Leviton omnilte User manual

Installation Manual
Control & Security System
Includes the SIA CP-01 Control Panel Standard
Features for False Alarm Reduction
WEB VERSION

WEB VERSION

WARNINGS AND CAUTIONS
• Read and understand all instructions. Follow all warnings and instructions marked on the product.
• Do not use this product near water - e.g., near a tub, wash basin, kitchen sink or laundry tub, in a wet basement,
or near a swimming pool.
• Never push objects of any kind into this product through openings, as they may touch dangerous voltages.
• Never install communications wiring or components during a lightning storm.
•
use in wet locations.
• Never touch uninsulated wires or terminals unless the wiring has been disconnected at the network interface.
• Use caution when installing or modifying communications wiring or components.
• SAVE THESE INSTRUCTIONS.
WEB VERSION

CONTENTS
INTRODUCTION ..............................................................................................................................1
PLANNING ......................................................................................................................................................................1
INSTALLATION ...............................................................................................................................2
CONTROLLER HOOKUP ...............................................................................................................................................2
ABOUT SECURITY ZONES............................................................................................................................................4
BURGLAR ZONE HOOKUPS ..................................................................................................................................4
ABOUT FIRE ZONES......................................................................................................................................................5
TWO-WIRE SMOKE DETECTORS..........................................................................................................................6
FOUR-WIRE SMOKE DETECTORS ........................................................................................................................6
TELEPHONE CONNECTIONS .......................................................................................................................................9
DIGITAL SUBSCRIBER LINE (DSL) CONNECTIONS ............................................................................................9
LCD CONSOLE HOOKUP ............................................................................................................................................11
CONSOLE SETUP ........................................................................................................................................................12
CONSOLE ADDRESS............................................................................................................................................12
SOUNDER..............................................................................................................................................................12
KEY CLICK .............................................................................................................................................................12
KEY BACKLIGHT ...................................................................................................................................................12
VIEWING ADJUSTMENT .......................................................................................................................................12
SOUNDER OUTPUTS...................................................................................................................................................14
INTERIOR SOUNDER HOOKUP ...........................................................................................................................14
EXTERIOR SOUNDER HOOKUP..........................................................................................................................14
CONTROLLER OUTPUTS............................................................................................................................................16
RESET OUTPUTS .........................................................................................................................................................16
OUTPUT APPLICATIONS ............................................................................................................................................16
GENERAL PURPOSE SWITCHING APPLICATIONS ...........................................................................................16
SOUNDER TRIGGERING ......................................................................................................................................16
COMMUNICATOR OUTPUTS ...............................................................................................................................17
"ARMED" AND "OK TO ARM" ................................................................................................................................17
SWITCHED OUTPUT.............................................................................................................................................17
OMNISTAT COMMUNICATING THERMOSTATS .................................................................................................17
REMOTE ARM/DISARM SWITCH ................................................................................................................................17
OMNISTAT THERMOSTATS ........................................................................................................................................19
PROGRAMMABLE ENERGY SAVER MODULES .......................................................................................................20
TEMPERATURE, OUTDOOR TEMPERATURE, AND HUMIDITY...............................................................................21
BUILT-IN SERIAL PORTS ............................................................................................................................................23
BUILT-IN ETHERNET PORT ........................................................................................................................................24
CONTROLLER IP ADDRESS, PORT NUMBER, AND ENCRYPTION KEY .........................................................24
CONTROLLER IP ADDRESS ................................................................................................................................25
CONTROLLER PORT NUMBER............................................................................................................................25
ENCRYPTION KEY ................................................................................................................................................25
ETHERNET CONNECTIONS .................................................................................................................................25
CONNECTING TO NETWORK VIA PC ACCESS..................................................................................................27
SYSTEM POWER UP PROCEDURE ............................................................................................29
CONSOLE CHECK OUT...............................................................................................................................................29
TELEPHONE CHECK OUT...........................................................................................................................................29
BURGLAR ZONE CHECK OUT....................................................................................................................................30
FIRE ZONE CHECK OUT .............................................................................................................................................30
CUSTOMER CHECKOUT .............................................................................................................................................30
IN CASE OF TROUBLE ................................................................................................................................................31
CONSOLES ............................................................................................................................................................31
CONTROLLER .......................................................................................................................................................31
WEB VERSION

