Page 6 of 11
SR517 ARCHITECTURAL CONTROLLER
Version 1.0 OWNER’S MANUAL 10/3/2023
www.lightronics.com
Lightronics Inc. 509 Central Drive, Virginia Beach, VA 23454 757 486 3588
17 Bank A, Scene 7 Fade Time
18 Bank A, Scene 8 Fade Time
21 Bank B, Scene 1 Fade Time
22 Bank B, Scene 2 Fade Time
23 Bank B, Scene 3 Fade Time
24 Bank B, Scene 4 Fade Time
25 Bank B, Scene 5 Fade Time
26 Bank B, Scene 6 Fade Time
27 Bank B, Scene 7 Fade Time
28 Bank B, Scene 8 Fade Time
31 Blackout (OFF) Fade Time
32 ALL Scenes and Blackout Fade Time
33 Simple Switch Input #1 Options
34 Simple Switch Input #2 Options
35 Simple Switch Input #3 Options
36 Not Used
37 System Configuration Options 1
38 System Configuration Options 2
41 Mutually Exclusive Group #1 Scenes
42 Mutually Exclusive Group #2 Scenes
43 Mutually Exclusive Group #3 Scenes
44 Mutually Exclusive Group #4 Scenes
88 DMX Fixed Channel Recording (Parking)
and Factory Reset
RECORD BUTTON
This is a small recessed pushbutton in a small hole in
the faceplate. It is just below the RECORD LED
(labeled REC). You will need a small rod (such as a
pen or paper clip) to push it.
ACCESSING AND SETTING FUNCTIONS
1. Hold down REC for more than 3 seconds. The
REC light will begin blinking. The unit will return to
its normal operating mode after about 20 seconds
if step 2 is not performed.
2. Push RECALL. The RECALL and REC lights will
blink alternately.
3. Enter a 2 digit function code using the scene
buttons (1 - 8). The scene lights will flash a
repeating pattern of the code entered. The unit
will return to its normal operating mode after about
20 seconds if no code is entered. The unit will
return to its normal operating mode after about
60 seconds if a code is entered but step 4 is not
performed.
4. Push RECALL. Both the RECALL and REC lights
will be ON. The scene lights (in some cases
including the OFF (0) and BANK (9) lights) will
show the current function setting or value.
Your action now depends on which function was
entered. Refer to the instructions for that function.
You can enter new values and push REC to save
them or push RECALL to exit without changing the
values.
SETTING FADE TIMES (Function Codes 11 - 32)
The fade time is the minutes or seconds to move
between scenes or for scenes to go ON or OFF. The
fade time for each scene can be individually set. The
allowable range is from 0 seconds to 99 minutes.
Fade time is entered as 4 digits and can be either
minutes or seconds.
Numbers entered from 0000 - 0099 will be recorded
as seconds.
Numbers 0100 and larger will be recorded as even
minutes and the last two digits will not be used. In
other words, seconds will be ignored.
After accessing a function (11 - 32) as described in
ACCESSING AND SETTING FUNCTIONS:
1. The scene lights + OFF (0) and BANK (9) lights will
be flashing a repeating pattern of the current fade
time setting.
2. Use the scene buttons to enter a new fade time (4
digits). Use OFF for (0) and BANK for (9) if
needed.
3. Push REC to save the new function setting.
Function Code 32 is a master fade time function which
will set ALL fade times to the value entered. You can
use this for a base setting for fade times and then set
individual scenes to other times as needed.
SIMPLE REMOTE SWITCH BEHAVIOR
The SR517 is very versatile in how it can respond to
the simple remote switch inputs. Each switch input
can be set to operate according to its own settings.
Most settings pertain to momentary switch closures.
The MAINTAIN setting allows the use of a regular
ON/OFF switch. When used this way, the applicable
scene(s) will be ON while the switch is closed and
OFF when the switch is open.
Other scenes can still be activated and the
OFF/Blackout function button will turn the MAINTAIN
scene OFF.