Lily Tech ZL-807A User manual

Suzhou Lily Tech. Co., Ltd.
Page 1,Total 6 Pages
ZL-807A Controller
Instruction Manual V1.0b
Catalog
Feature ................................................................................................................ 2
Function.............................................................................................................. 2
Specification....................................................................................................... 2
Display................................................................................................................. 2
Panel................................................................................................................................................................ 2
Display indication....................................................................................................................................... 2
Alarming code.............................................................................................................................................. 3
Operation ............................................................................................................ 3
Set setpoint................................................................................................................................................... 3
Set parameter............................................................................................................................................... 3
Check pipe temperature.......................................................................................................................... 3
Parameter code table................................................................................................................................ 3
Control................................................................................................................. 3
On/Offline control....................................................................................................................................... 3
Cooling only mode (F01 = 1).................................................................................................................. 3
Constant temperature mode (F01 = 0)............................................................................................... 4
Heat by compressor (F02 = 0)...........................................................................................4
Heat by electrical heater (F02 = 1) ....................................................................................4
Defrost (F02 = 0, and under heating mode) ......................................................................4
Forced defrost (F02 = 0, under heating mode)..................................................................4
Fast launch (Force the compressor energized)............................................................................ 4
Pump control................................................................................................................................................ 4
External alarm input.................................................................................................................................. 4
Delay protection for compressor........................................................................................................ 4
Auto restart................................................................................................................................................... 4
Calibration..................................................................................................................................................... 4
Waring for sensor failure........................................................................................................................ 4
Restore to factory settings..................................................................................................................... 5
Wiring diagram ................................................................................................... 5
Diagram one: heating by compressor............................................................................................... 5
Diagram two: heating by heater........................................................................................................... 5
Dimension........................................................................................................... 6
Out size........................................................................................................................................................... 6
Embedded hole........................................................................................................................................... 6
If the cable protection rubbers could be removed during installation................................6
If the cable protection rubbers could not be removed during installation..........................6

Suzhou Lily Tech. Co., Ltd.
Page 2,Total 6 Pages
ZL-807A Controller
Instruction Manual V1.0b
Feature
ZL-807A is water temperature controller. It could work in cooling mode, or constant temperature control mode.
It can drive 2 HP compressor directly.And it has water pump on/off control function.
With IP60 panel, friendly to operate, easy to install. It could control sea food chiller, aquarium pool, or water tank’s temperature.
Function
● Control mode: constant temperature, cooling only.
● Heating method: by compressor, by electrical heater.
● Periodic defrost (when install 1 sensor).
Intelligent defrost (when install 2 sensors)
* Default packing is with one sensor.
* Pipe sensor could be purchased standalone.
Pipe sensor can be found by controller when installed.
If the outdoor evaporator frosts serious, 2 sensors is better.
With 2 sensors, we can check outdoor pipe temperature.
● Water pump on/off control
● Compressor delay protection
● Instant start compressor
● Temperature calibration
● Sensor failure warning
● External warning input
● Auto restart for power supply failure
Specification
● Power supply: 100 ~ 240Vac, 50/60Hz
● Outputs:
Compressor: 40A/250Vac relay, can drive 2HP compressor.
Valve/Heater: 5A/250Vac, resistance.
Fan: 5A/250Vac, resistance.
Pump: 5A/250Vac, resistance.
●Set range: -9.9 ~ 65.0℃
●Display range: -9.9 ~ 70.0℃
●Working: -10 ~ 45℃, <85%RH without dew
●Deposit: -30 ~ 70℃
● Case: fireproof ABS
● Protection level: IP60
● Sensor: NTC, 5K@25℃, B=3470K.
Water sensor, plastic sealed, 5 meters cable.
Pipe sensor, copper sealed nickel coated, 2 meters cable.
● Size: See last page of this manual.
Display
Panel
Display indication
Lamp
On
Off
Blinking
OnOff (red)
Online
Offline
Alarming
SET (yellow)
Setting temperature
Setting parameters
PUMP (green)
Pump energized
Pump de-energized
COOL (green)
Cooling
Under delay protection
HEAT (red)
Heating
DEF (yellow)
Defrosting
Forced defrosting

