Liberty Pumps Ascent II-ESW User manual

Installer: Manual must remain with
owner/operator. Prior to installation, record information from pump
nameplate for future reference:
Model:
7000 Apple Tree Avenue
Bergen, NY 14416
ph: 800-543-2550
fax: 585-494-1839
www.LibertyPumps.com
Keep this manual handy for future reference.
For replacement manual, visit LibertyPumps.com,
or contact Liberty Pumps at 800-543-2550.
Retain dated sales receipt for warranty.
Serial:
Mfg Date:
Install Date:
Installation Manual 5755000K
Copyright © Liberty Pumps, Inc. 2020
All rights reserved.
Models
Ascent II-ESW
Complete System with Elongated Toilet
Ascent II-RSW
Complete System with Round Front Toilet
MaceraWRU&6$&HUWLÀHGDQG,$PMO
/LVWHGWR$60($3DQG&6$%59
Toilet complies with ADA
stDQGDrG,C&$16, $
aQG CSA %6
Toilet ,$PMO ListHG ASM(
$CSA %45
Toilet (3A WaterSHQse
ListHG for gallRQ pe
r
flush (gpf) requiremHQt
s

2 | EN Copyright © Liberty Pumps, Inc. 2020
All rights reserved. 5755000K
Contents
Safety Precautions. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 | EN
Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 | EN
Inspection and Storage. . . . . . . . . . . . . . . . . . . . . . . . . 3 | EN
General Information . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 | EN
Dimensional Data. . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 | EN
Macerating Unit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 | EN
Preparation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 | EN
Installation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8 | EN
Operation. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9 | EN
Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10 | EN
Troubleshooting . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12 | EN
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16 | EN
Safety Guidelines
Safety Precautions
Accidental contact with electrically live parts, items, fluid, or
water can cause serious injury or death.
Always disconnect pump (macerator) from power source
before handling or making any adjustments. Fatal electrical
shock could occur.
The pump shall be plugged into a properly fused electrical
outlet with a ground fault circuit interrupter (GFCI) that
conforms to current National Electric Code (NEC) and all
applicable local codes. All wiring must be performed by
qualified personnel.
All electrical and safety practices shall be in accordance with
the National Electrical Code®, the Occupational Safety and
Health Administration, or applicable local codes and
ordinances.
Pump shall be properly grounded using its supplied
grounding conductor. Do not bypass grounding wires or
remove ground prong from attachment plugs. Failure to
properly ground the pump system can cause all metal
portions of the pump and its surroundings to become
energized.
Do not handle or unplug pump with wet hands, when
standing on a wet/damp surface, or in water. Fatal electrical
shock could occur.
Do not lift or carry the pump by its power cord. This will
damage the power cord, and could expose the electrically live
wires inside the power cord.
The electrical power supply shall be located within the length
limitations of the pump power cord, and for below grade
installations it shall be at least 4 ft (1.22 m) above floor level.
Do not submerge macerator or allow macerator to be
exposed to water. Macerating toilet system is acceptable for
indoor dry location use only. Serious injury or death could
result.
Do not use an extension cord to power the product.
Extension cords can overload boththe product and extension
cord supply wires. Overloaded wires will get very hot and can
catch on fire.
Explosion hazard during installation. PVC cleaners, primers,
and cements can release explosive vapors. These
heavier-than-air vapors can accumulate in the tank. The heat
of soldering or sweating copper or other metal pipe can
ignite these vapors causing a violent explosion. If the unit is
to be connected to copper discharge or vent piping, all
solvent-welded PVC joints must be allowed to cure a
minimum of 24 hours. The access cover must be removed to
allow the tank to be thoroughly ventilated prior to sweating
copper pipe near the unit.
These pumps are not to be installed in locations classified as
hazardous in accordance with the National Electric Code®,
ANSI/NFPA 70.
This safety alert symbol is used in the manual
and on the pump to alert of potential risk for
serious injury or death.
This safety alert symbol identifies risk of
electric shock. It is accompanied with an
instruction intended to minimize potential
risk of electric shock.
This safety alert symbol identifies risk of fire.
It is accompanied with an instruction
intended to minimize potential risk of fire.
This safety alert symbol identifies risk of
serious injury or death. It is accompanied
with an instruction intended to minimize
potential risk of injury or death.
Warns of hazards which, if not avoided, will
result in serious injury or death.
Warns of hazards which, if not avoided, could
result in serious injury or death.
Warns of hazards which, if not avoided, could
result in minor or moderate injury.
Signals an important instruction related to
the pump. Failure to follow these instructions
could result in pump failure or property
damage.
Read every supplied manual before using
pump system. Follow all the safety
instructions in manual(s) and on the pump.
Failure to do so could result in serious injury
or death.
RISK OF ELECTRIC SHOCK
RISK OF FIRE