DIGITAL COMMUNICATOR ......................................................................................................... 33
DESCRIPTION OF CONTACT ID................................................................................................................................. 33
DESCRIPTION OF 4/2 FORMAT.................................................................................................................................. 34
3/1 FORMAT ................................................................................................................................................................. 34
OPENING AND CLOSING REPORTS ......................................................................................................................... 34
INSTALLER SETUP...................................................................................................................... 35
SETUP CONTROL........................................................................................................................................................ 35
X-10 HOUSE CODE............................................................................................................................................... 35
UPB NETWORK ID ................................................................................................................................................ 35
X-10 3-PHASE ....................................................................................................................................................... 36
UPB Transmit Count .............................................................................................................................................. 36
OUTPUT TYPES.................................................................................................................................................... 37
Z-WAVE NODE ID ................................................................................................................................................. 38
SETUP ZONES ............................................................................................................................................................. 38
WIRELESS RECEIVER ......................................................................................................................................... 38
ZONE RESISTORS................................................................................................................................................ 38
ZONE RESPONSE TIME....................................................................................................................................... 39
ZONE TYPES......................................................................................................................................................... 39
LATCHING ZONE TYPES ..................................................................................................................................... 40
DESCRIPTION OF ZONE TYPES ......................................................................................................................... 40
SETUP DIGITAL COMMUNICATOR............................................................................................................................ 43
FIRST PHONE NUMBER, FIRST ACCOUNT NUMBER....................................................................................... 43
COMMUNICATOR TYPE....................................................................................................................................... 43
TWO-WAY AUDIO ................................................................................................................................................. 44
REPORT OPEN/CLOSE ........................................................................................................................................ 44
REPORT BYPASS / RESTORE............................................................................................................................. 44
AC Fail Report Time............................................................................................................................................... 44
AUTOMATIC TEST TIME ...................................................................................................................................... 44
ALARM CODES (4/2 and 3/1 Formats).................................................................................................................. 45
SETUP TEMPERATURES............................................................................................................................................ 45
TEMPERATURE DISPLAY .................................................................................................................................... 45
THERMOSTAT TYPE ............................................................................................................................................ 45
Z-WAVE THERMOSTAT NODE ID........................................................................................................................ 46
SETUP MISCELLANEOUS .......................................................................................................................................... 46
INSTALLER CODE ................................................................................................................................................ 46
ENABLE PC ACCESS ........................................................................................................................................... 46
PC ACCESS CODE ............................................................................................................................................... 47
CALL BACK PHONE NUMBER ............................................................................................................................. 47
OUTSIDE SIREN DELAY....................................................................................................................................... 47
DIAL OUT DELAY .................................................................................................................................................. 47
ALARM RESET TIME ............................................................................................................................................ 47
ARMING CONFIRMATION .................................................................................................................................... 48
FIRE ALARM VERIFICATION................................................................................................................................ 48
SUPERVISE INT SNDR......................................................................................................................................... 48
SUPERVISE EXT SNDR........................................................................................................................................ 49
ENABLE EMERGENCY KEYS .............................................................................................................................. 49
TIME DISPLAY....................................................................................................................................................... 49
DATE DISPLAY...................................................................................................................................................... 49
AC POWER FREQUENCY .................................................................................................................................... 49
DEAD LINE DETECT ............................................................................................................................................. 49
OFF HOOK DETECT ............................................................................................................................................. 49
PICKUP AFTER HANGUP..................................................................................................................................... 50
CLOCK ADJUSTMENT.......................................................................................................................................... 50
MODEL AND SOFTWARE VERSION ................................................................................................................... 50
RESET SYSTEM EEPROM ................................................................................................................................... 50
RESET SYSTEM RAM........................................................................................................................................... 50
ETHERNET MAC ADDRESS................................................................................................................................. 50
WEB VERSION

