manuals.online logo
Brands
  1. Home
  2. •
  3. Brands
  4. •
  5. LG
  6. •
  7. Heat Pump
  8. •
  9. LG Multi V ZRUM080LTE6 Product guide

LG Multi V ZRUM080LTE6 Product guide

Multi V Outdoor Unit
Heat Recovery + Heat Pump (R32)
MFL67474088
Region : EU
Published on Feb. 2, 2024
Model Line Up
Combination of Outdoor Units
Multi V Outdoor Unit
General Information
Product Phase Chassis
Capacity
Index Model Name
HP
Multi V i 3
UXA(α)
8 ZRUM080LTE6
10 ZRUM100LTE6
12 ZRUM120LTE6
UXB(α)
14 ZRUM140LTE6
16 ZRUM160LTE6
18 ZRUM180LTE6
20 ZRUM200LTE6
UXA + UXA 22 ZRUM220LTE6
UXB + UXA
24 ZRUM240LTE6
26 ZRUM260LTE6
28 ZRUM280LTE6
* The capacity index may differ from actual capacity values.
Multi V Outdoor Unit
1. Model Line Up
General Information
1
Model Name Combination Unit
Unit 1 Unit 2 Unit 3 Unit 4
ZRUM220LTE6 ZRUM100LTE6 ZRUM120LTE6 - -
ZRUM240LTE6 ZRUM100LTE6 ZRUM140LTE6 - -
ZRUM260LTE6 ZRUM120LTE6 ZRUM140LTE6 - -
ZRUM280LTE6 ZRUM120LTE6 ZRUM160LTE6 - -
Multi V Outdoor Unit
2. Combination of Outdoor Units
General Information
2
Multi V i
Product Data
1. Specifications
2. List of Functions
3. Accessory Compatibility List
4. Dimensions
5. Piping Diagrams
6. Wiring Diagrams
7. Capacity Tables
8. Capacity Correction Factor
9. Operation Limits
10. Sound Levels
Multi V i
1.1 Product
ZRUM080LTE6
Category
Unit Specification
Major Minor
Classification
Chassis - UXA
Combination Unit (1) - ZRUM080LTE6
Combination Unit (2) - -
Combination Unit (3) - -
Combination Unit (4) - -
Power Supply
Case 1 V, Phase, Hz 380-400-415, 3, 50
Limit Range of Voltage(Case 1) V 342 ~ 456
Case 2 V, Phase, Hz 380, 3, 60
Limit Range of Voltage(Case 2) V 342 ~ 418
Running Current by Voltage (Cooling,Rated) A 9.97 - 9.47 - 9.13
Running Current by Voltage (Heating,Rated) A 8.43 - 8.01 - 7.72
Cooling Capacity Rated
kW 22.4
Btu/h 76,400
Heating Capacity
Rated
kW 22.4
Btu/h 76,400
Max
kW 25.2
Btu/h 86,000
Power Input(Cooling) Rated kW 6.10
Power Input(Heating) Rated kW 5.16
Efficiency
EER(Rated) W/W 3.67
COP(Rated) W/W 4.34
SEER Wh/Wh 8.28
SCOP Wh/Wh 4.45
Power Factor(Cooling/Heating) Rated - 0.93 / 0.93
Outdoor Fan
Type - Propeller fan
Air Flow Rate(High) m³/min 220
Max. External Static Pressure Pa 80
Discharge direction(Side / Top) - Top
Outdoor Fan Motor
Type - BLDC
Drive - Direct
Output W x No. 1,200 x 1
Compressor
Type - Hermetically Sealed Scroll
Piston Displacement cm³/rev 62.1
Number of Revolution rev./min 3,600
Motor Output W x No. 5,300 × 1
Starting Method - Inverter
Oil Type - FW68L(PVE)
Heat Exchanger
Type - Fin & Tube
No. - 1
Fin Type - Wide Louver Plus
Dimensions
Net(W x H x D) mm 930 x 1,745 x 760
Shipping(W x H x D) mm 965 x 1,919 x 802
Weight
Net kg 215
Shipping kg 225
Exterior
Color - Morning Gray / Dawn Gray
RAL (Classic) - RAL 7038 / RAL 7037
Protection Device
High Pressure Prevention - High pressure sensor / High pressure switch
Frost Prevention - O (Logical)
Discharge Tempreature Control - O (Logical)
Multi V i
1. Specifications
Product Data
1-1
Category
Unit Specification
Major Minor
Protection Device Compressor/Fan Protection - Over-heat protection / Fan driver overload protector
Inverter Protection - Over-heat protection / Over-current protection
Refrigerant
Type - R32
Precharged Amount kg 7.5
GWP(Global Warming Potential) - 675
t-CO₂ eq. - 5.063
Control Type - EEV
Connecting Pipe
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Low Pressure Gas (Heat Recovery) mm(inch) Φ19.05 (3/4)
High Pressure Gas (Heat Recovery) mm(inch) Φ15.88 (5/8)
Piping Connection Type
Liquid - Brazing
Gas - Brazing
Low Pressure Gas (Heat Recovery) - Brazing
High Pressure Gas (Heat Recovery) - Brazing
Sound Pressure Level (Outdoor Unit) Cooling / Heating dB(A) 57.0 / 58.0
Measurement Standard (Pressure Leve
l) - - ISO 3745
Sound Power Level (Outdoor Unit) Cooling / Heating dB(A) 78.0 / 78.0
Measurement Standard (Power Level) - - ISO 9614
Connecting Cable Communication Cable(VCTF-SB) mm² × cores 0.75 ~ 1.5 x 2C
Electrical Characteristic
Minimium Circuit Amperes (MCA) A 18.2
Maximum Fuse Amperes (MFA) A 20.0
Total Over Current Amperes (TOCA) A 20.0
Comp_Maximum Starting Current (MSC) A 5.9
Comp_Rated Load Amperes (Cooling) A 7.5
Comp_Rated Load Amperes (Heating) A 5.9
Outdoor Fan Motor_Full Load Amperes (FLA) A 2.5
Connectable indoor units number Max. (Conditional) Units 13(20)
Note
■Due to our policy of innovation some specifications may be changed without notification.
■Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■Power factor could vary less than ±1% according to the operating conditions.
■Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
