- 2 -
Copyright ©2009 LG Electronics. Inc. All right reserved.
Only for training and service purposes LGE Internal Use Only
1. Specification
Notes:-
1. Capacities are based on the following conditions:
Cooling • Indoor temp. 27°C[80.6°F]DB/ 19°C[66.2°F]WB
• Outdoor temp. 35°C[95°F]DB/ 24°C[75.2°F]WB
• Interconnecting piping length 7.5m
• Level difference of zero
Heating • Indoor temp. 20°C[68°F]DB/ 15°C[59°F]WB
• Outdoor temp. 7°C[44.6°F]DB/ 6°C[42.8°F]WB
• Interconnecting piping length 7.5m
• Level difference of zero
2. Capacities are net capacities
3. Due to our policy of innovation some specifications may be changed without prior notification
4. To be added for more available models
5. EEV : Electronic expansion valve
Conversion formula
kcal/h= kW x 860
Btu/h = kW x 3412
cfm = m3/min x 35.3
l/s = CMM x 1000/60
Indoor unit type 1Way ceiling cassette (art type)
Model AMNW09GTUC0
[MT09AH NU1]
AMNW12GTUC0
[MT12AH NU1]
Power Supply Ø / V / Hz 1/220~240/50 1/220~240/50
Cooling Capacity kW 2.64 3.52
Btu/h 9,000 12,000
Heating Capacity kW 2.93 3.87
Btu/h 10,000 13,200
Current Nominal Running Current A 0.2 0.2
Fan
Motor Type BLDC BLDC
Fan Type Cross Flow Fan Cross Flow Fan
Motor Output(W) x No. of Unit 20 x 1 20 x 1
Air Flow Rate
(H / M / L)
CMM 7.5/7.3/6.8 8.1/7.4/7.0
CFM 265/258/240 286/261/247
Capacitor μF / Vac - -
Drive Direct Drive Direct Drive
Coil Row x Column x FPI 2R x 12C x 18 2R x 12C x 18
Dimensions (W x H x D)
Body mm 860 x 132 x 450 860 x 132 x 450
inch 33.8 x 5.2 x 17.7 33.8 x 5.2 x 17.7
Front Panel mm 1,100 x 34 x 500 1,100 x 34 x 500
inch 43.3 x 1.3 x 19.7 43.3 x 1.3 x 19.7
Net Weight Body kg (lbs) 13.5(29.8) 13.5(29.8)
Package kg (lbs) 17.0(37.5) 17.0(37.5)
Sound Level (H / M / L) dB(A) + 3 36/34/32 37/36/33
Piping
Connections
Liquid mm(inch) 6.35(1/4) 6.35(1/4)
Gas mm(inch) 9.52(3/8) 9.52(3/8)
Drain(OD/ID) mm Φ32.0 / 25.0 Φ32.0 / 25.0
Safety Devices Fuse, Thermal Protector for Fan Motor
Temperature Sensor Thermistor Thermistor
Referigerant R410A R410A
Referigerant Control EEV(in Outdoor unit or BD) EEV(in Outdoor unit or BD)
Connectable Outdoor Unit Multi F / FDX series Multi F / FDX series
Power and Transmission Interunit Cable No. x mm24 x 0.75(including earth) 4 x 0.75(including earth)