5755000K Copyright © Liberty Pumps, Inc. 2020
All rights reserved. 3 | EN
Do not modify the pump/pump system in any way.
Modifications may affect seals, change the electrical loading
of the pump, or damage the pump and its components.
All pump/pump system installations shall be in compliance
with all applicable Federal, State, and Local codes and
ordinances.
Do not remove any tags or labels from the pump or its cord.
Keep clear of suction and discharge openings. To prevent
injury, never insert fingers into pump while it is connected to
a power source.
The macerator has a large opening to accept the discharge
hub of a rear discharge toilet. Do not place hand or other
objects into this opening even if unit is unplugged. The
macerator has razor sharp cutters within this opening.
Decorative covers must be installed for operation as a safety
device is integrated into the covers to prevent unintended
operation. The unit may start when energized the first time.
This product contains chemicals known to the State of
California to cause cancer and birth defects or other
reproductive harm. www.p65warnings.ca.gov.
This pump has been evaluated for use with water only.
Wear Protective Personal Equipment to protect hands as
exposed cutter blades have sharp edges.
Do not use pumps with fluid over 104°F (40°C). Operating the
pump in fluid above this temperature can overheat the pump,
resulting in pump failure.
Do not use an air admittance valve or a mechanical
spring-loaded venting device, as these devices are one-way
valves. The air pressure in and outside the macerating pump
unit must be equal and a “cheater” vent will obstruct the
airflow in one direction and prevent proper toilet function.
The Ascent II macerating unit includes electronic controls and
must be protected from direct water exposure during
installation and use.
Sanitary fixtures connected to the macerating system must be
located on the same floor level.
Introduction
Before installation, read the following instructions carefully. Each
Liberty Pumps product is individually factory tested to ensure
proper performance. Closely following these instructions will
eliminate potential operating problems, assuring years of
trouble-free service.
No repair work should be carried out during the warranty period
without prior factory approval. Any unauthorized repairs void
warranty. Contact Liberty Pumps at 1-800-543-2550.
Inspection and Storage
Initial Inspection
The Ascent II Macerating Toilet System is shipped in three
separate packages: the toilet tank, toilet bowl, and macerating
unit. The shipping containers should be immediately inspected for
damage that may have occurred in shipment.
1. Visually check the macerating unit and any spare parts for
damage.
2. Check for damaged electrical wires, especially where they exit
the macerating tank.
3. Check all packaging for spare parts before discarding.
Contact Liberty Pumps customer service to report any damage or
shortage of parts.
List of included parts:
•Toilet Tank (model: Ascent II - TW)
•Toilet Bowl (model: Ascent II – RW or EW)
•Macerator (model: Ascent II - MUW)
–Maceratortank
– Rubber couplings with clamps
– Reducing bushings
– 9V battery
– 3/16” Allen wrench
–Greasepacket
Storage Before Use
Liberty Pumps products are shipped from the factory ready for
installation and use. If storage is necessary, the pump should
remain in its shipping container. It should be stored in a
warehouse or other area that is clean, dry and temperature-stable.
The pump and packaging should be covered to protect it from
water, dirt and dust.
RISK OF SERIOUS INJURY OR DEATH
Ascent II - MUW
(macerating unit) GREASE
Ascent II - EW
(elongated toilet)
Ascent II - RW
(round front toilet)
Ascent II - TW
(toilet tank)

4 | EN Copyright © Liberty Pumps, Inc. 2020
All rights reserved. 5755000K
General Information
The macerator is designed to accept wastewater from a rear
discharge toilet but can also simultaneously receive wastewater
from several sanitary fixtures such as a sink, shower, bathtub, or
urinal (a single bathroom group). However, only one water closet
(toilet) per unit may be connected.
Usage
The macerating system is designed for the disposal of human
waste, toilet paper, and water. It is not intended for kitchen waste,
nor is it intended to be used for the disposal of wastewater from
such pumped appliances as dishwashers and clothes washers. This
product is not designed for emptying large pools or spas.
The macerating system starts automatically once the toilet is
flushed or liquid from other fixtures enters the unit. It
automatically shuts off once the contents have been pumped
away. Run times will vary depending on inflow and source.
Features
•Improved cutter design with RazorCut™ system. The cutter
blades are designed and rigorously tested to last
indefinitely without need for service or replacement in
ordinary applications.
•The CleanConnect™ Seal allows the macerator to sit closer
to the toilet.
•QuickFlip™ discharge and vent connectors allow for
horizontal or vertical pipe connections.
Bath Layout
Sanitary fixtures connected to the macerating system must be
located on the same floor level.
The toilet works as a conventional flushing toilet and needs no
special maintenance with normal use.
Any regular bathtub (up to 100 gallons) or shower can be used.
When installing these fixtures, build a 6 inch high platform for the
fixture to be placed. This provides enough space for a p-trap and
slope toward the macerator auxiliary inlets. When installing a
shower, manufacturers sometimes offer a prefabricated raised
shower base. Note: The actual distance between the p-trap of the
additional fixture and macerator determines the necessary
clearance to install the p-trap and elevation required to ensure a
minimum pitch of 1/4” per foot drop.
Normal Operating Cycle
The macerator controls are capable of distinguishing between
different modes of operation and optimizes the run time
accordingly.
Advanced run detection will energize the cutters once the unit
detects a flush. In doing so, the cutters are spinning at maximum
speed (rpm) prior to fluid and debris reaching the cutting system.
The unit may pulse during a shower or draining a bathtub because
the macerator can pump at a higher rate than the incoming flow.
Use and Care
All standard cleaners can be used just as with a standard
conventional toilet. The exterior of the macerating unit may be
cleaned with a damp cloth and normal household cleaners. Never
spray or dump water or chemicals directly on the unit.
Dimensional Data
ASCENT - ESW
ASCENT - RSW
16-5/16”
[41cm]
16”
[41cm]
30-1/2”
[77cm]
16”
[41cm]
28-1/2”
[72cm]
16-5/16”
[41cm]
13/16”
[2cm]
13/16”
[2cm]
ASCENT - ESW /
RSW
[46cm]
18-3/16”
[51cm]
20”
[18cm]
7”
[25cm]
9-3/4”
[51cm]
20”
[41cm]
16”
[24.8cm]
9-13/16”
[51cm]
20”
[27.8cm]
10-15/16”
[9.1cm]
3-5/8
”
[24.1cm]
9-1/2
”
[23.6cm]
9-5/16
”
[3cm]
1-1/4
”
[17.9cm]
7-1/16
”
MUW