■EUROVENT Test Condition :
-Performance values on the this PDB are based on Ceiling Mounted Cassette combination.
-Refer to EUROVENT web site (www.eurovent-certification.com) for other indoor unit combination and more detail test conditions.
■Use appropriate power source refer to national standard.
■Voltage supplied to the unit terminals should be within the minimum and maximum range.
■Maximum allowable voltage unbalance between phase is 2%.
■MSC means the Max. current during the starting of compressor.
MSC and RLA are measured as the compressor only test condition.
OFM are measured as the outdoor unit test condition.
TOCA means the total over current value of each outdoor unit.
Select the wire size based on the larger value among MCA or TOCA.
MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].
■Performances are based on the following conditions :
- Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
Multi V i
1. Specifications
Product Data
1-2
ZRUM100LTE6
Category
Unit Specification
Major Minor
Classification
Chassis - UXA
Combination Unit (1) - ZRUM100LTE6
Combination Unit (2) - -
Combination Unit (3) - -
Combination Unit (4) - -
Power Supply
Case 1 V, Phase, Hz 380-400-415, 3, 50
Limit Range of Voltage(Case 1) V 342 ~ 456
Case 2 V, Phase, Hz 380, 3, 60
Limit Range of Voltage(Case 2) V 342 ~ 418
Running Current by Voltage (Cooling,Rated) A 13.61 - 12.39 - 12.47
Running Current by Voltage (Heating,Rated) A 10.17 - 9.66 - 9.31
Cooling Capacity Rated
kW 28.0
Btu/h 95,500
Heating Capacity
Rated
kW 28.0
Btu/h 95,500
Max
kW 31.5
Btu/h 107,500
Power Input(Cooling) Rated kW 8.33
Power Input(Heating) Rated kW 6.22
Efficiency
EER(Rated) W/W 3.36
COP(Rated) W/W 4.50
SEER Wh/Wh 8.11
SCOP Wh/Wh 4.52
Power Factor(Cooling/Heating) Rated - 0.93 / 0.93
Outdoor Fan
Type - Propeller fan
Air Flow Rate(High) m³/min 220
Max. External Static Pressure Pa 80
Discharge direction(Side / Top) - Top
Outdoor Fan Motor
Type - BLDC
Drive - Direct
Output W x No. 1,200 x 1
Compressor
Type - Hermetically Sealed Scroll
Piston Displacement cm³/rev 62.1
Number of Revolution rev./min 3,600
Motor Output W x No. 5,300 x 1
Starting Method - Inverter
Oil Type - FW68L(PVE)
Heat Exchanger
Type - Fin & Tube
No. - 1
Fin Type - Wide Louver Plus
Dimensions
Net(W x H x D) mm 930 x 1,745 x 760
Shipping(W x H x D) mm 965 x 1,919 x 802
Weight
Net kg 215
Shipping kg 225
Exterior
Color - Morning Gray / Dawn Gray
RAL (Classic) - RAL 7038 / RAL 7037
Protection Device
High Pressure Prevention - High pressure sensor / High pressure switch
Frost Prevention - O (Logical)
Discharge Tempreature Control - O (Logical)
Compressor/Fan Protection - Over-heat protection / Fan driver overload protector
Inverter Protection - Over-heat protection / Over-current protection
Multi V i
1. Specifications
Product Data
1-3
Category
Unit Specification
Major Minor
Refrigerant
Type - R32
Precharged Amount kg 8.5
GWP(Global Warming Potential) - 675
t-CO₂ eq. - 5.738
Control Type - EEV
Connecting Pipe
Liquid mm(inch) Φ9.52 (3/8)
Gas mm(inch) Φ19.05 (3/4)
Low Pressure Gas (Heat Recovery) mm(inch) Φ19.05 (3/4)
High Pressure Gas (Heat Recovery) mm(inch) Φ15.88 (5/8)
Piping Connection Type
Liquid - Brazing
Gas - Brazing
Low Pressure Gas (Heat Recovery) - Brazing
High Pressure Gas (Heat Recovery) - Brazing
Sound Pressure Level (Outdoor Unit) Cooling / Heating dB(A) 57.5 / 58.5
Measurement Standard (Pressure Leve
l) - - ISO 3745
Sound Power Level (Outdoor Unit) Cooling / Heating dB(A) 79.0 / 79.0
Measurement Standard (Power Level) - - ISO 9614
Connecting Cable Communication Cable(VCTF-SB) mm² × cores 0.75 ~ 1.5 x 2C
Electrical Characteristic
Minimium Circuit Amperes (MCA) A 25.1
Maximum Fuse Amperes (MFA) A 32
Total Over Current Amperes (TOCA) A 28.0
Comp_Maximum Starting Current (MSC) A 5.9
Comp_Rated Load Amperes (Cooling) A 11.1
Comp_Rated Load Amperes (Heating) A 7.7
Outdoor Fan Motor_Full Load Amperes (FLA) A 2.5
Connectable indoor units number Max. (Conditional) Units 16(25)
Note
■Due to our policy of innovation some specifications may be changed without notification.
■Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■Power factor could vary less than ±1% according to the operating conditions.
■Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
■EUROVENT Test Condition :
-Performance values on the this PDB are based on Ceiling Mounted Cassette combination.
-Refer to EUROVENT web site (www.eurovent-certification.com) for other indoor unit combination and more detail test conditions.
■Use appropriate power source refer to national standard.
