Lily Tech ZL-R200A User manual

Suzhou Lily Tech. Co., Ltd.
Page 1, Total 4 Pages
ZL-R200A Heat Pump Water Heater Controller
Instruction Manual V2.0
Main Function
Auxiliary heating function
Water flowing auditing
Ventilation pump control
Antifreeze function
Sensor failures action
Auto defrost function
Auto restart function
Exhaustion temperature protection
Compressor delay and pressure protection
TechnicalSpecification
Sensor:
NTC 10K/3470
Set range:
10 ~ 70℃
Display range:
-40 ~ 130℃
Working temperature:
0~ 50℃
Storage temperature:
-10 ~ 60℃
Ambient humidity:
20 ~ 85%RH without dew
Power supply:
220Vac ±10% 50/60Hz
Outputs:
Compressor 30A
Heater 8A
Others 3A
Failure Code
No.
Code
Failure
No.
Code
Failure
1
E01
Water container sensor failure
6
E05
Water flow warning
2
E02
Pipe Coil sensor failure
7
E06
High/low pressure input warning
3
E03
Exhaustion sensor failure
8
E09
Communication failure
4
E04
Outdoor sensor failure
9
AdF
Filling refrigerant
5
EH
Exhausting alarming
10
UnL
Restore password to “11”
Display Indication
Icon
Display
Not shown
Icon
Displaying
Not shown
Online
Offline
Compressor running
Compressor stop
Heating
Not heating
Pump running
Pump stop
Electrical heating
Electrical heater off
Four valves on
Four valves off
Outdoor fan running
Outdoor fan stop
Locked
Unlocked
Defrosting
Not defrosting now
Key Operation
Temperature Inquiry
Under non-system parameter setting status, press key to check all sensors’ temperature consecutively.
The result keeps displaying for 3 seconds.
On/Off
Keep key depressed for 3 seconds to switch between online and offline.

Suzhou Lily Tech. Co., Ltd.
Page 2, Total 4 Pages
Set (water) Temperature (SP)
Press key to set. Keeping depressed can fast set. The setting will be saved 5seconds later after set.
Factory setting is 40℃.
System Parameter Set
Keep depressed for 3 seconds, the big digits show “P00” for password edit.
Press key to set password, press to confirm.
If the password is wrong, exit. Else enter parameter set status:
Press to select parameter. Press to show the value of the parameter.
Press to set the value. Press to return to parameter selection.
Keep depressed for 3 seconds to save the settings, and exit.
The status will exit, if there is no key operation for 15 seconds, and the settings will not be saved.
System Parameter Table:
No.
Code
Setting function
Range
Indication
Default
1
U01
Hysteresis
2~ 10℃
5
2
U02
Water sensor calibration
-9.9~ 9.9℃
0.0
3
U03
Heater energized from
-5 ~ 25℃
The outdoor temperature
12
4
U30
Defrost start time
10 ~ 90 min
45
5
U31
Defrost start temperature
-9 ~ 0℃
-5
6
U32
Defrost stop temperature
2~ 30℃
10
7
U33
Maximum defrost time
2~ 15 min
8
8
U34
Valve working mode
0~ 1
0: Heat off, defrost on
1: Heat on, defrost off
0
9
U50
Exhaustion protection mode
0~ 2
0: Disable the protection
1: Protect, fan keeps
2: Protect, fan stops
1
10
U51
Exhaust protection temperature
50 ~ 125℃
110
11
U60
High/low pressure warning mode
0~ 2
0: Disable
1: Warning when closed
2: Warning when Open
0
12
U61
Water flowing switch mode
0~ 2
0: Disable
1: Effective when closed
2: Effective when open
0
13
U65
Buzzing alarming
0~ 1
0: Disable. 1: Enable
1
14
U66
Backlight brightness when no key operation
0~ 1
0: Shut off. 1: Dim
1
15
U80
Auto restart function
0~ 1
0: Disable; 1: Enable
0
16
U81
Keypad lock
0~ 1
0: Unlocked; 1: Locked
0
17
U90
passwords
00 ~ 99
11
Working Mode
Press to switch between “AUTO” and “SAVE” working mode.
“AUTO” mode: always heating according setting. “SAVE” mode: only heating within three set periods.
When “Auto restart function” is disabled (U80 = 0), it will be “AUTO” mode after power supplied.
Clock Setting
Press key, the hour digits will blink, press key to set hour.
Press key again, minute digits will blink, press key to set minute.
Press key to exit.
Periods Setting for “SAVE” Mode
Keep key depressed for 3 seconds to enter the period setting status.
Press key to select the period and on/off. Press to set the value of the time.
Keep key depressed for 3 seconds to save the settings, and exit.
The status will exit, if there is no key operation for 15 seconds, and the settings will not be saved.

