Lumin LS-100544 User manual

WWW.LUMINSMART.COM
LS-100544 Re v. 2
Lumin Smart Panel - Outdoor
DOCUMENTATION
AND INSTALLATION
MANUAL

® U.S. Registered Trademark. Patents pending.
Copyright © 2022 Coulomb, Inc. (DBA Lumin). All rights reserved.

Lumin Sma rt Panel - Outd o or
DOCUMENTATION AND INSTALLATION MANUAL
TABLE OF CONTENTS
INTRODUCTION.................................................................................................................................................. 1
READ BEFORE USE ............................................................................................................................................. 2
Warnings ....................................................................................................................................................... 2
SYSTEM DESIGN CONSIDERATIONS ................................................................................................................. 3
INSTALLATION.................................................................................................................................................... 4
Items in the Box............................................................................................................................................ 4
Required Materials (Not Included).............................................................................................................. 5
Required Tools.............................................................................................................................................. 6
Hardware Installation Overview.................................................................................................................. 7
Hardware Installation Steps ........................................................................................................................ 8
Configuration and Account Setup............................................................................................................. 31
TROUBLESHOOTING AND REPAIRS................................................................................................................ 33
End User ...................................................................................................................................................... 33
Qualified Installer ....................................................................................................................................... 33
OPERATIONAL INFORMATION ........................................................................................................................ 34
PRODUCT SPECIFICATIONS............................................................................................................................. 35
LIMITED WARRANTY FOR LUMIN SMART PANEL........................................................................................... 36
RADIO FREQUENCY STATEMENT .................................................................................................................... 37

This page intentionally left blank

Lu mi n Smart Panel - Outdoor
DOCUMENTATION AND INSTALLATION MANUAL
1
INTRODUCTION
Welcome! The Lumin Smart Panel (LSP) is a standalone product that extends the capability of an
existing circuit breaker panel (or “electrical panel”) by providing measurement and remote control of
up to twelve (12) circuits in a home or building. The function of the circuit breaker panel remains the
same and is not impacted. The LSP securely and safely transmits real-time consumption information to
the cloud via Ethernet connection (preferred) or customer Wi-Fi.
Data and system controls can be accessed via the Lumin mobile app or the web-based Lumin
dashboard (app.luminsmart.com). The Lumin app gives customers insights into their energy
consumption and energy costs, as well as providing the user with the ability to control or automate
their energy use remotely.
NOTE: A Lumin Smart Panel will not function as designed until it is fully commissioned. It is generally
the responsibility of the installer to perform both the physical installation and the online
setup/commissioning process. Refer to pg. 31 to begin the setup process. All personnel installing this
product should complete Lumin Certified Installer Training prior to installation. Scan below to register
for training.
Need help? For installation assistance please contact Lumin by e-mail at
support@luminsmart.com or by phone at 1-888-421-0616 (North America).
DANGER: HAZARDOUS VOLTAGES PRESENT DURING
INSTALLATION AND SERVICING. PRECAUTIONS AND
QUALIFICATIONS REQUIRED. REFER TO THE FOLLOWING
PAGE.
DANGER: TENSIONS DANGEREUSES PRÉSENTES LORS
L'INSTALLATION ET L'ENTRETIEN. PRÉCAUTIONS ET
QUALIFICATIONS REQUISES. REPORTEZ-VOUS À LA PAGE
SUIVANTE.

2
READ BEFORE USE
The LSP interfaces with existing electrical panels and includes conduit/fittings for installation with
surface-mount electrical panels. Verify the label model number is LSP-12-OR before performing an
outdoor installation. Please review the product’s technical ratings and specifications (pg. 35) to confirm
it is suitable for your application prior to installation.
NOTE: The LSP Circuit Label & CT Table (provided with the LSP) must be completed and delivered to the
home/building owner upon the successful installation of the LSP. A completed LSP Circuit Label & CT
Table is required in order to complete LSP setup.
Warnings
LSP installation and servicing involves dangerous voltages that can cause injury or death. In addition to
specific instructions accompanied by the symbol throughout this booklet and product labeling,
observe the following safety precautions:
•Installation and servicing must be conducted by a qualified professional, according to local and
national electrical codes
•Lumin Certified Installer training is required for installation and servicing
•Review entire manual before starting the installation or servicing
•Personal protective equipment should be worn when installing or servicing the product
•Do not use the product in any way other than its intended use
•Do not install or operate the product outside the conditions specified on pg. 35
•Do not open, attempt to access, or touch any internal product parts —dangerous voltages would
be exposed even if main service feed is disconnected
•Do not use the product if it is damaged or appears to be damaged
•Use only the wires and cables supplied with the product
•Power relays are evaluated for 100,000 cycles at a 1.5 HP inductive load (e.g., motors) —larger
loads of this type may result in premature relay failure
•Adhere to all relevant local and national safety regulations for electrical work
•This manual covers outdoor surface mounted electrical panel installations only. Connecting the LSP
conduit to an outdoor recessed electrical panel is the sole responsibly of the installer and shall be
done in accordance with all local codes and regulations.