■Voltage supplied to the unit terminals should be within the minimum and maximum range.
■Maximum allowable voltage unbalance between phase is 2%.
■MSC means the Max. current during the starting of compressor.
MSC and RLA are measured as the compressor only test condition.
OFM are measured as the outdoor unit test condition.
TOCA means the total over current value of each outdoor unit.
Select the wire size based on the larger value among MCA or TOCA.
MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].
■Performances are based on the following conditions :
- Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
Multi V i
1. Specifications
Product Data
1-4
ZRUM120LTE6
Category
Unit Specification
Major Minor
Classification
Chassis - UXA
Combination Unit (1) - ZRUM120LTE6
Combination Unit (2) - -
Combination Unit (3) - -
Combination Unit (4) - -
Power Supply
Case 1 V, Phase, Hz 380-400-415, 3, 50
Limit Range of Voltage(Case 1) V 342 ~ 456
Case 2 V, Phase, Hz 380, 3, 60
Limit Range of Voltage(Case 2) V 342 ~ 418
Running Current by Voltage (Cooling,Rated) A 19.03 - 18.08 - 17.43
Running Current by Voltage (Heating,Rated) A 12.69 - 12.05 - 11.62
Cooling Capacity Rated
kW 33.6
Btu/h 114,600
Heating Capacity
Rated
kW 33.6
Btu/h 114,600
Max
kW 37.8
Btu/h 129,000
Power Input(Cooling) Rated kW 11.65
Power Input(Heating) Rated kW 7.77
Efficiency
EER(Rated) W/W 2.88
COP(Rated) W/W 4.32
SEER Wh/Wh 7.94
SCOP Wh/Wh 4.99
Power Factor(Cooling/Heating) Rated - 0.93 / 0.93
Outdoor Fan
Type - Propeller fan
Air Flow Rate(High) m³/min 220
Max. External Static Pressure Pa 80
Discharge direction(Side / Top) - Top
Outdoor Fan Motor
Type - BLDC
Drive - Direct
Output W x No. 1,200 x 1
Compressor
Type - Hermetically Sealed Scroll
Piston Displacement cm³/rev 62.1
Number of Revolution rev./min 3,600
Motor Output W x No. 5,300 x 1
Starting Method - Inverter
Oil Type - FW68L(PVE)
Heat Exchanger
Type - Fin & Tube
No. - 1
Fin Type - Wide Louver Plus
Dimensions
Net(W x H x D) mm 930 x 1,745 x 760
Shipping(W x H x D) mm 965 x 1,919 x 802
Weight
Net kg 215
Shipping kg 225
Exterior
Color - Morning Gray / Dawn Gray
RAL (Classic) - RAL 7038 / RAL 7037
Protection Device
High Pressure Prevention - High pressure sensor / High pressure switch
Frost Prevention - O (Logical)
Discharge Tempreature Control - O (Logical)
Compressor/Fan Protection - Over-heat protection / Fan driver overload protector
Inverter Protection - Over-heat protection / Over-current protection
Multi V i
1. Specifications
Product Data
1-5
Category
Unit Specification
Major Minor
Refrigerant
Type - R32
Precharged Amount kg 8.5
GWP(Global Warming Potential) - 675
t-CO₂ eq. - 5.738
Control Type - EEV
Connecting Pipe
Liquid mm(inch) Φ12.7 (1/2)
Gas mm(inch) Φ22.2 (7/8)
Low Pressure Gas (Heat Recovery) mm(inch) Φ22.2 (7/8)
High Pressure Gas (Heat Recovery) mm(inch) Φ19.05 (3/4)
Piping Connection Type
Liquid - Brazing
Gas - Brazing
Low Pressure Gas (Heat Recovery) - Brazing
High Pressure Gas (Heat Recovery) - Brazing
Sound Pressure Level (Outdoor Unit) Cooling / Heating dB(A) 59.0 / 60.0
Measurement Standard (Pressure Leve
l) - - ISO 3745
Sound Power Level (Outdoor Unit) Cooling / Heating dB(A) 80.0 / 82.0
Measurement Standard (Power Level) - - ISO 9614
Connecting Cable Communication Cable(VCTF-SB) mm² × cores 0.75 ~ 1.5 x 2C
Electrical Characteristic
Minimium Circuit Amperes (MCA) A 25.5
Maximum Fuse Amperes (MFA) A 32
Total Over Current Amperes (TOCA) A 28.0
Comp_Maximum Starting Current (MSC) A 5.9
Comp_Rated Load Amperes (Cooling) A 16.5
Comp_Rated Load Amperes (Heating) A 10.2
Outdoor Fan Motor_Full Load Amperes (FLA) A 2.5
Connectable indoor units number Max. (Conditional) Units 20(30)
Note
■Due to our policy of innovation some specifications may be changed without notification.
■Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■Power factor could vary less than ±1% according to the operating conditions.
■Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
■EUROVENT Test Condition :
-Performance values on the this PDB are based on Ceiling Mounted Cassette combination.
-Refer to EUROVENT web site (www.eurovent-certification.com) for other indoor unit combination and more detail test conditions.
■Use appropriate power source refer to national standard.
■Voltage supplied to the unit terminals should be within the minimum and maximum range.
■Maximum allowable voltage unbalance between phase is 2%.
■MSC means the Max. current during the starting of compressor.
MSC and RLA are measured as the compressor only test condition.
OFM are measured as the outdoor unit test condition.