SETUP EXPANSION.....................................................................................................................................................51
SERIAL ADDRESS.................................................................................................................................................51
SERIAL 1 RATE .....................................................................................................................................................51
SERIAL 1 FUNCTION ............................................................................................................................................51
SERIAL 2 – SERIAL 5 RATE..................................................................................................................................51
SERIAL 2 – SERIAL 5 FUNCTION.........................................................................................................................51
LEVITON Access Control .......................................................................................................................................52
Enrolling Access Control Readers ..........................................................................................................................52
Deleting Access Control Readers...........................................................................................................................52
Unlock Time............................................................................................................................................................53
Exit Time .................................................................................................................................................................53
Lock Type ...............................................................................................................................................................54
Reader Arm/Disarm ................................................................................................................................................54
SETUP ZONE OPTIONS...............................................................................................................................................55
SWINGER SHUTDOWN NUMBER ........................................................................................................................55
CROSS ZONE WINDOW .......................................................................................................................................55
ZONE 1 OPTIONS – ZONE 32 OPTIONS .............................................................................................................55
SIA CP-01 COMPLIANCE .............................................................................................................56
Minimum Equipment Requirements for a CP-01 Compliant Installation:...............................................................56
Omni LTe SPECIFICATIONS........................................................................................................57
UNDERWRITER'S LABORATORIES (UL) INSTALLATION REQUIREMENTS ..........................58
24-HOUR STANDBY BATTERY CAPACITY ................................................................................59
SMOKE DETECTOR INSTALLATION GUIDELINES ...................................................................60
APPENDIX A – CONTACT ID REPORTING FORMAT.................................................................61
APPENDIX B - DIGITAL COMMUNICATOR CODE SHEET ........................................................62
FIGURES
FIGURE 1 - CONTROLLER HOOKUP ............................................................................................................................3
FIGURE 2 - OVERALL CONNECTIONS DIAGRAM .......................................................................................................5
FIGURE 3 - TWO-WIRE FIRE ZONE CONNECTIONS ..................................................................................................7
FIGURE 4 - FOUR-WIRE FIRE ZONE CONNECTIONS.................................................................................................8
FIGURE 5 - RJ31X JACK CONNECTIONS...................................................................................................................10
FIGURE 6 - RJ31X JACK CONNECTIONS...................................................................................................................11
FIGURE 7 - CONSOLE CONNECTIONS ......................................................................................................................13
FIGURE 8 - SOUNDER CONNECTIONS......................................................................................................................15
FIGURE 9 - RESETTING CONTROLLER OUTPUTS ...................................................................................................16
FIGURE 10 - REMOTE KEYSWITCH CONNECTIONS ................................................................................................18
FIGURE 11 – OMNISTAT2 THERMOSTAT CONNECTIONS ......................................................................................19
FIGURE 12 - TEMPERATURE / HUMIDITY SENSOR CONNECTIONS......................................................................21
FIGURE 13 - PESM CONNECTIONS ...........................................................................................................................22
FIGURE 14 - RS-232 CONNECTIONS .........................................................................................................................23
FIGURE 15 - RS-485 CONNECTIONS .........................................................................................................................24
FIGURE 16 - LOCAL NETWORK ..................................................................................................................................27
FIGURE 17 - LOCAL / WIDE AREA NETWORK...........................................................................................................28
FIGURE 18 - 24-HOUR STANDBY CONNECTIONS ....................................................................................................59
WEB VERSION

Page 1
INTRODUCTION
This installation guide is intended as an aid to installing the Omni LTe Control & Security System. The installer should
also have thoroughly reviewed and understood the Omni LTe Owner's Manual, which has important information
regarding final setup of the system. This manual assumes that the installer has a basic understanding of installing a
security system.
This guide applies to the 20A00-70, -72, and -73 versions of the Omni LTe controller. Refer to the Underwriters
Laboratories Installation Requirements section for details in the application of each. Failure to install the Omni LTe
and its accessories in accordance with the UL Requirements in this manual and in the Owner's Manual is a violation
of the Listing Mark.
PLANNING
Before you start, your system should be planned as follows:
1. Zones:
•Decide where each contact or detector will be located
•Decide which zone it will occupy
•Decide zone type for each zone
•With the customer, decide what text and voice descriptors will be used. Consult table of voice descriptors, so
that you can choose similar words for the text to avoid customer confusion.
•See SMOKE DETECTOR INSTALLATION GUIDELINES to plan locations for smoke detectors
2. Consoles:
•Consult the customer on the console location. The console should be easily accessible.
3. Interior Sounder and Outside Siren:
•Locate both where they cannot be tampered with.
4. Lighting and Appliance Switches and Modules.
5. Plan for thermostats, energy saver modules, or other options.
6. Give consideration to where the controller will go. Remember that it needs a duplex receptacle not controlled by
a switch, preferably on its own circuit, within 5 feet of the controller.
WEB VERSION

Page 2
INSTALLATION
Go over your plan with your customer.
1. Install the entire system. Refer to sections in this manual to see how to install various components.
2. Follow the Power-Up and Checkout procedures.
3. Explain the basics to the customer. Deliver all manuals and documentation.
4. Follow up with your customer to keep them satisfied.
CONTROLLER HOOKUP
1. When choosing a place to mount the controller, consider the following:
a. A duplex outlet, preferably on its own circuit, is required to be within 5 feet of the controller for the power
transformer and the UPB PIM or X-10 Interface Module (if used).
b. The controller should be protected from weather, temperature extremes, and burglars.
2. GROUND THE CONTROLLER "EARTH GND" TERMINAL TO A COLD WATER PIPE OR TO A 4-FOOT
GROUND ROD TO PRESERVE ITS BUILT-IN TRANSIENT PROTECTION. USE 14 GAUGE WIRE.
TRANSIENT PROTECTION WILL NOT WORK IF THE CONTROLLER IS NOT PROPERLY GROUNDED.
3. Connect the 24VAC power transformer to the 24VAC INPUT terminals.
4. Connect the BLACK battery wire to the minus (-) terminal on the battery. DO NOT connect the red wire at this
time. DO NOT reverse the connections; the battery fuse will blow. Note that the unit will NOT START on the
battery alone.
5. Connect the Powerline Interface Module (if used) to the Omni LTe controller:
a) UPB PIM (P/N: 36A00-1): Plug one end of the 6-conductor modular cable into the connector marked “J3”
(SERIAL 3) on the Omni LTe controller and plug the other end into the modular connector on the PIM.
b) X-10 Interface Module (P/N: TW523): Plug one end of the 4-conductor modular cable into the connector
marked “J7” (X-10) on the Omni LTe controller and plug the other end into the modular connector on the X-10
Interface Module.
6. Refer to FIGURE 1 (CONTROLLER HOOKUP) for this configuration.
WEB VERSION