Lu mi n Smart Panel - Outdoor
DOCUMENTATION AND INSTALLATION MANUAL
3
SYSTEM DESIGN CONSIDERATIONS
•The LSP should be mounted so that the connected electrical panel is within reach of the LSP’s flexible
conduit fitting. The fitting extends 13" beyond the left face or 9”beyond the right face of the LSP
enclosure. Ensure that the electrical panel has adequate wiring space for LSP conductors and
connections. Suitable junction boxes and conduit may be used to route and/or extend LSP
conductors if needed. For voltage drop calculations, assume LSP conductors add 15 one-way-feet to
the circuit.
•An LSP requires an always-on Internet connection, either via Ethernet (preferred if available) or 2.4
GHz Wi-Fi. Communication wiring requires materials for routing in 3/4" liquid-tight conduit.
•When used for energy management, the LSP will be most effective when used to shed heavy
discretionary loads. These are loads greater than 15 amps that may be desired during grid outages
or other energy-constrained situations. Lumin can shed such loads automatically while permitting a
user to manually re-enable them at their discretion. More information about circuit selection is
provided in the required Lumin Certified Installer Training. In order to shed discretionary loads
in response to grid conditions, a connection to non-backed up utility grid power is required for
the LSP grid detection circuit. See pg. 28. This will require wiring beyond the LSP’s connected
electrical panel. Controlling the circuit that powers the Internet connection is not
recommended; manual control of the LSP will be lost when this circuit is switched off.
•The LSP does not replace the need for standard circuit breakers. Lumin does not provide overcurrent
protection, ground fault protection, arc fault detection, or other safety functionality that circuit
breakers provide.
•The LSP uses current transformers (CTs) to measure overall power flows. Correct placement of these
CTs may require wiring beyond the LSP’s connected electrical panel. See pg. 23.
•If the LSP is configured to automatically shed loads exceeding backup capacity following a grid
outage, a Temporary Power Unit (TPU) accessory module may be required if the transfer to backup
power takes more than 70 ms. Without the TPU, the LSP could lose power before backup transfer
completes, and circuit disconnection would be delayed until after the LSP powers on with the backup
source. If unsure about transfer times, contact Lumin to determine if a given system requires a
TPU. The TPU may be installed inside the LSP enclosure before (preferred) or after LSP purchase.
Need help? For system design and installation assistance please contact Lumin by e-mail at
support@luminsmart.com or by phone at 1-888-421-0616 (North America).

4
INSTALLATION
Items in the Box
Upper Outdoor Wall
Mounting Brackets
NOTE: Additional items include an antenna, installation hardware, and an LSP Circuit Label &
CT Table.
1 Pair of 200A Current Transformers
(A second pair is optional)
Lower Outdoor Wall
Mounting Brackets
1 Outdoor LSP with Conduit, Conduit
Bushings & Wire Whips Attached