TOCA means the total over current value of each outdoor unit.
Select the wire size based on the larger value among MCA or TOCA.
MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].
■Performances are based on the following conditions :
- Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
Multi V i
1. Specifications
Product Data
1-6
ZRUM140LTE6
Category
Unit Specification
Major Minor
Classification
Chassis - UXB
Combination Unit (1) - ZRUM140LTE6
Combination Unit (2) - -
Combination Unit (3) - -
Combination Unit (4) - -
Power Supply
Case 1 V, Phase, Hz 380-400-415, 3, 50
Limit Range of Voltage(Case 1) V 342 ~ 456
Case 2 V, Phase, Hz 380, 3, 60
Limit Range of Voltage(Case 2) V 342 ~ 418
Running Current by Voltage (Cooling,Rated) A 19.41 - 18.44 - 17.77
Running Current by Voltage (Heating,Rated) A 13.77 - 13.08 - 12.61
Cooling Capacity Rated
kW 39.2
Btu/h 133,800
Heating Capacity
Rated
kW 39.2
Btu/h 133,800
Max
kW 44.1
Btu/h 150,500
Power Input(Cooling) Rated kW 11.88
Power Input(Heating) Rated kW 8.43
Efficiency
EER(Rated) W/W 3.30
COP(Rated) W/W 4.65
SEER Wh/Wh 8.55
SCOP Wh/Wh 5.17
Power Factor(Cooling/Heating) Rated - 0.93 / 0.93
Outdoor Fan
Type - Propeller fan
Air Flow Rate(High) m³/min 320
Max. External Static Pressure Pa 80
Discharge direction(Side / Top) - Top
Outdoor Fan Motor
Type - BLDC
Drive - Direct
Output W x No. 900 x 2
Compressor
Type - Hermetically Sealed Scroll
Piston Displacement cm³/rev 62.1
Number of Revolution rev./min 3,600
Motor Output W x No. 5,300 x 1
Starting Method - Inverter
Oil Type - FW68L(PVE)
Heat Exchanger
Type - Fin & Tube
No. - 1
Fin Type - Wide Louver Plus
Dimensions
Net(W x H x D) mm 1,240 x 1,745 x 760
Shipping(W x H x D) mm 1,282 x 1,919 x 802
Weight
Net kg 255
Shipping kg 265
Exterior
Color - Morning Gray / Dawn Gray
RAL (Classic) - RAL 7038 / RAL 7037
Protection Device
High Pressure Prevention - High pressure sensor / High pressure switch
Frost Prevention - O (Logical)
Discharge Tempreature Control - O (Logical)
Compressor/Fan Protection - Over-heat protection / Fan driver overload protector
Inverter Protection - Over-heat protection / Over-current protection
Multi V i
1. Specifications
Product Data
1-7
Category
Unit Specification
Major Minor
Refrigerant
Type - R32
Precharged Amount kg 11.4
GWP(Global Warming Potential) - 675
t-CO₂ eq. - 7.695
Control Type - EEV
Connecting Pipe
Liquid mm(inch) Φ12.7 (1/2)
Gas mm(inch) Φ22.2 (7/8)
Low Pressure Gas (Heat Recovery) mm(inch) Φ22.2 (7/8)
High Pressure Gas (Heat Recovery) mm(inch) Φ19.05 (3/4)
Piping Connection Type
Liquid - Brazing
Gas - Brazing
Low Pressure Gas (Heat Recovery) - Brazing
High Pressure Gas (Heat Recovery) - Brazing
Sound Pressure Level (Outdoor Unit) Cooling / Heating dB(A) 60.0 / 61.0
Measurement Standard (Pressure Leve
l) - - ISO 3745
Sound Power Level (Outdoor Unit) Cooling / Heating dB(A) 81.0 / 81.0
Measurement Standard (Power Level) - - ISO 9614
Connecting Cable Communication Cable(VCTF-SB) mm² × cores 0.75 ~ 1.5 x 2C
Electrical Characteristic
Minimium Circuit Amperes (MCA) A 26.9
Maximum Fuse Amperes (MFA) A 32
Total Over Current Amperes (TOCA) A 30.0
Comp_Maximum Starting Current (MSC) A 5.9
Comp_Rated Load Amperes (Cooling) A 16.9
Comp_Rated Load Amperes (Heating) A 11.3
Outdoor Fan Motor_Full Load Amperes (FLA) A 2.5
Connectable indoor units number Max. (Conditional) Units 23(35)
Note
■Due to our policy of innovation some specifications may be changed without notification.
■Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■Power factor could vary less than ±1% according to the operating conditions.
■Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
■EUROVENT Test Condition :
-Performance values on the this PDB are based on Ceiling Mounted Cassette combination.
-Refer to EUROVENT web site (www.eurovent-certification.com) for other indoor unit combination and more detail test conditions.
■Use appropriate power source refer to national standard.
■Voltage supplied to the unit terminals should be within the minimum and maximum range.
■Maximum allowable voltage unbalance between phase is 2%.
■MSC means the Max. current during the starting of compressor.
MSC and RLA are measured as the compressor only test condition.
OFM are measured as the outdoor unit test condition.
TOCA means the total over current value of each outdoor unit.
Select the wire size based on the larger value among MCA or TOCA.
MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].
■Performances are based on the following conditions :
- Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
Multi V i
1. Specifications
Product Data
1-8