5755000K Copyright © Liberty Pumps, Inc. 2020
All rights reserved. 5 | EN
Macerating Unit
User Interface
The macerator has a user
interface (touchpad with LEDs)
located on the top left side of
the unit.
This interface has three LEDs:
ALARM: unit is unable to
evacuate the holding tank or
cannot keep up with the
incoming flow. Audible alarm
also activates.
LOW BATTERY: 9V battery needs
to be replaced.
POWER: unit has power.
The interface also has two
pushbuttons:
PUSH to Silence: silences the
audible alarm.
PUSH to Run: overrides the
internal switch to manually run
the macerator and pump.
Alarm
The macerator has an integral alarm that will sound if the unit
cannot remove liquid or keep up with incoming water. If the alarm
sounds, a number of conditions could exist. Refer to the
Troubleshooting section to determine the cause and solution.
A silence button located on the user interface touchpad stops the
audible alarm. The red alarm LED will continue to illuminate.
Discontinue using the product until the problem has been
identified and resolved.
IMPORTANT: In the event of a power outage, a 9V battery will
power the alarm, and if necessary, the macerator will accept two
flushes prior to alarm activation. After that, the unit should not be
used again until the power is restored. The alarm automatically
resets once a normal cycle is performed.
Low Battery
If the yellow LED is illuminated, the 9V battery needs to be
replaced. The expected life of the supplied battery is 5 to 7 years.
Power
The LED will be green when power is applied, but LED must be
steady to operate. Both decorative covers must be properly in
place to engage safety switch.
Decorative Covers
The decorative covers are shipped
from the factory assembled on the
unit. However, during the installation
both covers must be removed from
the macerator.
Battery Access
The battery receptacle is accessible
under the left decorative cover. Do not
install battery until the unit has been
installed, connected, and ready for
operation.
Auxiliary Inlets
The macerator unit is equipped with
two inlet ports, one on each side.
These ports are designed for standard
PVC pipe. Included with the system are
two 2” flexible PVC couplers and
1-1/2” reducing bushings. These inlets,
which incorporate an internal check
valve, are used to connect the
drainpipe of other sanitary fixtures to
the macerating pump unit.
Typically, the 2” drain is used with
shower stalls only. A tub, shower/tub
combo, or sink would use a 1-1/2”
drain line. From the factory, the
auxiliary inlets are plugged; if the port
is to be used, the plug must be removed by rotating until the rib is
vertical and then pulling outward. If the unit has been stored for
some time, pliers may be needed to assist in removal.
Access Cover
The macerator has an access cover that
can be removed to gain access to the
pumping and macerating cartridge to
remove debris or perform service. The
auxiliary inlet couplers, Allen wrench,
grease packet, clamps, and 9V battery
are shipped in the access cover
beneath the right access cover.
Preparation
The pump shall be plugged into a properly fused electrical
outlet with a ground fault circuit interrupter (GFCI) that
conforms to current National Electric Code (NEC) and all
applicable local codes. All wiring must be performed by
qualified personnel.
Pump shall be properly grounded using its supplied
grounding conductor. Do not bypass grounding wires or
remove ground prong from attachment plugs. Failure to
properly ground the pump system can cause all metal
portions of the pump and its surroundings to become
energized.
The electrical power supply shall be located within the length
limitations of the pump power cord, and for below grade
installations it shall be at least 4 ft (1.22 m) above floor level.
Replace 9V battery
under this cover
If blinking, decorative
covers not in place
See instructions
under main cover
RISK OF ELECTRIC SHOCK

6 | EN Copyright © Liberty Pumps, Inc. 2020
All rights reserved. 5755000K
Do not use an extension cord to power the product.
Extension cords can overload both the product and extension
cord supply wires. Overloaded wires will get very hot and can
catch on fire.
Explosion hazard during installation. PVC cleaners, primers,
and cements can release explosive vapors. These
heavier-than-air vapors can accumulate in the tank. The heat
of soldering or sweating copper or other metal pipe can
ignite these vapors causing a violent explosion. If the unit is
to be connected to copper discharge or vent piping, all
solvent-welded PVC joints must be allowed to cure a
minimum of 24 hours. The access cover must be removed to
allow the tank to be thoroughly ventilated prior to sweating
copper pipe near the unit.
Do not modify the pump/pump system in any way.
Modifications may affect seals, change the electrical loading
of the pump, or damage the pump and its components.
All pump/pump system installations shall be in compliance
with all applicable Federal, State, and Local codes and
ordinances.
Macerating unit must be located on same floor as connecting
fixtures.
Layout: The bathroom layout should be designed prior to
installation. Make certain the power source (GFCI receptacle) is
within range of the macerator’s 8 ft power cord. The GFCI
receptacle shall be 40 inches away (in a straight line) from a
shower or bathtub. For basement installation, the receptacle shall
be 48 inches from the floor.
Power Cord: The power cord can be configured to exit the unit on
either the left or right side. If the power cord will exit the left side
of the macerator, the vent flange must be removed so the cord
can be routed between the positioning clips. Reinstall vent flange
after routing the cord. Do not use an extension cord. If the
electrical power receptacle (outlet) is in close proximity to the
macerator, any extra power cord can be coiled and tucked away in
the access cover located under the right decorative cover.
Easy Access: The unit should be accessible and removable in the
event of required maintenance. During installation, a full port ball
valve should be installed near the discharge flange to allow easy
service of the unit. If possible, the right side of the macerator
should remain unobstructed. The access cover allows access to
the internal mechanisms. In the event of a jam, the decorative
cover as well as the access cover will need to be removed from the
macerator and working room to do so would be beneficial.
Water Supply: The water supply line for the toilet tank is located
on the left side. When roughing in, allow for the macerator.
Discharge: Never discharge directly into an open drain, fixture,
manhole or rainwater drainpipe. It is illegal, as it constitutes a
health hazard. Only direct connections into sanitary waste systems
shall be acceptable.
Auxiliary Ports: Auxiliary inlet ports are located on either side
toward the back of the macerator tank. These ports can accept
waste from sink or tub/shower. A sink should be plumbed into
one of the auxiliary inlets and not the discharge line of the
macerator even if elevations would allow such an installation. The
discharge line is pressurized and the plumbing system needs to
accommodate this.
Freezing: Ensure all pipework susceptible to freezing is adequately
insulated or heated. In unheated buildings, the toilet, piping, and
macerating unit must be properly winterized. Use plumbing
antifreeze or drain completely. The battery should also be
disconnected.
Discharge Extension: An optional discharge extension [P/N
K001184 sold separately] allows the macerator to be positioned
behind a wall. For example, the macerator could be positioned on
the floor of a linen closet or utility room. Do not fully frame unit
into a wall as access to macerator must be maintained.
Toilet Placement: The toilet hold down fasteners should be
located 16 inches from the wall and spaced 7 inches apart. This
assumes a typical baseboard of 3/4” x 5-1/2” with 3/4” quarter
round. Actual baseboard dimensions must be taken into account
during the installation and thus rough-in dimensions may change.
Tub/Shower: Water height will be 4½ inches in the macerator
tank before the unit starts pumping. A shower stall floor must be
well above this level. Liberty Pumps recommends at least 6–8
inches to ensure proper shower drainage and prevent any
backflow.
Figure 1. Typical Applications
Pipework: All pipework should be copper, PVC, or CPVC. Do not
use flexible piping. Support hangers should not be less than 4 ft
apart to prevent pipe rattling.
Pipe Supports: All sanitary pipework must be supported in
accordance with the pipe manufacturer’s recommendations.
Avoid dipping or trapping, which may cause the buildup of
residual solids and subsequent blockage.
Bends: Wherever possible, long sweeping bends should be used.
Do not use short elbows. If sweeping 90° elbows are not available,
use two 45° elbows to make a 90° turn.
Shut-off Head: The macerator has a shut-off head of 36 ft. All
frictional losses from horizontal runs and elbows need to be
accounted for. The minimum flow rate for 1” PVC Schedule 40
pipe is 5 gal/min compared to 3 gal/min for 3/4” PVC pipe.
RISK OF FIRE
RISK OF SERIOUS INJURY OR DEATH
Tub/shower should be installed on
a riser to accommodate the p-trap.
All fixtures must be properly vented per applicable local plumbing code.