Page 3
YUASA NP7-12
OR EQUIVALENT
BLACK WIRE TO -
RED WIRE TO +
12V 7AH
BATTERY
ELECTRIC CODE, ANSI/NFPA 70.
ACCORDANCE WITH THE NATIONAL
GOUNDING METHOD MUST BE IN
OR GROUND ROD
COLD WATER PIPE
14 GA. WIRE
OR EQUIVALENT
MODEL RT-2440SL
REVERE
24 VAC 40 VA
POWER TRANSFORMER
WIRING IN THE ENCLOSURE
ALL OTHER POWER LIMITED/CLASS II
MUST BE SEPERATED FROM
LIMITED. THE BATTERY LEADS
THE BATTERY IS NON-POWER
BY AT LEAST 1/4"
SPACING
1/4"
6 CONDUCTOR
Powerline Interface Module
Status
<Program
UPB™
FIGURE 1 - CONTROLLER HOOKUP
WEB VERSION

Page 4
ABOUT SECURITY ZONES
Each of the 32 security zone (16 wired and/or 16 wireless) on an Omni LTe system may be configured as a burglary
zone, a fire zone, a temperature zone, or an auxiliary input. Zones 1-4, however, are the only inputs that can be used
with 2-wire smoke detectors. Zones 9-16 are the only inputs that can be configured as a PESM.
An external 1000-ohm end-of-line zone resistor is required for all zones unless the Setup item ZONE RESISTERS is
set to "No". If the Setup item ZONE RESISTORS is disabled, all zones other than Supervised Fire and Gas, will not
use an end-of-line resistor. In this configuration, all zone switches (other than Supervised Fire and Gas) must be
normally closed (open for alarm). If any zone requires a normally open (closed for alarm) switch (other than
Supervised Fire and Gas), the Setup item ZONE RESISTORS must be set to "Yes" and all zones will require and
external 1000-ohm end-of-line resistor.
The zone type for each zone is selected through the INSTALLER SETUP menu or by using the PC ACCESS
software.
The system supports a maximum zone resistance, excluding the end-of-line resistor, of 150 ohms. The default setting
for ZONE RESISTORS is "Yes". The default settings for all zone inputs on an Omni LTe controller are configured as
Auxiliary inputs.
Omni LTe can be expanded to 32 zones by adding one 16 Zone Wireless Receiver.
BURGLAR ZONE HOOKUPS
The Omni LTe system supports both normally open and normally closed switches. Most contacts designed for doors,
windows, motion detectors, glassbreak detectors and other security devices meet this requirement. An external 1000-
ohm end-of-line resistor must be used for all burglary zones if ZONE RESISTORS is set to "Yes".
1. When using a normally open switch, a 1000-ohm end-of-line resistor must be in parallel with the zone being used.
Maximum loop resistance excluding end-of-line resistor should not exceed 150 ohms. ZONE RESISTORS must
be set to "Yes".
2. When using a normally closed switch, a 1000-ohm end-of-line resistor must be put in series with the zone being
used if ZONE RESISTORS are set to "Yes". If ZONE RESISTORS are set to "No", the 1000-ohm end-of-line
resistor is not used. Maximum loop resistance excluding end-of-line resistor should not exceed 150 ohms.
3. Power motion detectors from AUXILIARY 12V.
4. Unused zones may be left open, and should be left at the default setting of AUXILIARY zone types.
5. When Zones 1-4 are configured to anything other than a Supervised Fire or Gas zone, the corresponding Zone
Jumpers (JP11-JP14) must be in the NRM (normal) position.
6. See FIGURE 2 (OVERALL CONNECTIONS DIAGRAM) for configurations of burglary zones.
WEB VERSION