ZRUM160LTE6
Category
Unit Specification
Major Minor
Classification
Chassis - UXB
Combination Unit (1) - ZRUM160LTE6
Combination Unit (2) - -
Combination Unit (3) - -
Combination Unit (4) - -
Power Supply
Case 1 V, Phase, Hz 380-400-415, 3, 50
Limit Range of Voltage(Case 1) V 342 ~ 456
Case 2 V, Phase, Hz 380, 3, 60
Limit Range of Voltage(Case 2) V 342 ~ 418
Running Current by Voltage (Cooling,Rated) A 25.24 - 23.98 - 23.11
Running Current by Voltage (Heating,Rated) A 16.48 - 15.65 - 15.09
Cooling Capacity Rated
kW 44.8
Btu/h 152,900
Heating Capacity
Rated
kW 44.8
Btu/h 152,900
Max
kW 50.4
Btu/h 172,000
Power Input(Cooling) Rated kW 15.45
Power Input(Heating) Rated kW 10.09
Efficiency
EER(Rated) W/W 2.90
COP(Rated) W/W 4.44
SEER Wh/Wh 7.97
SCOP Wh/Wh 5.46
Power Factor(Cooling/Heating) Rated - 0.93 / 0.93
Outdoor Fan
Type - Propeller fan
Air Flow Rate(High) m³/min 320
Max. External Static Pressure Pa 80
Discharge direction(Side / Top) - Top
Outdoor Fan Motor
Type - BLDC
Drive - Direct
Output W x No. 900 x 2
Compressor
Type - Hermetically Sealed Scroll
Piston Displacement cm³/rev 62.1
Number of Revolution rev./min 3,600
Motor Output W x No. 5,300 x 1
Starting Method - Inverter
Oil Type - FW68L(PVE)
Heat Exchanger
Type - Fin & Tube
No. - 1
Fin Type - Wide Louver Plus
Dimensions
Net(W x H x D) mm 1,240 x 1,745 x 760
Shipping(W x H x D) mm 1,282 x 1,919 x 802
Weight
Net kg 255
Shipping kg 265
Exterior
Color - Morning Gray / Dawn Gray
RAL (Classic) - RAL 7038 / RAL 7037
Protection Device
High Pressure Prevention - High pressure sensor / High pressure switch
Frost Prevention - O (Logical)
Discharge Tempreature Control - O (Logical)
Compressor/Fan Protection - Over-heat protection / Fan driver overload protector
Inverter Protection - Over-heat protection / Over-current protection
Multi V i
1. Specifications
Product Data
1-9
Category
Unit Specification
Major Minor
Refrigerant
Type - R32
Precharged Amount kg 11.4
GWP(Global Warming Potential) - 675
t-CO₂ eq. - 7.695
Control Type - EEV
Connecting Pipe
Liquid mm(inch) Φ12.7 (1/2)
Gas mm(inch) Φ22.2 (7/8)
Low Pressure Gas (Heat Recovery) mm(inch) Φ22.2 (7/8)
High Pressure Gas (Heat Recovery) mm(inch) Φ19.05 (3/4)
Piping Connection Type
Liquid - Brazing
Gas - Brazing
Low Pressure Gas (Heat Recovery) - Brazing
High Pressure Gas (Heat Recovery) - Brazing
Sound Pressure Level (Outdoor Unit) Cooling / Heating dB(A) 60.5 / 61.5
Measurement Standard (Pressure Leve
l) - - ISO 3745
Sound Power Level (Outdoor Unit) Cooling / Heating dB(A) 85.0 / 85.0
Measurement Standard (Power Level) - - ISO 9614
Connecting Cable Communication Cable(VCTF-SB) mm² × cores 0.75 ~ 1.5 x 2C
Electrical Characteristic
Minimium Circuit Amperes (MCA) A 27.3
Maximum Fuse Amperes (MFA) A 32
Total Over Current Amperes (TOCA) A 30.0
Comp_Maximum Starting Current (MSC) A 5.9
Comp_Rated Load Amperes (Cooling) A 22.7
Comp_Rated Load Amperes (Heating) A 14.0
Outdoor Fan Motor_Full Load Amperes (FLA) A 2.5
Connectable indoor units number Max. (Conditional) Units 26(40)
Note
■Due to our policy of innovation some specifications may be changed without notification.
■Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■Power factor could vary less than ±1% according to the operating conditions.
■Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
■EUROVENT Test Condition :
-Performance values on the this PDB are based on Ceiling Mounted Cassette combination.
-Refer to EUROVENT web site (www.eurovent-certification.com) for other indoor unit combination and more detail test conditions.
■Use appropriate power source refer to national standard.
■Voltage supplied to the unit terminals should be within the minimum and maximum range.
■Maximum allowable voltage unbalance between phase is 2%.
■MSC means the Max. current during the starting of compressor.
MSC and RLA are measured as the compressor only test condition.
OFM are measured as the outdoor unit test condition.
TOCA means the total over current value of each outdoor unit.
Select the wire size based on the larger value among MCA or TOCA.
MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].
■Performances are based on the following conditions :
- Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
Multi V i
1. Specifications
Product Data
1-10
ZRUM180LTE6
Category
Unit Specification
Major Minor
Classification
Chassis - UXB
Combination Unit (1) - ZRUM180LTE6
Combination Unit (2) - -
Combination Unit (3) - -
Combination Unit (4) - -
Power Supply
Case 1 V, Phase, Hz 380-400-415, 3, 50
Limit Range of Voltage(Case 1) V 342 ~ 456
Case 2 V, Phase, Hz 380, 3, 60