5755000K Copyright © Liberty Pumps, Inc. 2020
All rights reserved. 7 | EN
Gravity Fall: The unit accepts wastewater by gravity; it does not
vacuum in water. All inlet pipework must have a positive gravity
fall (1/4 inch per foot drop minimum).
Vertical Lift: If vertical lift is required, this must precede the
horizontal pipe run. All vertical lifts should rise as close to the
macerator as possible, allowing only for the need to clear the
toilet tank. The initial horizontal run should not exceed 12 inches.
Once the horizontal run is started, do not change directions in a
vertical manner.
Discharge: All discharge piping from the unit should run either
directly vertical or in a horizontal plane (with a minimum 1/4 inch
per foot drop) to the point of discharge. Pipework must not be
installed with a diagonal upward slope from the unit to the point
of discharge. Long downward pitched runs of discharge piping, or
piping where the point of discharge is at a lower elevation than
the macerator unit, should be designed to prevent siphoning from
the macerator tank.
Friction: Friction losses from horizontal runs without 1/4 inch per
foot pitch will reduce the amount of vertical lift the system is
capable of handling. Refer to Figure 3. Consult factory for proper
sizing if there are long runs or multiple elbows.
Lift Calculations: To pump vertically and horizontally, calculate
3 ft of vertical lift as equivalent to 30 ft of horizontal run. Each
bend or change of direction gives a pressure drop, which must be
calculated into the total head of the unit. As an estimate, reduce
discharge height by 3 ft for each 90° bend.
For example: 1” Schedule 40
PVC pipe is used for the
discharge and runs
horizontally for 1 ft, then
turns 90°, and rises 5 ft
vertical. Then it travels
horizontal with another 90°
turn (3 turns in total) and
connects with the soil-stack.
Refer to Figure 2.
Calculations:
[A] Total vertical lift 5 ft= 5 ft
vertical
[C+D+E] Total horizontal run
43 ft = 4.3 ft vertical
[B] Total of three 90° elbows
= 9 ft vertical
Add the three calculation
totals together to get 18.3 ft
ofvertical head (lift).Referring
to Figure 3, the application
would result in a flow rate of
23 gal/min (60 Hz).
Figure 2. Example Calculations
Figure 3. Performance Curve
Macerating Unit Preparation
Auxiliary inlets should be plumbed using the supplied auxiliary
inlet couplings and/or reducing bushing when connecting to
either 2” or 1-1/2” standard Schedule 40 PVC pipe. A plug must be
removed by turning until the rib is vertical and pulling outward.
Pliers may be required if unit has been stored.
Both the discharge and vent flanges are shipped from the factory
in the horizontal orientation. If the installation allows for a vertical
orientation, the four screws must be removed from each in order
to flip the flange. The decorative cover will need to be modified
with the use of a hole saw and cutters to remove material. A
template is provided on the underside of the decorative cover.
1 ft
[30.5cm]
5 ft
[1.5m]
30 ft
[9.1m]
12 ft
[3.7m]
[E]
[B]
[B]
[B]
[D]
[A]
[C]
0 5 10 15 20 25 30 35 40 45
0
5
10
15
20
25
30
35
40
0
1.5
3.0
4.6
6.1
7.6
9.1
10.7
12.2
37.9 56.818.90 75.7 94.6 113.6 132.5 151.4 170.3
US Gallons Per Minute
Total Head in Feet
Liters Per Minute
Total Head in Meters
50 Hz
60 Hz
Discharge flange
PVC solvent
weld
1” schedule
40 PVC pipe
Vent flange
PVC
solvent weld
1-1/2” schedule
40 PVC pipe
Discharge and vent
flanges
in horizontal orientation
Discharge and vent flanges
in vertical
orientation

