LUXOMAT LUXOMAT net PD4-M-DALI User guide

Installation and Operating Instruction for B.E.G. - Occupancy detector
PD4-M-DALI/DSI-HVAC-FC
LUXOMAT®
net PD4-M-DALI/DSI-HVAC
EN
1. Product information
• Occupancy detector for daylight-dependent lighting
control
• DALI/DSI interface for controlling digitally dimmable
electronic ballasts as a group
• One additional switching channel (NO potential-free, dry)
for controlling lights and HVAC (heating, ventilation, air
conditioning) devices
• Switching between DSI and DALI program by remote
control or DIP switch
• Extension of the detection area by Slave devices is
possible
• Set value brightness, follow-up time – LIGHT/HVAC and
orientation light adjustable
• Manual switching and dimming via pushbutton possible
• Orientation light function
2. Operation
The presence detector controls the light automatically according
to people present (movements) and the ambient brightness.
The integrated light sensor constantly measures the ambient light
and compares it with the set value brightness on the detector. If
the ambient light is sufficient, lighting will not be switched.
If the ambient light level is below the set value brightness, a
movement activates the lighting in the room.
The detector switches the light off despite of a person being pre-
sent if there is enough natural light for 5 min or if no movement
is detected for one follow-up time.
3. Safety information
Work on the 110-240V mains supply may only be
carried out by qualified professionals or by instructed
persons under the direction and supervision of quali-
fied skilled electrical personnel in accordance with
electrotechnical regulations.
Disconnect supply before installing!
This device is not suitable for disconnection.
Mounting the cover ring, after introduction of the
power cable (FC version).
4. Mounting
68 mm
A circular opening of diameter 68mm must be produced in the
ceiling. Having connected up the cables in accordance with
regulations, the detector is inserted into the opening as shown in
the drawing and fixed into position with the assistance of the
spring clips.
5. Position DIP switches, LEDs and
Potentiometers
DALI_DSI
HVAC_
LIGHT
VA_HA
PD4-
False ceiling
mounting
Light
measurement
1
2
3
III III
DCBA
6. Self test cycle/Startup behavior
The product enters an initial 60-second self-test cycle, when the
supply is first connected. During this time the device does not
respond to movement and stays on.
7. Putting into operation / Settings
Brightness value for constant light control
(Potentiometer A)
The brightness set value can be defined between
10 and 2000 lux. The potentiometer enables a free
selection of the brightness value.
Symbol : Night-time operation
Symbol : Day-time operation
(Light evaluation inactive)
Follow-up time for light control (Potentiometer B)
The follow-up time can be set to 1 to 30 minutes.
Symbol TEST: test mode
Irrespective of the brightness, every movement switches
the light on for 1s, then off again for 2s.
Follow-up time for orientation light (Potentiometer C)
The follow-up time can be set infinitely variably at
between 5 and 60 minutes. Manually switching ON/
OFF the orientation light.
“ON” for permanent orientation light
“OFF” for deactiviation of orientation light
Follow-up time for device control (Potentiometer D)
The follow-up time can be adjusted between 5min. and
120min. The delay is active from a set time of >15 mi-
nutes. This delay is about 5 min. If no other movements
are detected during this time, the delay starts again.
Impulse function
The impulse function can be used to control external
HVAC systems. All 9sec. will be set an impulse of
2.5 sec.
Alarm impulse
In order to initiate an alarm impulse, there have to be
three detected movements within a period of 9sec.
This function can be used to display a presence in the
room on external visualizations. All 9 sec. will be set an
impulse of 2.5 sec.
The device does not fulfil the requirements of DIN
EN50131-2-2 and therefore cannot be used in
professional intrusion detection systems.
DIP switch functions
DIP 1 Full automatic mode Semi-automatic mode
DIP 2 HVAC function Light control*
DIP 3 Operation mode DALI Operation mode DSI
*If you select “LIGHT”, the switching relay R2 operates synchro-
nously to the DALI light channel. The potentiometer R2 has no
function in this setting.
Potentiometer A Brightness (constant light control) channel 1
Potentiometer B Follow-up time (light) channel 1
Potentiometer C Follow-up time (orientation light)
Potentiometer D Follow-up time (device control) channel 2
LED I green
LED II red
LED III white
8. Wiring diagram
Schematic diagram - when connecting the detector, please
respect the labelling of the terminal connections at the detector!
Standard mode with Master/Slave
L
N
L
N
DA
DA
E1 DALI/DSI
LN NO NO RS+ -
Master Slave
L
R N
DA
HVAC HVAC
M1
T1
T2
9.
Manual switching and dimming
By pressing the push button, the phase can be given to the S
terminal.
To turn on or off the light, press the push button briefly. The light
will remain on or off, as long as people are detected plus the
follow-up time.