Page 5
EARTH
GROUND
TRANSFORMER
24 VAC 40 VA
INTERIOR
SOUNDER
SWITCHED
12 VDC
AUXILIARY 12 VDC
CONSOLE(S)
NOTES:
1. SWITCH 12V, AUXILIARY 12V, CONSOLE, AND OUTPUTS 1-8 ARE INCLUDED IN THE TOTAL DEVICE LOAD, WHICH CANNOT EXCEED 1 AMP.
2. SOUNDERS CANNOT EXCEED 1 AMP, SPLIT BETWEEN INTERIOR AND EXTERIOR HORN OUTPUTS. IN UL INSTALLATIONS, SOUNDERS CANNOT EXCEED 350mA.
OMNISTAT
THERMOSTAT(S)
EXTERIOR
SOUNDER
1A Max.
(See NOTE 1)
1A Max.
(See NOTE 1)
(See NOTE 2)
ZONE (1-4)
IN
4-WIRE FIRE ZONE
ZONE (1-4)
ZN
1K
EOL
SMOKE
2-WIRE
12V
2-WIRE FIRE ZONE
SMK
NRM
COM
OUT
WARNING
SMOKE
4-WIRE
12V
SWITCH 12V
(OUTPUT)
12V
ZN
JP11-14
(OUTPUT)
SWITCH 12V
INPUT
OUTPUT
ZN 1K
EOL
NRM
SMK
TO PREVENT RISK
FROM ELECTRIC SHOCK,
DE-ENERGIZE THIS
UNIT AND DISCONNECT
TELEPHONE LINES
BEFORE SERVICING.
OUTPUT
100 mA Max. (See NOTE 1)
OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT OUTPUT
ALL CIRCUITS EXCEPT FOR THE BATTERY
ARE POWER-LIMITED (CLASS II)
CONNECT CABLE
TO CONTROLLER,
PLUG MODULAR
END INTO
RJ31X JACK
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONE
INPUT
ZONES 1-16 ARE CONFIGURABLE FOR BURGLARY, FIRE, TEMPERATURE, OR AUXILIARY.
2-WIRE SOMKE DETECTORS MAY ONLY BE CONNECTED TO ZONES 1-4.
INPUT
ZONE
INPUT
ZONE
INPUT
ZONEZONE
INPUT
ZONE
INPUT
ZONEZONE
INPUT INPUT
ONLY ZONES 9-16 MAY BE CONFIGURED AS ENERGY SAVER ZONES.
ONLY ZONE 16 MAY BE USED FOR OMNISTAT THERMOSTATS.
JP11-14
ZONEZONE ZONE
1K EOL 1K EOL 1K EOL
(NC)
(NO)
(NO)
(NC)
BURGLARY ZONES
IN UL INSTALLATIONS, THE TOTAL DEVICE LOAD CANNOT EXCEED 250mA.
FIGURE 2 - OVERALL CONNECTIONS DIAGRAM
ABOUT FIRE ZONES
The Omni LTe system supports normally open (closed for alarm), two-wire or four-wire smoke detectors. Two-wire
smoke detectors can only be connected to Zones 1-4. Four-wire smoke detectors can be connected to Zones 1-16.
An external 1000-ohm end-of-line resistor must be used for all fire (and gas) zones. When Zones 1-4 are configured
as a Supervised Fire (two-wire or four-wire) or Gas zone, the corresponding Zone Jumpers (JP11-JP14) must be in
the "SMK" (smoke) position. Zone Jumper "JP11" corresponds to Zone 1, "JP12" corresponds to Zone 2, "JP13"
corresponds to Zone 3, and "JP14" corresponds to Zone 4.
1. Smoke detectors must be powered from SWITCH 12V or an Output configured as a SWITCHED POWER
OUTPUT.
2. End of line resistor: 1000 ohms. Maximum loop resistance EXCLUDING end of line resistor is a 150 ohms. Use
LEVITON Model 1503A0011 End of Line Resistor Assembly in UL Listed Installations.
3. Smoke detectors are reset when the security system is armed.
WEB VERSION

Page 6
TWO-WIRE SMOKE DETECTORS
Omni LTe supports two-wire smoke detectors connected to Zones 1-4.
1. Use normally open (closed for alarm) two-wire "SYSTEM" type smoke detectors (See - 2-Wire Smoke Detector
Compatibility Chart).
2. Smoke detectors must be connected to Zones 1-4 and configured as a Supervised Fire Zone.
3. An external 1000-ohm end-of-line resistor must be used.
4. Connect to the SWITCH 12V or an Output configured as a SWITCHED POWER OUTPUT.
5. The corresponding Zone Jumpers (JP11-JP14) must be in the SMK (smoke) position.
4. Refer to FIGURE 3 (TWO-WIRE FIRE ZONE CONNECTIONS) for this configuration.
Smoke detector compatibility identifier: A
Detector Models
Detector Manufacturer
Maximum Detectors/Zone
2W-B
2WT-B
System Sensor, Unincorporated Div. of Honeywell International Inc.
10
DS260
DS282
DS282S
DS282TH
DS282THS
DS250
DS250TH
Bosch Security Systems
10
F220-P
F220-PTH
F220-PTHC
DS230
DS230F
Bosch Security Systems
8
429AT
521B (SW 1 “ON”)
521BXT (SW 1 “ON”)
521NB (6V)
521NBXT (6V)
GE Security Inc.
10
2-Wire Smoke Detector Compatibility Chart
FOUR-WIRE SMOKE DETECTORS
Omni LTe supports four-wire smoke detectors connected to any zone (1-16).
1. Use normally open (closed for alarm) four-wire "SYSTEM" type smoke detectors (System Sensor 2112/24TR or
equivalent), rated 8 - 14VDC.
2. An End of Line Power Supervision Relay Module (System Sensor A77-716B or equivalent) is required for UL
installations. Install 1000-ohm end-of-line resistor as shown.
3. Power the smoke detector from SWITCH 12V or an Output configured as a SWITCHED POWER OUTPUT.
4. When connected to Zones 1-4, the appropriate Zone Jumper (JP11-JP14) must be in the SMK (smoke) position.
NOTE: Smoke detectors connected to Zones 1-4 are wired differently from those connected to Zones 5-48.
Refer to FIGURE 4 (FOUR-WIRE FIRE ZONE CONNECTIONS) for each configuration.
WEB VERSION