8 | EN Copyright © Liberty Pumps, Inc. 2020
All rights reserved. 5755000K
Installation
The pump shall be plugged into a properly fused electrical
outlet with a ground fault circuit interrupter (GFCI) that
conforms to current National Electric Code (NEC) and all
applicable local codes. All wiring must be performed by
qualified personnel.
All electrical and safety practices shall be in accordance with
the National Electrical Code®, the Occupational Safety and
Health Administration, or applicable local codes and
ordinances.
Pump shall be properly grounded using its supplied
grounding conductor. Do not bypass grounding wires or
remove ground prong from attachment plugs. Failure to
properly ground the pump system can cause all metal
portions of the pump and its surroundings to become
energized.
Note to Installer: During installation, it is best to cover the
macerating unit with plastic to protect it from potential leaks at
the toilet fill connection or tank to bowl gasket.
Refer to Figure 1 Typical Applications as needed during the
installation process. Installations may vary per local plumbing and
electrical codes. Also, discharge and vent pipe routing can vary
per installation.
1. Place the macerator in the desired location and connect all
inlet and outlet waste piping to the unit. The inlet side should
be facing the toilet to ensure proper placement. Refer to
Figure 4 and Figure 5.
2. Assemble the toilet in accordance with the installation
manual(s) provided with it. Be careful when tightening
fasteners as to not crack the porcelain.
Figure 4. Placement Options
Figure 5. Toilet Connections
1. To mount the toilet to a concrete floor, drill two holes
approximately 2-1/4” deep with a 5/16” masonry drill bit.
Insert plastic plugs into holes. If the floor is wood, bore a pilot
hole with a 1/4” drill bit. Fasteners not included.
2. Toilet to macerator connection:
a. Standard Installation:
Place the toilet in front of the
macerating tank and apply
silicone grease (supplied) to the
rubber sealing lip of macerator.
Then slide the discharge hub of
the toilet into the rubber
sealing ring of the macerator.
b. Behind Wall Installation:
To install the macerator behind a wall, an Extension Pipe Kit
(K001184, sold separately) is needed. Included in the kit
are an 18-3/4” long extension pipe, a decorative trim ring,
and a grease packet. Rubber rings seal both ends of the
extension pipe.
To prevent tearing, always grease both seals prior to
installing the pipe. Slip the decorative trim ring onto the
pipe. To install the pipe, no fasteners are required. Slip the
extension pipe over the toilet discharge, and then insert
the pipe into the macerator.
Liberty Pumps recommends using only one extension pipe.
RISK OF ELECTRIC SHOCK
Standard Installation
Behind Wall Installatio
n
Option
al 18”
Ext
ension Pipe
#K001
184
Water Supply
Connector
Water
Supply
Valve
Toilet Tank
Fitting
Allow sufficient
clearance for
water supply line
to route around
macerating tank
[25cm]
10”
Centerline to
edge of tank
[9cm]
3-1/2”
Centerline to
mounting bolt [x2]
[34cm]
13-1/2”
[25cm]
10”
[30cm]
11-3/4”
Apply grease to
rubber ring

5755000K Copyright © Liberty Pumps, Inc. 2020
All rights reserved. 9 | EN
3. Place the toilet over the holes in the floor. Slip the plastic
china protectors over the lag screws ensuring proper
orientation. Tighten lag screws (do not overtighten) and snap
plastic caps in place.
For proper flushing performance, ensure that the base of the
toilet is not below the base of the macerator. Check the
extension pipe, if applicable, with a level, and verify that the
pipe is either level or sloped toward the macerator unit and
away from the toilet.
4. Connect the water supply line to the fill valve, located directly
below the flush lever, on the bottom of the toilet tank.
Connection to the Discharge and Vent Flanges
To finish the installation, fasten the toilet to the floor and secure
the macerator discharge and vent piping.
Do not use an air admittance valve or a mechanical
spring-loaded venting device, as these devices are one-way
valves. The air pressure in and outside the macerating pump
unit must be equal and a “cheater” vent will obstruct the
airflow in one direction and prevent proper toilet function.
Discharge Flange
The macerator has a PVC discharge flange with an integrated
check valve that can be configured in a horizontal or vertical
orientation. Standard 1” Schedule 40 PVC pipe can be solvent
welded directly to the flange.
Excessive amounts of glue should be avoided. The check valve can
be removed from the flange if required.
A full port ball or gate valve and a union should be installed in the
discharge pipe to facilitate the removal of the macerator or to
perform maintenance. Additionally, a drain off point is
recommended to allow the discharge piping to be drained.
Vent Flange
The macerator is equipped with a PVC vent flange, which can be
configured in a horizontal or vertical orientation. Standard 1-1/2”
Schedule 40 PVC pipe can be solvent welded directly into the
flange.
The macerator must be vented to allow for proper toilet flush
performance. Depending on the installation, the product should
either be connected to the stack vent of the dwelling or vented
(plumbed) directly outside. Vent in accordance with applicable
plumbing codes.
The macerator is not designed to support the discharge and vent
piping; proper pipe supports are required.
Connection to the Soil-stack or Sewer
The discharge piping can be made from 3/4” or 1” diameter PVC
pipe. Use long turn bends and avoid elbows where possible. The
connection to the soil-stack or sewer pipe must be made with an
approved connection, such as a T or Y fitting.
Operation
Decorative covers must be installed for operation as a safety
device is integrated into the covers to prevent unintended
operation. The unit may start when energized the first time.
The macerating system is designed for human waste and
toilet paper. Do not dispose of acids, alkalis, solvents, oils,
paint, paint strippers, food waste, and cotton swabs.
Off-the-shelf toilet cleansers will normally not hurt the
macerating unit.
During cleaning or when using a plunger, the macerator
could turn on.
Do not hang bleach blocks or hypochlorite cleaners in the
toilet tank. These solutions have been shown to deteriorate
the plastic and neoprene components of the flush and fill
valves, and may cause leaks.
In the event of a power loss, the toilet can be used twice. Use
of sanitary fixtures such as a sink should be limited. Do not
use shower or tub as the macerating unit will fail to pump
until the power is restored.
1. Ensure that the toilet and tank have been assembled per
instructions provided with the toilet tank.
2. Ensure any full port ball or gate valve in the discharge line is
in the open (full flow) position.
3. Open the shut-off valve and let the toilet tank completely fill.
Look for leaks at connections and verify that the toilet fill
valve float and the flush valve operate freely.
4. Ensure the macerating unit has both decorative covers
installed and is plugged in with the power supply turned on.
The green POWER LED should be illuminated steady.
a. If the green LED is blinking, confirm the decorative covers
are properly seated.
5. Battery: Battery must be
installed after the
macerator is connected to
the AC power supply.
If battery was
inadvertently installed
before power was applied:
a. unplug the macerator
from power source
b. remove the 9V battery
c. plug the macerator
back into the power
source
d. reinstall the 9V battery
6. Deposit a few sheets of toilet paper into the bowl and flush
the toilet. There should be no paper remaining in the bowl
after the flush. Repeat several times.
The unit will turn on shortly after the toilet is flushed or when
water depth is achieved. The duration of operation will differ
depending upon the installation. The macerator may not run
immediately on sink usage.
RISK OF SERIOUS INJURY OR DEATH

