Control
Heating Control
If Troom ≤ Set-point -【
【d】
】, and R1 has been de-energized for 【
【Pt】
】, then R1 energized;
If Troom ≥ Set-point +【
【d】
】, then R1 de-energized.
R1 Load Delay Protection
After power supplied, R1 could be energized after 【
【Pt】
】;
After R1 de-energized, it could be energized again after 【
【Pt】
】.
Warning
When sensor fails, Blinking display the failure code “LL” or “HH”, buzzing, R1 de-energized.
If Troom ≥【HS】, blinking display “EH”, buzzing, warning output (R2 R3) acts (see table below), R1 de-energized.
After power supplied, and after once having reached to set-point +
【
【d】
】
,
,
i
if
f
Troom ≤【LS】, blinking display “EL”, buzzing, warning
output (R2 R3) acts (see table below), R1 energized.
Note: when buzzing warning, pressing〖P〗will stop buzzing.
Warning Output (R1 R2) Table:
Terminal Remark
R3 After power supplied: open when warning, closed when no warning. When no power supply: open
R2 After power supplied: closed when warning, open when no warning. When no power supply: closed
COM Common terminal
Calibration
The sensor absolute accuracy could be calibrated by setting【
【CA】
】.
Restore to Factory Default Settings
Under none-setting status, keep all four keys depressed simultaneously for 6 seconds, the “8888” will display, and all system
parameters will be restored to factory default settings.
Installation
1st: Insert into drilling hole;
2nd: Clamp
Attention
Do not make wiring (R1, R2, R3 and sensor) when power supplied.
Wiring work should be manipulated by certified technicians.
Wrong connection could damage the controller, and the loads. Power supply to terminal 7 and 8 to check the controller. If there is a
multimeter, check the outputs, as well as input, by the help of settings.
Sensor and input signal wires should not be laid together with power supply wire, and even in same pipe.
Sensor wire is better as short as possible. Not wind the redundant length wire to electrical noise equipment.
The loads should be within the specification of the controller output driving ability. If using ac/dc module as load, or tungsten lamp,
or motor, following the below requirements to avoid surging current damaging or shorten the life time of the controller outputs:
For ac/dc module as load, the rated current should be no more 1/10th of output specification under pure resistance.
For tungsten lamp as load, the rated current should be no more 1/15th of output specification under pure resistance.
For motor, the rate current should be no more 1/5th of output specification under pure resistance.
For example: a 3A (pure resistance spec.) relay, if drive a 660W tungsten lamp with, the relay contactor will be burnt
immediately, if drive a 0.2A tungsten lamp (44W), the life-time will be guaranteed.
Don’t touch inside components;
Avoid installing controller in the following
environment:
More wet than 90%RH, or easily dew; Vibrating, or
will be shocked; Possible sprayed; Under erosive
air; Under explosive air.