Lu mi n Smart Panel - Outdoor
DOCUMENTATION AND INSTALLATION MANUAL
5
Required Materials (Not Included)
NOTE: Additional supplies may be required depending on the existing electrical panel installation. A
NON-GFCI dual-pole breaker of 15 to 20 amps may be required to power the LSP. Appropriately rated,
NON-GFCI breakers may be double-tapped depending on local electrical codes. See pg. 17 for more
details. A supply-side connection (line-side tap) and/or wire extension may be required for the LSP’s
Grid Detection Circuit (see pg. 28). Specific wire extension supplies may be required for current
transformers (see pg. 26). Liquid-tight conduit (3/4” trade size) may be required for communication
wiring (see pg. 31). The conduit provided is 2”(trade size) NMLT Type B. Additional NMLT Type B
conduit and fittings maybe required depending on installation conditions. The installer may orient the
provided 90 deg conduit elbow to the left or right side or replace it with a different 2”(trade size) NMLT
Type B fitting.
For outdoor installations: The installation orientation of the LSP must plumb and level with the
conduit fitting at the bottom of the enclosure. All conduit and fittings between the LSP, the electrical
panel, and/or the optional communication cable routes must be liquid-tight conduit.
Supply-side/line-side tap
(Optional)
Cable ties (Optional)
Pen or marker
Wire splice connectors
Dual-pole breaker: 15 to 20 amps
(Optional)
3/4" Liquid-tight conduit and
fittings (Optional Ethernet cable)

6
Required Tools
NOTE: A multimeter may be required for determining current transformer placement (see pg. 25).
2” Knockout punch
(2-3/8” hole size)
Pliers
Tape measure
Stud-finder (Optional)
Fish tape (Optional)
Utility knife
Wire stripper
Drill
Phillips screwdriver
Flathead screwdriver
Level
Multimeter (Optional)

Lu mi n Smart Panel - Outdoor
DOCUMENTATION AND INSTALLATION MANUAL
7
Hardware Installation Overview
STEP 1. Turn Off Main Feed and Remove
Electrical Panel Cover
STEP 2. Knock Out or Punch One Hole for 2”
Conduit Fitting
STEP 3. Determine LSP Mounting Position
Relative to Conduit Routing
STEP 4. Measure and Mark Hole Locations for
Mounting
STEP 5. Secure Mounting Brackets to Wall
STEP 6. Attach LSP Antenna and Guide LSP Wire
Whip into Electrical Panel
STEP 7. Secure LSP to Wall/Bracket and Electrical
Panel
STEP 8. Connect LSP Equipment Grounding
Conductor (EGC) to Ground Bar
STEP 9. Identify A-Row and B-Row Breakers
STEP 10. Connect LSP Power Circuit and Label
Breaker
STEP 11. Select Circuit Breaker to Connect to
LSP, Turn Off, and Disconnect Load
STEP 12. Connect One LSP Wire Labeled “Line 1
Breaker” to Circuit Breaker
STEP 13. Connect Corresponding LSP Wire
Labeled “Line 1 Load” to Load and Turn
Circuit Breaker Back On
STEP 14. Record Circuit Label/Name and Breaker
Row (A/B) With Corresponding LSP Wire
Number
STEP 15. Repeat Steps 11-14 Until All LSP Line #
Wires Are Connected
STEP 16. Determine Placement of Current
Transformers (CTs)
STEP 17. Phase Conductors Monitored by
Current Transformers
STEP 18. Testing for Crossover before Current
Transformer Placement
STEP 19. Connecting Current Transformers
STEP 20. Record Line Name(s) of Corresponding
Current Transformers
STEP 21. Connect the LSP’s Grid Detection Circuit
(GDC) Wires to the Grid Side of an
Automatic Transfer Switch (ATS) or
Microgrid Interconnect Device (MID)
STEP 22. Replace Electrical Panel Cover and Turn
On Main Feed
STEP 23. Attach Antenna and Turn On the LSP to
Begin Configuration and Account Setup
STEP 24. LSP Configuration
STEP 25. Reinstall LSP Cover

8
Hardware Installation Steps
STEP 1. Turn Off Main Feed and Remove Electrical Panel Cover
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE.
AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES
CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
Tools: Screwdriver

Lu mi n Smart Panel - Outdoor
DOCUMENTATION AND INSTALLATION MANUAL
9
STEP 2. Knock Out or Punch One Hole for 2” Conduit Fitting
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE.
AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES
CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
Tools: Screwdriver, pliers, drill (optional), and knockout punch (optional)
NOTE: Knockout hole location in electrical panel may vary depending on spacing constraints. Choose a
location that avoids existing obstructions and provides adequate clearance for routing of the LSP wire
whips. Use of existing pre-stamped 2” knockouts are acceptable provided there is sufficient clearance.
Otherwise, a 2” knockout punch (2-3/8” hole) will be required to attach the LSP conduit. Additional
conduit fittings may be required depending on routing conditions, including installations that utilize
the bottom face of the electrical panel. Ensure the knockout hole location allows vertical mounting
of the LSP as shown in the following steps.