Suzhou Lily Tech. Co., Ltd.
Page 3,Total 6 Pages
Alarming code
Code
Remark
E1
Water sensor failure
E2
Defrost sensor failure
E3
External alarming (all controller outputs will be de-energized)
Operation
Set setpoint
Enter into temperature setting status: Keep【SET】depressed for 3 seconds.
The SET lamp will be on. The current setpoint displays.
Press【▲】or【▼】to set setpoint. (keep the keys depressed can fast setting)
Keep【SET】depressed for 3 seconds, exit the setting status, the setting will be saved.
The setting status will exit, the set value will not be saved, if there is no key operation for 10 seconds.
Set parameter
Enter into parameter setting status: Successively and fast press【▲】【 ▼】【 ▲】【 ▼】【 ▲】【 ▲】【 ▼】, like input password.
The SET lamp will be blinking. The 1st parameter code “F01” displays.
Press【▲】or【▼】to select code (F01, F02, F03, …).
Press 【SET】to display the value of the code.
Press【▲】or【▼】to set the value of the code. (keep the keys depressed can fast setting)
Press【SET】to return to parameter code display.
By this, all code could be set.
Keep【SET】depressed for 3 seconds, exit the setting status, the settings will be saved.
The setting status will exit, the set values will not be saved, if there is no key operation for 30 seconds.
Check pipe temperature
In online status, short press【 】 will blinkingly show pipe temperature for 10 seconds.
Short press【 】 could stop show the pipe temperature.
Parameter code table
Code
Function
Setting range
Remark
Factory
set
F01
Temperature control mode
0/1
0: constant temperature
1: cooling only
0
F02
Heating mode
0/1
0: by compressor
1: by electrical heater
0
F03
Hysteresis
0.1 ~ 20.0℃
1.0
F04
Calibration for water sensor
-9.9 ~ 9.9℃
0.0
F05
Calibration for pipe sensor
-9.9 ~ 9.9℃
0.0
F06
Delay protection for compressor
0 ~ 10 min
3
F07
Temperature for start defrost
-20 ~ 20℃
-5
F08
Temperature for stop defrost
-20 ~ 20℃
If F08 ≤F07, disable defrost function
10
F09
Max defrost time
0 ~ 60 min
5
F10
Min time to start defrost (1)
0 ~ 600 min
0: disable defrost function
30
F11
Buzzing alarm (2)
0/1
0: disable
1: enable
0
F12
External alarm setting
0 ~ 2
0: disable
1: Effective when short
2: Effective when open
0
F13
Delay for external alarm
0 ~ 120 sec
3
Note: (1) The continuous energized time for compressor. (2) When alarming buzzing, it could stop by press any key.
Control
On/Offline control
Keep【 】depressed for 3 seconds to switch between online and offline.
Cooling only mode (F01 = 1)
If (water temperature) ≥(setpoint + F03), and the compressor has stopped for F06, the compressor energized.
If (water temperature) ≤(setpoint), the compressor de-energized.
Control sequence: Compressor on, fan will be on after 10 seconds. Compressor off, fan will be off after 5 seconds.