Limit Range of Voltage(Case 2) V 342 ~ 418
Running Current by Voltage (Cooling,Rated) A 23.51 - 22.34 - 21.53
Running Current by Voltage (Heating,Rated) A 17.30 - 16.44 - 15.84
Cooling Capacity Rated
kW 50.4
Btu/h 172,000
Heating Capacity
Rated
kW 50.4
Btu/h 172,000
Max
kW 56.7
Btu/h 193,500
Power Input(Cooling) Rated kW 14.39
Power Input(Heating) Rated kW 10.59
Efficiency
EER(Rated) W/W 3.50
COP(Rated) W/W 4.76
SEER Wh/Wh 8.65
SCOP Wh/Wh 4.81
Power Factor(Cooling/Heating) Rated - 0.93 / 0.93
Outdoor Fan
Type - Propeller fan
Air Flow Rate(High) m³/min 320
Max. External Static Pressure Pa 80
Discharge direction(Side / Top) - Top
Outdoor Fan Motor
Type - BLDC
Drive - Direct
Output W x No. 900 x 2
Compressor
Type - Hermetically Sealed Scroll
Piston Displacement cm³/rev 62.1 x 2
Number of Revolution rev./min 3,600 x 2
Motor Output W x No. 5,300 x 2
Starting Method - Inverter
Oil Type - FW68L(PVE)
Heat Exchanger
Type - Fin & Tube
No. - 1
Fin Type - Wide Louver Plus
Dimensions
Net(W x H x D) mm 1,240 x 1,745 x 760
Shipping(W x H x D) mm 1,282 x 1,919 x 802
Weight
Net kg 300
Shipping kg 310
Exterior
Color - Morning Gray / Dawn Gray
RAL (Classic) - RAL 7038 / RAL 7037
Protection Device
High Pressure Prevention - High pressure sensor / High pressure switch
Frost Prevention - O (Logical)
Discharge Tempreature Control - O (Logical)
Compressor/Fan Protection - Over-heat protection / Fan driver overload protector
Inverter Protection - Over-heat protection / Over-current protection
Multi V i
1. Specifications
Product Data
1-11
Category
Unit Specification
Major Minor
Refrigerant
Type - R32
Precharged Amount kg 14.0
GWP(Global Warming Potential) - 675
t-CO₂ eq. - 9.450
Control Type - EEV
Connecting Pipe
Liquid mm(inch) Φ12.7 (1/2)
Gas mm(inch) Φ22.2 (7/8)
Low Pressure Gas (Heat Recovery) mm(inch) Φ22.2 (7/8)
High Pressure Gas (Heat Recovery) mm(inch) Φ19.05 (3/4)
Piping Connection Type
Liquid - Brazing
Gas - Brazing
Low Pressure Gas (Heat Recovery) - Brazing
High Pressure Gas (Heat Recovery) - Brazing
Sound Pressure Level (Outdoor Unit) Cooling / Heating dB(A) 61.0 / 62.0
Measurement Standard (Pressure Leve
l) - - ISO 3745
Sound Power Level (Outdoor Unit) Cooling / Heating dB(A) 85.0 / 86.0
Measurement Standard (Power Level) - - ISO 9614
Connecting Cable Communication Cable(VCTF-SB) mm² × cores 0.75 ~ 1.5 x 2C
Electrical Characteristic
Minimium Circuit Amperes (MCA) A 44.8
Maximum Fuse Amperes (MFA) A 50
Total Over Current Amperes (TOCA) A 50.0
Comp_Maximum Starting Current (MSC) A 11.8
Comp_Rated Load Amperes (Cooling) A 21.0
Comp_Rated Load Amperes (Heating) A 14.8
Outdoor Fan Motor_Full Load Amperes (FLA) A 2.5
Connectable indoor units number Max. (Conditional) Units 29(45)
Note
■Due to our policy of innovation some specifications may be changed without notification.
■Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■Power factor could vary less than ±1% according to the operating conditions.
■Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
■EUROVENT Test Condition :
-Performance values on the this PDB are based on Ceiling Mounted Cassette combination.
-Refer to EUROVENT web site (www.eurovent-certification.com) for other indoor unit combination and more detail test conditions.
■Use appropriate power source refer to national standard.
■Voltage supplied to the unit terminals should be within the minimum and maximum range.
■Maximum allowable voltage unbalance between phase is 2%.
■MSC means the Max. current during the starting of compressor.
MSC and RLA are measured as the compressor only test condition.
OFM are measured as the outdoor unit test condition.
TOCA means the total over current value of each outdoor unit.
Select the wire size based on the larger value among MCA or TOCA.
MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].
■Performances are based on the following conditions :
- Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
Multi V i
1. Specifications
Product Data
1-12
ZRUM200LTE6
Category
Unit Specification
Major Minor
Classification
Chassis - UXB
Combination Unit (1) - ZRUM200LTE6
Combination Unit (2) - -
Combination Unit (3) - -
Combination Unit (4) - -
Power Supply
Case 1 V, Phase, Hz 380-400-415, 3, 50
Limit Range of Voltage(Case 1) V 342 ~ 456
Case 2 V, Phase, Hz 380, 3, 60
Limit Range of Voltage(Case 2) V 342 ~ 418
Running Current by Voltage (Cooling,Rated) A 28.65 - 27.22 - 26.24
Running Current by Voltage (Heating,Rated) A 20.66 - 19.62 - 18.91
Cooling Capacity Rated
kW 56.0
Btu/h 191,100
Heating Capacity
Rated
kW 56.0
Btu/h 191,100
Max
kW 63.0
Btu/h 215,000
Power Input(Cooling) Rated kW 17.54