Page 7
ZONE
ZONE
ZONE
ZONE
BOTTOM
PLATE
MODEL 2100TS
SYSTEM SENSOR
PLATE
BOTTOM
MODEL 2100TS
SYSTEM SENSOR
MODEL 1503A0011
1K OHM EOL RESISTOR
WHEN Z1-Z4 IS CONFIGURED AS A
SUPERVISED FIRE OR GAS ZONE, THE
CORRESPONDING ZONE JUMPERS J11-J14
MUST BE IN "SMK" POSISTION
FIGURE 3 - TWO-WIRE FIRE ZONE CONNECTIONS
WEB VERSION

Page 8
ZONE
ZONE
BOTTOM
PLATE
PLATE
BOTTOM
MODEL 2112/24TR
SYSTEM SENSOR
MODEL 1503A0011
1K OHM EOL RESISTOR
FOUR-WIRE DETECTORS ON ZONES 1-4
+12V
GND
YELLOW
GREEN
RED
BLACK
ZONE
ZONE
+12V
GND
YELLOW
BLACK
RED
GREEN
BLACK
VIOLET
VIOLET
GREEN
YELLOW
BLACK
RED
RED
MODEL A77-716B
SYSTEM SENSOR
RELAY
SUPERVISION
EOL POWER
ZONE POWER
GREEN
ZONE
VIOLET
RELAY
VIOLET
1K OHM EOL RESISTOR
MODEL 1503A0011
YELLOW
RED
+12V
MODEL A77-716B
SYSTEM SENSOR
SUPERVISION
EOL POWER
GND
BLACK
RED
POWER
BLACK
MODEL 2112/24TR
SYSTEM SENSOR
ZONE
ZONE GREEN
YELLOW
BLACK
RED
PLATE
BOTTOM
SYSTEM SENSOR
MODEL 2112/24TR
ZONE
GND
+12V
ZONE
YELLOW
BLACK
RED
GREEN
PLATE
BOTTOM
BLACK
RED
YELLOW
GREEN
GREEN
RED
BLACK
YELLOW
MODEL 2112/24TR
SYSTEM SENSOR
CORRESPONDING ZONE JUMPERS J11-J14
SUPERVISED FIRE OR GAS ZONE, THE
WHEN Z1-Z4 IS CONFIGURED AS A
MUST BE IN "SMK" POSISTION
FOUR-WIRE DETECTORS ON ZONES 5-16
FIGURE 4 - FOUR-WIRE FIRE ZONE CONNECTIONS
WEB VERSION