10 | EN Copyright © Liberty Pumps, Inc. 2020
All rights reserved. 5755000K
Maintenance
Always disconnect pump (macerator) from power source
before handling or making any adjustments. Fatal electrical
shock could occur.
The macerator is designed such that every component can easily
be serviced or replaced as necessary. Replacement parts can be
ordered at www.LibertyPumps.com/Service/Replacement-Parts/.
The macerator is designed with a removable access cover, making
the unit serviceable without removing the macerating unit from
the toilet or disconnecting any plumbing.
Cleaning
All standard cleaners can be used just as with a standard
conventional toilet. The exterior of the macerating unit may be
cleaned with a damp cloth and normal household cleaners. Never
spray or dump water or chemicals directly on the unit.
Decorative Covers
The right cover can be removed by pulling it horizontally away
from the macerator and then lifting vertically. The left cover is
secured and positioned by two mating posts on the main cover.
Discharge and Vent Flanges
Both the discharge and vent
flanges are fastened to the main
cover and can be removed by
unscrewing the four fasteners
and pulling the flange away from
the main cover.
Toilet Sealing Ring
The seal between the toilet and
the macerator consists of a rubber
ring connected to the macerator
into which the toilet slides. The
rubber ring stretches and forms a
seal around the discharge hub of
the toilet. This rubber ring is
replaceable by unclipping the
plastic retainer and then pulling
the ring outward. Installation is
reversed, first slide the rubber ring
onto the macerator, followed by
the retaining ring.
Check Valve
The discharge flange has an integrated check valve. The valve is
held in place by a support backing plate that is also connected to
the discharge hose. To access the check valve, first remove the
discharge flange from the main cover by removing 4 screws. Then
remove the hose, followed by the two screws. The hose nipple can
then be separated from the flange by pulling it outward. The
check valve snaps onto the hose nipple.
When reinstalling, the hinge of the check valve must be aligned
with the “notch” in the hose nipple or backing plate. After
installation of the hose nipple, confirm the check valve opens
completely.
Access Cover
The access cover is secured to the main cover with five fasteners. If
required, use the 3/16” Allen wrench supplied to loosen the
fasteners. Once the screws have been removed, the access cover
can be lifted upward. Some manipulation might be necessary if
the macerator is located directly under the toilet reservoir tank.
Once the access cover is removed, the power cartridge can be slid
toward the opening by grasping the handle of the basket and
pulling to the right toward the opening. In some instances, debris
might be caught between the tank and the basket so some
manipulation might be required.
With the power cartridge fully slid over, the cutters should be in
view at the center of the basket. Any obstruction or object can be
removed at this point. The cutters are very sharp and extreme
caution should be used.
Interconnect Hose
A hose connects the discharge of the motor cartridge (pump) to
the discharge flange. To remove this hose, follow the procedure
Discharge and Vent Flanges and Accessibility to Motorized
Cartridge. Both ends of the hose are secured with clamps.
RISK OF ELECTRIC SHOCK
The hinge of the
check valve must
be aligned with
the notch in the
hose nipple.
Once the access cover is removed,
pull the power cartridge towards
opening

5755000K Copyright © Liberty Pumps, Inc. 2020
All rights reserved. 11 | EN
Cutter Blade Replacement
Wear Protective Personal Equipment to protect hands as
exposed cutter blades have sharp edges.
The cutter blades are designed and rigorously tested to last
indefinitely without need for service or replacement in ordinary
applications. In the unlikely event that the cutter blades need
replacement, Liberty Pumps recommends replacement kit
# K001370 (440A Stainless Steel Cutter Blades hardened to
Rockwell 54c) available from http://www.libertypumps.com/
Services/Replacement-Parts or equivalent substitute.
To replace the cutter blades, the 3/16” Allen wrench (supplied)
should be inserted into one of the holes located on the basket
floor. This will create a wedge preventing the cutter blade
assembly from turning. The locking fastener can be unscrewed
with the use of a 7/16” socket (1/4” drive). Once loose, the screw
and cap can be removed by pulling upward, exposing the two
cutter blades. Carefully insert the new cutter blade onto the two
pins. Replace the cap and screw.
The base of the cutting cartridge can be replaced as well. After
removing the cutter blades, a thin slotted screwdriver can be
inserted into the center hole and, once engaged, the base can be
rotated counterclockwise until it is free.
Accessibility to Motorized Cartridge
The motorized cartridge can be accessed through the access
opening or removal of the main cover.
Removal of Power Cartridge Through the Access Opening:
Once the access cover has been removed and the basket is slid
toward the opening, the four fasteners securing the basket can be
unscrewed. The basket can then be removed through the opening
followed by the power cartridge.
Removal of Power Cartridge by Disassembly of Macerator: If a
full port ball valve was installed in the discharge line, it should be
closed to eliminate the possibility of waste discharging from the
discharge pipe. Next, the discharge and vent flanges should be
separated from the main cover by removing 4 screws from each.
The main cover can then be detached from the tank by removing
the fasteners on the periphery of the tank. The main cover can
then be lifted upward exposing the power cartridge.
Power Cord: The inner connecting power cord running from the
switch box to the motorized cartridge can be detached by
unscrewing the compression nut located at the motorized
cartridge.
To remove cap,
unscrew fastener
Place Allen wrench
in hole to prevent
cutter from turning
Screw
Cap
Cutter
Blade
Base
Wear Protective
Personal Equipment
to protect hands as
exposed cutter
blades have sharp
edges.
CAUTION
Power Cord
Disconnect

