or
Raco 695. by E.C.
DimmerReadback
Vxxxx=sendreadbackrequesttodimmer1-2048.V22Returns3digitrawvalue,or
'NA'(Dimmernumbernotapplicable).
TheA/VInterfacealsohassometoolsfordebuggingautomationsequences.
Theyare:
M_aa@_lll=setoptions.
Maddress@level (e.g.M1@1)
aa=2digitaddress,1or2.
lll=3digitlevelnumber,0-255.
ifaa=01,then:
100addsdebugparsingechoing.(e.g.M1@100)
101addsaboveandparsingquotesaroundparameters.(e.g.M1@101)
102addsaboveanddisplayofparsednumbers.(e.g.M01@102)
ifaa=02,then:
1addsuserprompt.(e.g.M2@1)
2addsuserpromptanderrormessages.(e.g.M2@2)
B=DisplaySoftwareBuildNumber.
Z=ToggleDebugNetworkModeStatusOutput.
NOTE:YoumustpresstheReturn/Enterkeytoexecutethedesiredcommand.