Power Input(Heating) Rated kW 12.64
Efficiency
EER(Rated) W/W 3.19
COP(Rated) W/W 4.43
SEER Wh/Wh 8.42
SCOP Wh/Wh 5.13
Power Factor(Cooling/Heating) Rated - 0.93 / 0.93
Outdoor Fan
Type - Propeller fan
Air Flow Rate(High) m³/min 320
Max. External Static Pressure Pa 80
Discharge direction(Side / Top) - Top
Outdoor Fan Motor
Type - BLDC
Drive - Direct
Output W x No. 900 x 2
Compressor
Type - Hermetically Sealed Scroll
Piston Displacement cm³/rev 62.1 x 2
Number of Revolution rev./min 3,600 x 2
Motor Output W x No. 5,300 x 2
Starting Method - Inverter
Oil Type - FW68L(PVE)
Heat Exchanger
Type - Fin & Tube
No. - 1
Fin Type - Wide Louver Plus
Dimensions
Net(W x H x D) mm 1,240 x 1,745 x 760
Shipping(W x H x D) mm 1,282 x 1,919 x 802
Weight
Net kg 300
Shipping kg 310
Exterior
Color - Morning Gray / Dawn Gray
RAL (Classic) - RAL 7038 / RAL 7037
Protection Device
High Pressure Prevention - High pressure sensor / High pressure switch
Frost Prevention - O (Logical)
Discharge Tempreature Control - O (Logical)
Compressor/Fan Protection - Over-heat protection / Fan driver overload protector
Inverter Protection - Over-heat protection / Over-current protection
Multi V i
1. Specifications
Product Data
1-13
Category
Unit Specification
Major Minor
Refrigerant
Type - R32
Precharged Amount kg 14.0
GWP(Global Warming Potential) - 675
t-CO₂ eq. - 9.450
Control Type - EEV
Connecting Pipe
Liquid mm(inch) Φ12.7 (1/2)
Gas mm(inch) Φ28.58 (1-1/8)
Low Pressure Gas (Heat Recovery) mm(inch) Φ28.58 (1-1/8)
High Pressure Gas (Heat Recovery) mm(inch) Φ22.2 (7/8)
Piping Connection Type
Liquid - Brazing
Gas - Brazing
Low Pressure Gas (Heat Recovery) - Brazing
High Pressure Gas (Heat Recovery) - Brazing
Sound Pressure Level (Outdoor Unit) Cooling / Heating dB(A) 62.0 / 63.5
Measurement Standard (Pressure Leve
l) - - ISO 3745
Sound Power Level (Outdoor Unit) Cooling / Heating dB(A) 86.0 / 89.0
Measurement Standard (Power Level) - - ISO 9614
Connecting Cable Communication Cable(VCTF-SB) mm² × cores 0.75 ~ 1.5 x 2C
Electrical Characteristic
Minimium Circuit Amperes (MCA) A 45.5
Maximum Fuse Amperes (MFA) A 50
Total Over Current Amperes (TOCA) A 50.0
Comp_Maximum Starting Current (MSC) A 11.8
Comp_Rated Load Amperes (Cooling) A 26.2
Comp_Rated Load Amperes (Heating) A 18.2
Outdoor Fan Motor_Full Load Amperes (FLA) A 2.5
Connectable indoor units number Max. (Conditional) Units 32(50)
Note
■Due to our policy of innovation some specifications may be changed without notification.
■Wiring cable size must comply with the applicable local and national codes. And “Electric characteristics” should be considered for electrical work and design.
Especially the power cable and circuit breaker should be selected in accordance with that.
■Power factor could vary less than ±1% according to the operating conditions.
■Sound level values are depend on the ambient conditions and values are normally higher in actual operation.
Sound values of combination model are calculated values based on sound results of independent models.
Sound values can be increased owing to ambient or installation conditions during operation.
Sound values of system [dB(A)] = 10*log [10^(A1/10)+ ... +10^(An/10)] , A1~An means sound values of independent models.
■EUROVENT Test Condition :
-Performance values on the this PDB are based on Ceiling Mounted Cassette combination.
-Refer to EUROVENT web site (www.eurovent-certification.com) for other indoor unit combination and more detail test conditions.
■Use appropriate power source refer to national standard.
■Voltage supplied to the unit terminals should be within the minimum and maximum range.
■Maximum allowable voltage unbalance between phase is 2%.
■MSC means the Max. current during the starting of compressor.
MSC and RLA are measured as the compressor only test condition.
OFM are measured as the outdoor unit test condition.
TOCA means the total over current value of each outdoor unit.
Select the wire size based on the larger value among MCA or TOCA.
MFA is used to select the circuit breaker and ground fault circuit interrupter, and all installation site must require attachment of an earth leakage breaker.
[circuit breaker type is ELCB(Earth Leakage Circuit Breaker)].
■Performances are based on the following conditions :
- Cooling : Indoor Ambient Temp. 27°CDB / 19°CWB, Outdoor Ambient Temp. 35°CDB / 24°CWB
- Heating : Indoor Ambient Temp. 20°CDB / 15°CWB, Outdoor Ambient Temp. 7°CDB / 6°CWB
- Interconnected Pipe Length is 7.5m and difference of Elevation (Outdoor ~ Indoor Unit) is 0m.
Multi V i
1. Specifications
Product Data
1-14