With a long press of the push button the light will be dimmed
manually. When releasing the button, the current brightness value
is retained.
With renewed long press of the push button, the dimming direction
is reversed.
Taking the phase to the R terminal by using a button, the HVAC
channel can be switched with a short key press.
10. Range
!
Connected Slave devices must have the same phase
as the Master device.
R1
TE
1
3
6
22
18 16 10
30
25
LUX
40
2000
600
120 0
200
R2
A
120
60
5
15
30
40
50
20%
60 5
10
50 30
OFF
ON
R1
TE
1
3
6
22
18 16 10
30
25
LUX
40
2000
600
120 0
200
R2
A
120
60
5
15
30
40
50
20%
60 5
10
50 30
OFF
ON
R1
TE
1
3
6
22
18 16 10
30
25
LUX
40
2000
600
120 0
200
R2
A
120
60
5
15
30
40
50
20%
60 5
10
50 30
OFF
ON
!
R1
TE
1
3
6
22
18 16 10
30
25
LUX
40
2000
600
120 0
200
R2
A
120
60
5
15
30
40
50
20%
60 5
10
50 30
OFF
ON
A
!
!
!
!
The light sensor should be mounted on the opposite
side of the window.
In Master/Slave operation the Master device must
always be installed at the site with less daylight.
!
!
LEDs
24 m
8 m
6.40 m
24 m
360°
2.50 m
2
1
1
2
quer zum Melder gehen
frontal zum Melder gehen
Unterkriechschutz
Walking across
Walking towards
Seated
3
3

11. Exclude sources of interference
If the detection zone is too large, or areas are covered that should
not be monitored, use the blinds to reduce or limit those areas.
12. Technical data
Power supply: 110-240 VAC, 50/60 Hz
Power consumption: approx. 1W
Ambient temperature -25°C to +50°C
Degree of protection/class:
IP20 / II
Recommended height
for mounting:
2 - 3 m
Range of coverage
Ø H 2,5 m / T = 18°C:
seated 6.4m / tangential 24 m /
radial 8 m
Area of coverage:
circular 360°
Dimensions H x Ø [mm]
FC
103 x 97mm
Visible part when built into ceiling:
15 x 97mm
Lux value:
10 - 2000 Lux
• DALI/DSI
digital BUS control wire, 2-core, no polarity (broadcast only)
Max. no. of series-connected electronic ballasts:
up to 50 (broadcast only)
Time settings:
1 - 30 min. / test
• Channel 2
Type of contact:
NOC/with pre-travel tungsten
contact
Contact load:
2300 W, cosϕ=1;
1150 VA, cosϕ= 0,5, µ contact
EU Declaration of Conformity:
This product respects the directives concerning
1. electromagnetic compatibility (2014/30/EU)
2. low voltage (2014/35/EU)
3. restriction of the use of certain hazardous substances in electrical
and electronic equipment (2011/65/EU)
13. Article / Part nr. / Accessory
Typ FC
PD4-M-DALI/DSI-HVAC (Master) 92699
PD4-S (Slave) 92254
LUXOMAT®Remote control:
IR-PD-DALI-1C (incl. wall bracket) 92116
IR-PD-DALI-Mini 92112
IR-RC-Adapter with smartphone app 92726
Accessories:
BSK Wire basket 92199
14. LED function indicators
LED function indicators
Process
Standard
mode
Double-locked
Initialisation time
unprogrammed Red flashes Green flashes
Initialisation time
programmed
Red flashes
quickly
Green flashes
quickly
Motion detection
Red flashes
on each
detected
movement
Green flashes
on each
detected
movement
Too bright detected
Red flashes
2x per
second
Green
flashes
2x per
second
Too bright / too dark /
undefined in opened state
Red flashes
very quickly
Green flashes
very quickly
Toggle DALI/DSI
DSI active
Red shines
3 sec.
Toggle DALI/DSI
DALI active
Green shines
3 sec.
Toggle HA/VA
HA active
White shines
permanently
Toggle Preset/User
Preset active
Red shines
3 sec.
Toggle Preset/User
User active
Green shines
3 sec.
IR signal valid received
Red and
white shine
3 sec.
IR signal invalid received Red shines
0.5 sec.
100 h function active
Red / Green
flash
alternately
Red / Green
flash
alternately
Light measurement in
progress
Green
flashes 1x in
10 sec.
Green flashes
1x in 10 sec.
Wall bracket for remote
control IR-PD-DALI-1C
IR-PD-DALI-1C
15. Putting into operation of the remote control
(optional)
Settings with remote control override the potentiometer
and DIP settings.
