Sivoia®QS QSPS-P1-10-60 Installation instructions
2
2.1
Installation
1. Mount QSPS-P1-10-60 using one of the following methods (Mounting Hardware is not
provided) Do not mount in any other orientation.
a. Surface Mount - Use the keyholes located on the back of the enclosure to fasten the
QSPS-P1-10-60 to the wall. Use fasteners rated for a 50 lb. (23 kg) load. See illustration
of QSPS-P1-10-60 .
b. Recess Mount - Install a 2 in x 4 in (50 mm x 100 mm) board between the studs as
a bottom support. Fasten the QSPS-P1-10-60 to the right stud and bottom support
inserting fasteners through the mounting holes provided.
The equipment is air-cooled.
Mount in a location where the vented
cover will not be blocked. A minimum
of 1 ft. (300 mm) is necessary.
SHOCK HAZARD. Risk of serious injury
or death. Locate and lock the supply
breaker in the OFF position
before wiring to the terminal blocks.
SHOCK HAZARD. Risk of serious
injury or death. Disconnect input
power before servicing.
16 in (406 mm)
10.4 in (264 mm)
4.8 in (121 mm)
1.2 in (30 mm)
14.8 in (375 mm)
17.5 in (445 mm)
6 in (152 mm)
1.8 in (45 mm)
2 x 4 in (50 x 100 mm)
Bottom Support
2. Connect 120 V~ power wiring
into the QSPS-P1-10-60.
Remove one of the knockout tabs
on the top left side of the enclosure
near the input terminal blocks. In-
sert a strain relief into the knockout
hole. Run the power wire through
the strain relief (not included) to
the input terminal blocks at the top
left side of the enclosure. Tighten
terminal blocks to 3.5 to 5 in-lbs.
(0.4-0.6 N•m).
Note: Maximum of 1 QSPS-P1-10-60 per 15 A Breaker.
Maximum of 2 QSPS-P1-10-60 per 20 A Breaker.
Maximum feed breaker size of 30 Amps.
Use only High-Magnetic breakers.