10
STEP 3. Determine LSP Mounting Position Relative to Conduit Routing
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE.
AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES
CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
NOTE: The LSP must be mounted in the vertical orientation shown (with the conduit exiting the
LSP from the bottom). To prepare for mounting, position the LSP in alignment with the knockout hole
in the electrical panel. Temporarily feed the wire whips and conduit fitting into the knockout hole.

Lu mi n Smart Panel - Outdoor
DOCUMENTATION AND INSTALLATION MANUAL
11
STEP 4. Measure and Mark Hole Locations for Mounting
Tools: Tape measure, marker, stud-finder (optional), and level.
NOTE: The LSP must be mounted in the vertical orientation shown. Verify that the bracket
placement provides a level installation without introducing strain on the conduit attachments. Then
mark the applicable hole locations using the mounting brackets. Exact hole locations may vary
depending on existing conditions. Qty 4 holes are required for sufficiently mounting the LSP.
Location of Mounting Holes and Slots (Large Arrows)
Bracket Attachment Stud Locations (Small Dashed Arrows)
Marking Hole Locations Using Brackets

12
STEP 5. Secure Mounting Brackets to Wall
Tools: Drill, stud-finder (optional), screws (x4), and washers (x4)
NOTE: Ensure the outer screws of the upper bracket are securely threaded into studs, sheathing, brick,
masonry, or other suitable structural anchors. For masonry applications (including brick) use the
appropriate fasteners included in the installation hardware. Exterior cladding such as vinyl or
aluminum siding are examples of unsuitable anchors. Secure the LSP to the structure behind exterior
cladding systems.

Lu mi n Smart Panel - Outdoor
DOCUMENTATION AND INSTALLATION MANUAL
13
STEP 6. Attach LSP Antenna and Guide LSP Wire Whip into Electrical Panel
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE.
AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES
CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
NOTE: Attach the antenna provided with the LSP and then guide the wire whip through the knockout in
the electrical panel. Remove the conduit bushing before guiding the wire whip through the hole.
Wire
Whip
Attach
Antenna
Conduit
Bushing

14
STEP 7. Secure LSP to Wall/Bracket and Electrical Panel
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE.
AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES
CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION.
Tools: Drill, washer, and nuts (x3)
NOTE: Lift the LSP to align with the mounting holes and secure it to the mounting brackets utilizing the
hardware provided. Use two nuts with the upper bracket. Use a washer and nut to position the LSP in
the lower bracket slot such that the LSP is vertical (front face plumb). Secure the LSP conduit to the
electrical panel with the 2” conduit bushing provided.

Lu mi n Smart Panel - Outdoor
DOCUMENTATION AND INSTALLATION MANUAL
15
STEP 8. Connect LSP Equipment Grounding Conductor (EGC) to Ground Bar
WARNING: HIGH VOLTAGE. ENSURE MAIN BREAKER IS OFF. MAIN SERVICE LINES ARE ALWAYS LIVE.
GROUND WIRE MUST BE INSTALLED FOR SAFETY.
AVERTISSEMENT: HAUTE TENSION. ASSUREZ-VOUS QUE LE DISJONCTEUR PRINCIPAL EST ÉTEINT. LES
CONDUCTEURS DE SERVICE PRINCIPAUX SONT TOUJOURS SOUS TENSION. UN FIL DE TERRE DOIT ÊTRE
INSTALLÉ POUR LA SÉCURITÉ.
Tools: Screwdriver and pliers (optional)
NOTE: Connect the EGC (bare copper wire) from the LSP to the existing ground bar in the electrical
panel (exact location of ground bar may vary).
EGC to
Ground Bar

16
STEP 9. Identify A-Row and B-Row Breakers
NOTE: For purposes of Lumin installation, the top row of breakers will always be classified as “A”. The
second row of standard breakers will be “B”. The alternating A-B-A-B pattern continues down the rows
of breakers. Exception: All breaker rows are designated “A” in panels with two-wire single-phase power
rather than three-wire single-phase (split phase).
NOTE: If the electrical panel contains tandem or “skinny” breakers, there will be two breakers in a
standard breaker space. Thus, the top-to-bottom breaker panel will be A-A-B-B-A-A-B-B.
A
B
A
B
A
B
Table of contents
Other Lumin Home Automation manuals