Page 9
TELEPHONE CONNECTIONS
1. If an RJ31X jack has been supplied by the telephone company, it is probably wired correctly and the controller
can be connected by plugging the supplied 8 conductor telephone cable into the RJ31X jack. The other end of
the cable is spaded. The green, red, brown, and gray wires must be connected to the controller at the designated
terminals under the section of the board marked 'PHONE'.
2. If required, install the supplied RJ31X jack as shown in the following diagram. The polarity must be correct for
proper operation of the phone access feature.
3. IT IS IMPERATIVE THAT THE PHONE LINE COMING INTO THE HOUSE BE CONNECTED TO A GROUNDED
SURGE ARRESTOR OUTSIDE THE PREMISES. IT IS THE RESPONSIBILITY OF THE TELEPHONE
COMPANY TO PROVIDE THIS SURGE ARRESTOR.
4. INSPECT THE INCOMING PHONE LINES. THE FIRST THING THAT THEY SHOULD GO TO IS A SMALL BOX
ON THE OUTSIDE OF THE PREMISES. THERE SHOULD BE A HEAVY GROUND WIRE COMING FROM
THIS BOX GOING TO A COLD WATER PIPE OR A SEPARATE GROUNDING ROD.
5. IF THERE IS NO SURGE ARRESTOR OR IF THE GROUND WIRE IS MISSING, HAVE THE CUSTOMER
INSIST THAT THE TELEPHONE COMPANY INSTALL ONE FOR THE SAFETY OF THE CUSTOMER.
6. WHEN WIRING A RJ31X JACK, MAKE SURE THAT THE INCOMING PHONE LINES GO TO THE TELEPHONE
COMPANY SURGE ARRESTOR BEFORE THEY GO TO THE RJ31X JACK.
7. When the RJ31X is installed as shown, locate the green, red, brown, and gray spaded wires from the 8 conductor
phone cable and connect to the section on the Omni LTe controller marked 'PHONE'. Plug the modular end of
the cable into the RJ31X jack. If necessary, bend the tab up on the plug to ensure a tight fit that will not fall out.
8. Verify the following if you have trouble during check out: With the system running, the RJ31X jack properly
connected and all phones on-hook (hung up), the PHONE LED, located in the upper left corner of the controller,
should be OFF. If it is on, reverse the RED and GREEN wires to both the house phones and the telephone
company wires at the RJ31X jack. When the receiver is picked up on any phone, the PHONE LED will come on.
When the phone line rings, the PHONE LED will light.
9. If the Omni LTe is accessed on an in house telephone, the Omni LTe will disconnect the phones from the phone
company lines and supply its own talk voltage to the phones. The PHONE LED will be on in this case.
10. Refer to FIGURE 5 (RJ31X JACK CONNECTIONS) for this configuration.
DIGITAL SUBSCRIBER LINE (DSL) CONNECTIONS
When the Omni LTe is connected to a Digital Subscriber Line (DSL), a DSL Splitter must be used to provide separate
outputs for filtered voice (phone) and DSL (data). Splitting the voice and data is necessary because:
1. The higher frequencies of the DSL signal must not pass through the Omni LTe controller. It can cause problems
with the DTMF detection and the digital dialer.
2. Whenever the Omni LTe is accessed on an in house telephone, the Omni LTe will disconnect the phones from
the phone company lines (in this case the DSL line). When that occurs, the DSL connection is temporarily lost.
Refer to FIGURE 6 (DSL SPLITTER CONNECTIONS) for this configuration.
WEB VERSION

Page 10
OR PBX
TELEPHONES
TO ALL HOUSE
JACK(S)
PHONE
HOUSE
RJ11
GREEN(+)
GREEN(+)
ENSURE TIGHT FIT
NECESSARY TO
BEND TAB UP IF
SURGE ARRESTOR
INTERFACE AT
TO TELCO
RED(-)
SURGE ARRESTOR
ACCESS
CUSTOMER
RED(-)
INTERFACE
TELEPHONE
NETWORK
MUST BE GROUNDED!
SURGE ARRESTOR
GREEN
RED
BROWN
GRAY
FIGURE 5 - RJ31X JACK CONNECTIONS
WEB VERSION

Page 11
DSL SPLITTER
DATA
VOICE
TO ALL HOUSE
TELEPHONES
JACK(S)
RJ11
HOUSE
PHONE
GREEN(+)
DSL MODEM
RED(-)
GREEN(+) RED(-)
COMPUTER
LINE IN
NETWORK
TELEPHONE
INTERFACE
SURGE ARRESTOR
CUSTOMER
ACCESS
SURGE ARRESTOR
MUST BE GROUNDED!
FIGURE 6 - RJ31X JACK CONNECTIONS
LCD CONSOLE HOOKUP
1. 4 LCD Consoles (Models 33A00-1, 33A00-4, 11A00-1, 11A00-2, 11A00-9, and 15A00) MAXIMUM per system,
subject to power availability.
2. Use 4-conductor 22-gage wire, 1000 feet maximum length. Consoles can be homerun or daisy chained. This
length shall be divided by the total number of consoles at the end of the run. For example, for 8 consoles, the
maximum length reduces to 125 feet. All LCD Consoles are connected to the same 4 wires, +12, GND, A, B.
3. The console should be mounted so that the LCD display is at or slightly above eye level. Consoles should be
kept out of the reach of young children. A good height is approximately 58 inches from the floor to the bottom of
the console enclosure.
4. Remove console face from back plate (slots on bottom of console will release back plate, use a screwdriver).
Mount the back plate to the wall. Mounting holes are designed to fit on a single or double gang box, or directly to
the wall. Pull the wires from the wall through the opening in the back plate. Splice the wires to the supplied
cable. Connect the cable to the connector on the console board (J1). Snap the console face on to the back plate.
Remove protective film from the LCD lens.
5. Refer to FIGURE 7 (CONSOLE CONNECTIONS) for this configuration.
WEB VERSION