This manual suits for next models

10

Other LG Heat Pump manuals

LG THERMA V Air-to-Water Heat Pump User manual

LG

LG THERMA V Air-to-Water Heat Pump User manual

LG LC098HV4 Installation and operation manual

LG

LG LC098HV4 Installation and operation manual

LG THERMA V User manual

LG

LG THERMA V User manual

LG LC098HV Installation and operation manual

LG

LG LC098HV Installation and operation manual

LG Multi F A2UW14GFA0 Product guide

LG

LG Multi F A2UW14GFA0 Product guide

LG Hydro Kit ARNH30GK1A4 User manual

LG

LG Hydro Kit ARNH30GK1A4 User manual

LG Multi V water mini Series Owner's manual

LG

LG Multi V water mini Series Owner's manual

LG MULTI V ARNH423K3A4 User manual

LG

LG MULTI V ARNH423K3A4 User manual

LG LH247HV Installation and operation manual

LG

LG LH247HV Installation and operation manual

LG THERMA V User manual

LG

LG THERMA V User manual

LG THERMA V DHW Tank Kit User manual

LG

LG THERMA V DHW Tank Kit User manual

LG AH Series THERMA V User manual

LG

LG AH Series THERMA V User manual

LG Therma V ZHBW056A0 User manual

LG

LG Therma V ZHBW056A0 User manual

LG MULTI F Series Installation and operation manual

LG

LG MULTI F Series Installation and operation manual

LG Therma V R32 Gen3 Manual

LG

LG Therma V R32 Gen3 Manual

LG MULTI V S ARUN072BSS5 Installation and operation manual

LG

LG MULTI V S ARUN072BSS5 Installation and operation manual

LG THERMA V User manual

LG

LG THERMA V User manual

LG MULTI F MAX Installation and operation manual

LG

LG MULTI F MAX Installation and operation manual

LG THERMA V AHUW126A3 User manual

LG

LG THERMA V AHUW126A3 User manual

LG 0CVW0-01O User manual

LG

LG 0CVW0-01O User manual

LG THERMA V HN0613T User manual

LG

LG THERMA V HN0613T User manual

LG THERMA V HN1639 User manual

LG

LG THERMA V HN1639 User manual

LG MULTI V S 0CVM0-05A Product guide

LG

LG MULTI V S 0CVM0-05A Product guide

LG ATNW18GTLP1 Product guide

LG

LG ATNW18GTLP1 Product guide

Popular Heat Pump manuals by other brands

Daikin Altherma EHFH-D3V installation manual

Daikin

Daikin Altherma EHFH-D3V installation manual

Nortek GHH09LUA4DH Owner's manual and installation instructions

Nortek

Nortek GHH09LUA4DH Owner's manual and installation instructions

Daikin EWSAH06D 9W Series Installer's reference guide

Daikin

Daikin EWSAH06D 9W Series Installer's reference guide

Garden PAC InverTech GHD-150-0219 Installation and user manual

Garden PAC

Garden PAC InverTech GHD-150-0219 Installation and user manual

EarthLinked SCWD-024-1C Quick start instructions

EarthLinked

EarthLinked SCWD-024-1C Quick start instructions

Rinnai EHP32 Operation and installation guide

Rinnai

Rinnai EHP32 Operation and installation guide

Trane XL Series Weathertron Use and care

Trane

Trane XL Series Weathertron Use and care

Daikin ERGA06EAV3H Installer's reference guide

Daikin

Daikin ERGA06EAV3H Installer's reference guide

ClimateMaster Trilogy VE Series Installation, operation & maintenance instructions

ClimateMaster

ClimateMaster Trilogy VE Series Installation, operation & maintenance instructions

Daikin Altherma 3 H HT EPRA18DAW1 Installer's reference guide

Daikin

Daikin Altherma 3 H HT EPRA18DAW1 Installer's reference guide

Gree GRS-CQ16Pd/NaB-K owner's manual

Gree

Gree GRS-CQ16Pd/NaB-K owner's manual

Green Star BYC-007TH1 Installation & operation manual

Green Star

Green Star BYC-007TH1 Installation & operation manual

Carrier AQUAZONE 50KQL07-19 Product data

Carrier

Carrier AQUAZONE 50KQL07-19 Product data

nilan Compact P user manual

nilan

nilan Compact P user manual

Carrier 48JZ Operating and maintaining guide

Carrier

Carrier 48JZ Operating and maintaining guide

Daikin NHY2KOMB28AA Installer's reference guide

Daikin

Daikin NHY2KOMB28AA Installer's reference guide

Kensa Heat Pumps 7kW Evo Installation and commissioning manual

Kensa Heat Pumps

Kensa Heat Pumps 7kW Evo Installation and commissioning manual

Aquacal Heat Pump installation guide

Aquacal

Aquacal Heat Pump installation guide

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.