R-Hot Wire; one side of the control (20 - 30 VAC)
transformer. If two hot wires are present (as with RC and RH)
determine if they come from separate transformers. The e-Stat™
must be installed on a single transformer
system.
G - Fan Wire.
W1 - First stage of heating.
Y1 -First stage of cooling.
When conventional rooftop equipment is selected, the interstage
differential is always 1.5°F. With heat pump switch #1 set to “ON”,
the interstage differential is 3.0°F for heating stages and 1.5°F for
cooling stages. (If using a humidity sensor, interstage differential
will increase during cooling to compensate for high humidity
conditions.)
C - Common or Neutral side of transformer. This must be
connected for the e-Stat™to operate.
W2 -Second stage of Heat or Auxiliary heat with heat pumps.
Y2 - Second stage of cooling.
O- This output will be active with a call for cooling.
Often used for heat pump reversing valve.
B- This output will be active with a call for heating.
(Connect O & B outputs as required by the HVAC equipment.)
Note: When connecting to a heat pump with Thermostat
Reversing Valve Control you will need to install a jumper
wire between W1 and Y1 at the e-Stat™. There should be no
connection between W1 on the e-Stat™ and the RTU terminal
strip. Aux heat is connected to W2.
Note: When connecting to a heat pump with Unit Reversing
Valve Control no jumper wire is required as the reversing valve is
positioned by the unit internal controls based on whether cooling
or heating is being called by Y1, Y2 or W1, W2.
A1, A2, A3 are dry contact relay terminals that may be used for
night shutdown of dampers or control of other equipment. This is a
separate relay with isolated contacts.
Relay load: 1 AMP (MAX) @ 24VAC.
Connecting the Outputs
5