Suzhou Lily Tech. Co., Ltd.
Page 3, Total 4 Pages
The maximum periods are 3. Every period has an on-time and an off-time.
If one period’s on-time = off-time =0, this period will be shut off.
If one period’s off -time is earlier than its on-time, this off-time is the time of the 2nd day.
Keypad Lock
When U81 = 1, only and have reaction.
Control Function
Temperature Control
When T-water ≤SP –U01, start heating. When T-water ≥SP, stop heating.
Heating start procedure:
Pump is on; 30 seconds later, outdoor fan is on, valve acts; 30 seconds later, compressor is on.
Heating stop procedure:
Compress is off; 30 seconds later, outdoor fan is off, valve acts; 30 seconds later, pump is off.
Note: the four-way valve works according to U34.
Aux Electrical HeaterControl
When T-outdoor ≤U03, and T-water ≤ SP – U01, heater is on.
When T-outdoor ≥U03 + 3℃, or T-water ≥SP, heater is off.
If compressor is on, the heater will be on 10 seconds later when condition meets.
If compressor is off, the heater willbe off 10 seconds later.
Note: Heater will be on during defrosting.
Water Ventilation Pump Control
The pump will be on 60 seconds before the compressor is on, be off 60 seconds after the compressor is off.
The pump will always be on during defrosting.
If there is no water flowing for 10 seconds, stop compressor and heater, and keep warning.
When the water flowing restores, restore the systemcontrol
Avoid Freezing in Winter
In offline standby status:
When T-outdoor ≤2℃, start anti-freezing pumping, the pump run 3 minutes for every 30 minutes.
When T-outdoor ≥ 3℃, stop thisanti-freezing protection pumping.
Auto Defrost
Start auto defrosting: When compressor has been running for U30, and if T-pipe ≤U31, start defrosting.
Compressor and outdoor fan stop; 55 seconds later, valve acts; 5 seconds later, start compressor.
Stop defrosting: When T-pip ≥U32, or the compressor has been running for U33, stop defrosting:
Stop compressor; 55 seconds later, valve acts; 5 seconds later, start heating control.
Defrost after turning the systemonline: When turn online, if the T-pipe ≤U31, defrost 1st.
Timer Defrost
If pipe sensor fails,and the compressor has been running for U30,
If outdoor sensor isok, and T-outdoor ≤ 3℃, start defrosting.
If outdoor sensor fails,start defrosting.
Exhaustion Protection forOver Hot
If U50 = 0, no exhaustion protection.
If U50 = 1 or 2:
When T-exhaustion ≥ U51 + 10℃, stop heating and start alarming.
When T-exhaustion ≤U51 - 10℃, stop protection and alarming, heating again.
If U50 = 2: When T-exhaustion ≥ U51, stop fan.
High/Low Pressure Warning and Protection
When compressor running, if the high/low pressure is effective for 15 seconds, start pressure protection:
Stop compressor, until the high/low pressure is not effective.
If the pressure protection occurs 3 times within an hour, the controller willbe in machine protection mode:
Never start heating again, until remove power supply and supply power again.
When compressor has just started, the high/low pressure will not be in checking for 3 minutes.
Note: the high/low pressure mode is set in U60.

Suzhou Lily Tech. Co., Ltd.
Page 4, Total 4 Pages
CompressorDelay Protection
After power supplied, the compressor can start after 3 minutes.
After compressor stops, it can re-start 3 minutes later.
Water Sensor Failure Warning
When this sensor fails, system stops heating, until the sensor becomes well again.
Refrigerant Filling
In online status, keep depressed simultaneously for 3 seconds, display “AdF”, start refrigerant filling.
There will be no pressure and exhaustion alarming during the filling status.
Keep depressed simultaneously for 3 seconds, exit the filling status.
If the filling status has been for 15 minutes, it will exit automatically.
The action: pump on,fan on 30 seconds later, valve acts (acts oppositely to the U34 setting), compressor on
30 seconds later.
Auto Restart
If U80 = 0, the controller will be in offline status after power supplied.
If U80 = 1, the controller will be the same status as that before the power supply lost.
Restore to Factory Settings
Restore password:
Press keys simultaneously, display “UnL”, the password will be restored to “11”3 seconds later.
Restore all parameters:
Press keys simultaneously, all parameters, including password, will be restored to factory settings.
Wiring Diagram
Attention
Set U34 correctly, otherwise systemdoes not work correctly.
The real clock can only keep running correctly for 72 hours after power supply loses.
All sensorsmust be installed at correct position.
Do not plug in/out panel bundle with power supplied.
Panel should be installed indoors, instead of outdoors.
Other Lily Tech Controllers manuals
Popular Controllers manuals by other brands

Greenheck
Greenheck Belimo Actuators Direct Drive Series installation instructions

Mitsubishi Electric
Mitsubishi Electric MELSEC iQ-R Series user manual

Morningstar
Morningstar MC6 MkII user manual

Beamz
Beamz DMX65W user manual

Adaptec
Adaptec 58300 - SAS Storage Controller 300 MBps Installation and user guide

EWELLY
EWELLY EW-988TK Operation manual