12 | EN Copyright © Liberty Pumps, Inc. 2020
All rights reserved. 5755000K
Impeller Access
Once the bottom of the
motorized cartridge is
accessible, the fasteners
retaining the volute can be
removed and the volute
separated by pulling it away. The
impeller chamber can now be
cleaned if required, or the
impeller can be replaced.
Note: the impeller has a
left-handed thread. To remove,
use a slotted screwdriver to hold
the shaft and turn the impeller
clockwise.
Control Switch
The control switch
cartridge is mounted to
the main cover with
fasteners. The control has
two power cords; first is
the main power cord that
plugs into the GFCI
receptacle and the other
powers the motorized
cartridge. The motorized
cartridge must be
removed to disconnect
this cord. Refer to
Accessibility to
Motorized Cartridge for
details.
Troubleshooting
Liberty Pumps, Inc. assumes no responsibility for damage or injury
due to disassembly in the field. Disassembly, other than at Liberty
Pumps or its authorized service centers, automatically voids
warranty.
In addition to the Alarm Panel Help in Table 1 and the
Troubleshooting Matrix in Table 2, verify the following:
Plumbing System
Flush toilet and ensure water supply is turned on.
Electrical System
Ensure breaker and receptacle GFCI are on. Check condition of
circuit breaker or fuse. Ensure plug is not loose. If the pumping
unit thermal overload has activated, it will take about 20 minutes
to reset.
Decorative Covers
Ensure decorative covers are installed and fully seated such that
safety switch is activated. The green LED is solid when safety
switch is properly activated.
Hydraulic System
Check that the discharge pipe and vent pipe are not blocked.
Water Leakage
If the macerating pump turns on intermittently without flushing
the toilet or collecting water drainage from sink, shower, or tub,
check for leakage from the toilet tank flush valve.
Impeller has
a left-handed thread
(counterclockwise to
tighten)
Table 1. Alarm Panel Help
Label
LED Color/State Condition Corrective Action
ALARM
Red/Blinking Water is not being evacuated from
holding tank. 1. Verify unit is plugged into outlet.
2. Verify Green LED is steady, indicating normal operating
condition.
3. Check discharge line for blockage.
4. If items 1-3 do not remedy the alarm condition, refer to Table 2
Troubleshooting Matrix.
LOW BATTERY
Yellow/Steady Battery is missing, defective, or needs to
be replaced. 1. Replace with new battery.
POWER
Green/Steady Normal operating condition.
POWER
Green/Blinking Safety switch condition (no signal from
safety switch; unit will not operate). 1. Verify decorative covers in place.
2. Verify magnet in place on underside of decorative cover.
3. Safety switch is broken; consult factory.

5755000K Copyright © Liberty Pumps, Inc. 2020
All rights reserved. 13 | EN
Accidental contact with electrically live parts, items, fluid, or
water can cause serious injury or death.
Always disconnect pump (macerator) from power source
before handling or making any adjustments. Fatal electrical
shock could occur.
RISK OF ELECTRIC SHOCK
Table 2. Troubleshooting Matrix
Problem Possible Cause Corrective Action
Water is entering the macerator holding tank slowly
Toilet flushes normally but
evacuates or drains from the bowl
slowly.
• Macerator sounds normal and
runs for 4 seconds, then after
some time runs for 4 seconds.
•Noalarm.
The toilet or discharge extension might be
blocked. The piping must be cleaned.
Poor vent. Unit must be vented properly to open air to allow
water to enter the macerator tank. Confirm vent is
clear.
Do not use a quick vent.
Accumulation in the strainer basket. Repetitively flush clean water and allow the
macerator to clear debris. If unit is unable to
self-clear the blockage, the access cover should
be removed for manual cleaning. See Access
Cover on page 10.
Water is unable to enter the macerator holding tank
Toilet flushes normally but does not
evacuate or drain from the bowl.
• Macerator sounds normal and
runs for 4 seconds then remains
off.
•Noalarm.
The toilet discharge or extension pipe may
be blocked. The piping must be cleaned.
Unit not vented correctly. Unit must be vented properly to open air to allow
water to enter the macerator tank. Confirm vent is
clear.
Do not use a quick vent.
The macerator is jammed
Toilet Flushes normally but
macerator does not turn on or just
hums.
• Green LED is on steady.
The cutter or impeller are jammed
preventing the motor from turning. Clear the cutter or impeller of blockage.
Internal motor problem. The pump cartridge must be replaced.
The macerator is unable to evacuate its holding tank and is cycling on thermal overload
Toilet flushes normally but does not
evacuate or drain from the bowl.
• Macerator starts to run and
sounds normal (running) then
stops after 5-10 min. Restarts
after 30 to 60 min.
• Alarm is activated.
Damaged impeller. Replace impeller. See Impeller Access on
page 12.
Check valve stuck closed. Confirm the check valve is functioning properly; if
not, repair or replace. See Check Valve on
page 10.
Internal hose damaged or disconnected. Confirm the internal hose is functioning properly;
if not, replace. See Control Switch on page 12.
If the macerator was installed with a ball
valve in the discharge line, valve may be
closed.
Open ball valve.
Air lock. The volute has a passageway to allow trapped air
to escape. This passageway must be cleaned of
obstruction. See Accessibility to Motorized
Cartridge on page 11.
Volute inlet plugged. Clean volute inlet, located on the bottom of the
pump cartridge. See Accessibility to Motorized
Cartridge on page 11.

14 | EN Copyright © Liberty Pumps, Inc. 2020
All rights reserved. 5755000K
The macerator has electrical power, safety switch is off
The macerator does not start up
(the macerator has electrical power,
safety switch is off).
• Green LED is blinking.
Decorative cover not installed. Both halves of the decorative cover must be
installed and fitted properly on the unit. See
Check Valve on page 10.
The right decorative cover (over the access
cover) should have a magnet located on a
post. This magnet activates a safety switch.
Replace magnet or entire right decorative cover.
See Check Valve on page 10.
The toilet has an inadequate flush volume, possible blockage of the strainer basket, or improper venting
Waste build up in the toilet bowl. Inadequate water level in the reservoir tank. Check and/or adjust the water fill mechanism so
that the water level matches the reference line in
the tank.
Strainer basket requires cleaning. Clear debris from the strainer basket. See
Accessibility to Motorized Cartridge on
page 11.
Unit not vented correctly. Unit must be vented properly to open air to allow
water to enter the macerator tank. Confirm vent is
clear.
Do not use a quick vent.
No electrical power or battery protection mode
The macerator has no LEDs
illuminated when power is
connected (no electrical power or
battery protection mode).
• All LEDs are off.
The macerator is either not plugged in,
supply breaker is turned off, or GFCI
receptacle has tripped.
Check electrical power source.
Control system in battery protection mode. 1. Unplug macerator from receptacle.
2. Remove the 9V battery that powers the alarm.
3. Plug the macerator back into the receptacle.
4. Re-install the 9V battery.
No electrical power
The macerator does not start up.
• Green LED is off. The macerator is either not plugged in,
supply breaker is turned off, or GFCI
receptacle has tripped.
Check electrical power source.
Solid debris in basket
During a pumping cycle, a rattling
noise is emanating from the
macerator.
Solid object larger than 1/2” is trapped in
the cutting basket of the macerator. The access cover should be removed for manual
cleaning. See Access Cover on page 10.
Pump is unable to evacuate tank
Alarm sounds frequently (pump
unable to evacuate tank). Damaged impeller. Replace impeller. See Impeller Access on
page 12.
Volute inlet clogged. Clean volute inlet. See Accessibility to Motorized
Cartridge on page 11.
Internal hose damaged. Confirm the internal hose is functioning properly;
if not, replace. See Control Switch on page 12.
Air lock. The volute has a passageway to allow trapped air
to escape. This passageway must be cleaned of
obstruction. See Accessibility to Motorized
Cartridge on page 11.
Application. The pumping capacity has been exceeded by the
rate of incoming water. Either reduce flow coming
into the macerator or reduce the pumping head.
Table 2. Troubleshooting Matrix (continued)
Problem Possible Cause Corrective Action