Suzhou Lily Tech. Co., Ltd.
Page 4,Total 6 Pages
Constant temperature mode (F01 = 0)
Heat by compressor (F02 = 0)
If (water temperature) ≥(setpoint + F03), and the compressor has stopped for F06, the compressor starts cooling.
If (water temperature) ≤(setpoint), the compressor de-energized.
If (water temperature) ≤(setpoint-F03), and the compressor has stopped for F06, the compressor starts heating.
If (water temperature) ≥(setpoint), the compressor de-energized.
Control sequence: Compressor on, fan will be on after 10 seconds. Compressor off, fan will be off after 5 seconds.
Heating cooling change sequence: the compressor will be energized 15 seconds after 4-way valve is set.
Heat by electrical heater (F02 = 1)
If (water temperature) ≥ (setpoint + F03), and the compressor has stopped for F06, the compressor energized.
If (water temperature) ≤ (setpoint), the compressor de-energized.
If (water temperature) ≤ (setpoint-F03), the heater energized.
If (water temperature) ≥ (setpoint), the heater de-energized.
Control sequence: Compressor on, fan will be on after 10 seconds. Compressor off, fan will be off after 5 seconds.
Defrost (F02 = 0, and under heating mode)
Intelligent defrost
If (pipe temperature) ≤F07, and the compressor has been energized for F10, start defrost.
If (pipe temperature) ≥F08, or (the defrosting time) ≥F09, stop defrost.
Periodic defrost
Without defrost sensor, or when defrost sensor fails, the controller will defrost periodically.
When the compressor has been energized for F10, start defrost.
When defrosting time reaches F09, defrost ends.
Defrost procedure
Compressor stops→valve switches after 30 seconds→compressor starts for defrost after 30 seconds→compressor stops
when F08 or F09 condition meets→valve switches after 30 seconds→start compressor heating after 30 seconds.
Fan stops during defrosting.
Forced defrost (F02 = 0, under heating mode)
Keep【▲】and【▼】depressed simultaneously for one second to enter into forced defrosting.
* Forced defrosting works the same way as periodical defrost.
* Once launched forced defrost, it will not stop, till the full process finished.
* Fan stops during forced defrosting.
Fast launch (Force the compressor energized)
Launch: when online, keep【 】and【S】depressed simultaneously for 6 seconds, there will be 3 short beeps and 1 long beep,
and the compressor will be energized.
The controller will keep working as the set of F01 for 90 seconds, then exit the status.
Stop: It can stop and exit by keeping【 】and【S】depressed simultaneously for 6 seconds.
Pump control
When online, keep【PUMP】depressed for 3 seconds to switch pump on/off.
* When power supplied, pump works in the same status as that of previous power supplied.
* Press【 】to shut to offline, the pump will stop. Press【 】to switch to online, the pump keeps off!
* External alarm does not influence the pump status.
External alarm input
F12 = 0, disable external alarm function.
F12 = 1, when short for F13 time, alarming.
F12 = 2, when open for F13 time, alarming.
During alarming, all outputs except pump de-energized, buzzing, E3 displays, power lamp blinking.
Delay protection for compressor
Every time, the power supplied, the compressor is possible to be energized after F06 time.
Every time, the compressor is de-energized, it is possible to be energized after F06 time.
Auto restart
When power supply loses, and then come back, the controller will work in the same status as that before power loses.
Calibration
By setting F04/F05, we can compensate the error of the sensors.
Warning for sensor failure
When water sensor fails, display E1, compressor/valve or heater/fan will be de-energized, beeping, OnOff lamp blinking.
When pipe sensor fails, display E2.

Suzhou Lily Tech. Co., Ltd.
Page 5,Total 6 Pages
Restore to factory settings
Keep【SET】and【▲】depressed simultaneously for 2 seconds, display “UnL”.
Press【▼】twice, all settings will restore to factory default values.
Wiring diagram
Diagram one: heating by compressor
Diagram two: heating by heater

Suzhou Lily Tech. Co., Ltd.
Page 6,Total 6 Pages
Dimension
Case size
Embedded hole
If the cable protection rubbers could be
removed during installation
Hole size = 136.1 * 86.5 mm, R = 7 mm
If the cable protection rubbers could not be
removed during installation
Hole size: 135.1 * 90.5 mm, R = 6 mm
Table of contents
Other Lily Tech Controllers manuals
Popular Controllers manuals by other brands

Federal Signal Corporation
Federal Signal Corporation UltraVoice UVIC Description, Specifications, Installation, Operation, and Service Manual

Ko Propo
Ko Propo BSx2 Series manual

Johnson Controls
Johnson Controls FAC2611 installation guide

Kessler Crane
Kessler Crane Oracle manual

Omron
Omron E5EC-B instruction manual

micro-trak
micro-trak MT-2405FTW II Reference manual

CBS ArcSafe
CBS ArcSafe RSA-112 Installation and operation

battioni Pagani
battioni Pagani LOCKER Instruction manual for use and maintenance

Nivetec
Nivetec UNICONT PMM-500 User and programming manual

Kirby Morgan
Kirby Morgan SuperFlow manual

Tescom
Tescom ER3000 user manual

MKS
MKS Mass-Flo 1479A instruction manual