Page 12
CONSOLE SETUP
The console has different operating options that can be setup from the console to the user's preference. If more than
one console is being used, it is required that you give each console a different address. You can change the address
of a console through the console setup mode.
To enter the console setup mode, simultaneously press and hold the 4 and up arrow () for approximately 1 second.
The console will beep 5 times and enter the setup mode. The top line of the display will indicate what you are doing,
followed by the current setting. The bottom line will show a menu of your options. To the lower right corner of the
display is the direction arrow(s). Where possible, the up (↑), down (↓), and two-headed () arrow characters are
shown on the console display to indicate which arrow keys may be pressed at that time. Press the down arrow ()
key to advance to the next item. Press the up arrow () key to go back to the previous item.
CONSOLE ADDRESS
If you are installing more than one console, each console must be set to a different address. The default address
setting is (1) - this is adequate if only one console is being used. The choices at the bottom are 1-16. When making
your choice, choose an address between 1-4, and press the # (pound) key.
SOUNDER
If you wish not to hear the beeper in the console for any reason, the sounder option can be turned off. Select (0) for
OFF or (1) for ON, then press the # key.
KEY CLICK
The sounder makes a click every time a key is pressed. This option may also be turned off. Select (0) for OFF or (1)
for ON, then press the # key.
KEY BACKLIGHT
The keys on the console keypad are lit. The keys can be never lit, always lit, or only lit when the LCD display is lit.
Select (0) OFF, (1) for ON, or (2) TIMED, then press the # key.
VIEWING ADJUSTMENT
This option is an adjustment for the viewing angle of the LCD display. This has been set to its best value at the
factory, however, you may wish to tweak it. The display has 20 levels of adjustment. Select (1) for a lower viewing
angle, or (2) for a higher viewing angle.
LANGUAGE
This option is to display the 'console setup' text on the LCD display in English, French, Italian, or Spanish. Select one
of the languages, then press the # key.
EXIT SETUP MODE
To exit Setup Mode, press and hold the 4 and up arrow () keys simultaneously for about 1 second. The console will
return to normal operation. You may need to press (*) to restore the display.
WEB VERSION

Page 13
MENUCANCEL
MESSAGE
TEMP
EVENTS
ALL
SETUP
AUX
STATUS
FIRE
SECURITYCONTROL BUTTONS
POL
(MOUNTED TO CONSOLE FACE)
CONSOLE PC BOARD
BOTTOM PLATE
YELLOW
GREEN
RED
BLACK
CONNECT ENDS OF SUPPLIED
CABLE TO CORRESPONDING
ENDS OF 4 - WIRE CABLE
FROM CONTROLLER
SUPPLIED CABLE
(PLUGS INTO J1)
GREEN
YELLOW
BLACK
RED
(SNAPS ON TO BOTTOM PLATE)
CONSOLE FACE
FOR MODEL NUMBERS
SEE NOTE 1 UNDER
"LCD CONSOLE HOOKUP"
FIGURE 7 - CONSOLE CONNECTIONS
WEB VERSION

Page 14
SOUNDER OUTPUTS
The Horn Output provides 12VDC to power bells, piezo sirens, self-contained sirens, and siren drivers (do not connect
speakers to the Horn Output). Sounders can draw up to 1 amp MAXIMUM, split between the Interior and Exterior
Horn Outputs - (See Specifications for UL Ratings). Use a relay connected to an auxiliary power supply if higher
current draw is required.
INTERIOR SOUNDER HOOKUP
1. Locate the interior sounder in a central location. The sounder is very loud. Do not install it in a room where small
children or animals could be trapped if the alarm is activated.
2. The Interior Horn Output monitors the wiring to bells and sirens. When enabled, it will report trouble and make a
digital dial out when an open, short, or other wiring problem is detected in the supervised bell circuit. When
violated, the following trouble is displayed on the console, "FIRE TAMPER TRBL NOW".
3. For UL Listed residential fire alarm applications, the UL Listed Wheelock Model MT-12/24-R Multitone Signal or
equivalent must be used, and the "SUPERVISE INT SNDR" feature must be set to "ON".
4. Refer to FIGURE 8 (SOUNDER CONNECTION) for connections.
EXTERIOR SOUNDER HOOKUP
1. If used, wire tamper switches to a tamper zone with a 1000-ohm end-of-line resistor.
2. The Exterior Horn Output monitors the wiring to bells and sirens. When enabled, it will report trouble and make a
digital dial out when an open, short, or other wiring problem is detected in the supervised bell circuit. When
violated, the following trouble is displayed on the console, "FIRE TAMPER TRBL NOW".
3. To enable supervision of the Exterior Horn Output, the "SUPERVISE EXT SNDR" feature must be set to "ON".
5. Refer to FIGURE 8 (SOUNDER CONNECTION) for connections.
WEB VERSION
Table of contents
Other Leviton Security System manuals
Popular Security System manuals by other brands

Smartwares
Smartwares SC88 Instructions for use

GSS
GSS PROFESSIONAL PAVP 4300 Assembly instructions

NAPCO
NAPCO MAGNUM ALERT 854 SYSTEM manual

Interactive Technologies
Interactive Technologies ITI Simon owner's manual

Concoa
Concoa 529 5310 Installation and operation instruction

Se-Kure Controls
Se-Kure Controls SK-554NP-RKAC-4 installation instructions