5755000K Copyright © Liberty Pumps, Inc. 2020
All rights reserved. 15 | EN
General plumbing
The macerator pulses for no
apparent reason. Water leakage from the toilet reservoir. Check flush valve and related components in the
reservoir tank.
Check valve failure of the macerator. The discharge flange contains a check valve that
requires cleaning or replacement. See Check
Valve on page 10.
General plumbing
Water backs up into shower tray.
• Alarm is not activated. Blockage or inadequate slope of pipe. Clear blockage in piping, or increase pitch of
discharge pipe. Typically ¼” drop per foot is
adequate for a gravity drain.
The inlet flappers of the macerator are not
functioning. Clear any buildup in the macerator holding tank
that is preventing the flappers from opening. See
Accessibility to Motorized Cartridge on
page 11.
General plumbing
Macerator is noisy when running. Rattling piping. Both the discharge and vent plumbing should be
secured using appropriate pipe clamping.
Foreign object in cutter basket. The access cover should be removed for manual
cleaning. See Access Cover on page 10.
General plumbing
During the draining of the bathtub,
the alarm sounds and/or water
backs up into the toilet.
The inflow is greater than the macerator
can handle. A full port ball valve should be installed between
the tub and macerator. Throttle down or partially
close the ball valve until the macerator can handle
the drainage rate from the tub.
System is backing up
Water backs up into shower tray.
• Alarm is activated. Damaged impeller. Replace impeller. See Impeller Access on
page 12.
Volute inlet clogged. Clean volute inlet. See Accessibility to Motorized
Cartridge on page 11.
Internal hose damaged. Confirm the internal hose is functioning properly;
if not, replace. See Control Switch on page 12.
Air lock. The volute has a passageway to allow trapped air
to escape, this passageway must be cleaned of
obstruction. See Accessibility to Motorized
Cartridge on page 11.
Incoming flow rate is greater than pump
capacity. The unit is capable of handling up to two shower
heads—multiple (3 and up) shower heads must
be avoided.
Check valve failure of the macerator. The discharge flange contains a check valve that
either requires cleaning or replacement. See
Check Valve on page 10.
Table 2. Troubleshooting Matrix (continued)
Problem Possible Cause Corrective Action

16 | EN Copyright © Liberty Pumps, Inc. 2020
All rights reserved. 5755000K
Warranty
Liberty Pumps Wholesale Products Limited Warranty
Liberty Pumps, Inc. warrants that Liberty Pumps wholesale products are free from all factory defects in material and workmanship for a
period of three (3) years from the date of purchase (excluding batteries). The date of purchase shall be determined by a dated sales
receipt noting the model and serial number of the pump. The dated sales receipt must accompany the returned pump if the date of
return is more than three years from the date of manufacture noted on the pump nameplate.
The manufacturer's sole obligation under this Warranty shall be limited to the repair or replacement of any parts found by the
manufacturer to be defective, provided the part or assembly is returned freight prepaid to the manufacturer or its authorized service
center, and provided that none of the following warranty-voiding characteristics are evident:
The manufacturer shall not be liable under this Warranty if the product has not been properly installed, operated, or maintained per
manufacturer instructions; if it has been disassembled, modified, abused, or tampered with; if the electrical cord has been cut, damaged,
or spliced; if the pump discharge has been reduced in size; if the pump has been used in water temperatures above the advertised rating;
if the pump has been used in water containing sand, lime, cement, gravel, or other abrasives; if the product has been used to pump
chemicals, grease, or hydrocarbons; if a non-submersible motor has been subjected to moisture; or if the label bearing the model and
serial number has been removed.
Liberty Pumps, Inc. shall not be liable for any loss, damage, or expenses resulting from installation or use of its products, or for indirect,
incidental, and consequential damages, including costs of removal, reinstallation or transportation.
There is no other express warranty. All implied warranties, including those of merchantability and fitness for a particular purpose, are
limited to three years from the date of purchase. This Warranty contains the exclusive remedy of the purchaser, and, where
permitted, liability for consequential or incidental damages under any and all warranties are excluded.
7000 Apple Tree Avenue
Bergen, NY 14416
ph: 800-543-2550
fax: 585-494-1839
www.LibertyPumps.com
Other manuals for Ascent II-ESW
1
This manual suits for next models
1
Table of contents
Other Liberty Pumps Toilet manuals
Popular Toilet manuals by other brands

American Standard
American Standard Cadet 270AA Series INSTALLATION INSTRUCTIONS CARE AND MAINTENANCE

YANXUAN
YANXUAN YX-ETS001 installation manual

DURAVIT
DURAVIT Rimless ME by Starck Dry 2814300000 Mounting instructions

BEMIS
BEMIS bioBidet SLIM ONE owner's manual

Sanela
Sanela 94110 Mounting instructions

Glacier bay
Glacier bay N2420E-SF Use and care guide