The DIP settings are reactivated by
• setting the potentiometers to “TEST“ and ”SUN” (see
section 24), or
• pressing the “Reset” button on the remote control in
open state
LUXOMAT®IR-PD-DALI-1C
1. Check Battery:
Open battery compartment by pressing
the plastic springs together and removing
the battery-holder.
2. Note:
Using the remote control, the occupancy detector can only be
operated brightness-depending. The setting „SUN“ can only be
chosen with potentiometer A.
When using the remote control IR-PD-DALI-1C, we recommand to
set potentiometer A to „SUN“. Pressing the RESET button on the
remote control then resets the detector to brightness-independant
mode (SUN).
!
16. Settings by remote control in open state
Unlocking device –
Activation of the
programming mode
Resetting
when open:
Deletes all
values set with
the remote
control, light
OFF.
Orientation light
on/off
Automatic reading
in the current light
value as new lumi-
nance set value
or
Dimming of the
lighting to the
desired brightness
value
Adjusting of the lumi-
nance set value from
50 to 1500 Lux:
+/– 5 Lux steps
+/– 10 Lux steps
+/–20 Lux steps
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
DSI/
DALI
Switching between DSI
and DALI program;
The Factory setting
is DALI
or
+–
Full automatic /semi-
automatic mode (se.18)
Preset/user mode
(see section 23)
max
50
Lux
1500
Lux
ON
OFF
Follow-up time
orientation light
at
1
min
10
min
optional
optionaloptional
optional
1. Start light meas-
urement by long
press of the button
(see section 17)
2. Start LED ON/OFF
by a
short press of
the button
Follow-up time
Channel 1: 1 - 30min.
Follow-up time
Channel 2 (HVAC): 5 -
60 min. or impulse
1
min
5
min
30
min
60
min
Exit programming mode
If there is no entry for
about 3 min.
the programming
mode is ended
automatically.
Permanent double lock
With this function, the
detector is permanently
locked. This mode can
only be activated during
5 sec. after closing the
detector. In this mode,
only the function „Light
ON/OFF“ can be
activated.
Red LED ashes
optional
max
50
Lux
1500
Lux
ON
OFF
t < 5 sec.

24. Reset the detector
If the double lock is activated, the detector can be opened again as
follows:
• Disconnect operating voltage
• Connect operating voltage for 31sec. to 59 sec.
• Disconnect operating voltage again
• Connect operating voltage again and wait for the self testing
• Open detector
With this procedure, the remote control programmed values are not
deleted (before activation of the double lock).
If the setting is not changed by remote control after deactivation of
the double lock, the detector changes in the double locked mode
again after a period of 30 minutes. This way the detector cannot be
unlocked during an accidental power failure.
Alternatively, the detector can be reset in this way:
Set potentiometer A to “Sun” and potentiometer B to “Test”. The de-
tector now is in test mode and the potentiometer settings are active.
All operating LEDs are flashing for three seconds.
Except of the INI ON/OFF setting, the detector is reset to factory
setting or the setting of the potentionmeter.
Pushing the “RESET” button on the remote control, in opened mode,
will delete all of the values which were set by the remote control
(beside of INI ON/OFF) and set the detector back to
its factory settings.
Factory settings
The detector is delivered with the following factory
settings: lux value: 500Lux, follow-up time: 10 minutes.
Starting the detector in the factory program the initialisation
mode starts with a constant ashing of the three operating
LEDs.
23. Manual Dimming - Preset /User
(long press when closed)
You can dim manually by pressing the external push button or the
remote control buttons "min/max" – for a long time
(> 2 sec.). When the button is released, the current dimming
value is retained. Upon renewed dimming, the dimming direction
is reversed.
max
50
Lux
1500
Lux
ON
OFF
Two different operating modes are selected
in the opened state.
Changing the mode is done by pressing the "double lock" button.
Each time the button is pressed, the current operating mode is
indicated:
Red shines for 3 sec. = Preset
Green shines for 3 sec. = User
PRESET –
the set value brightness is set during start-up operation by
the installer and remains unchanged. The set value brightness cong-
ured through manual dimming is only applied for the time being.
The constant light regulation is now deactivated! The current set
articial light is retained independent of the ambient/daylight
brightness! After switching off and then back on, the original set
set value brightness
is reset = constant light regulation is activated.
USER can only be activated via the remote control
The
set value brightness
is changed upon each manual dimming
and re-adjusted by the user. The constant light regulation remains
activated!
22. Manual Switching
(short press when closed)
max
50
Lux
1500
Lux
ON
OFF
You can switch the lighting on and off manually by pressing the
pushbutton or the remote control button “Light ON/OFF” for a
short time. It will stay on or off as long as people are detected
plus the congured follow up time.
17. Light regulation
The detector has two different integrated light control algorithms.
The set value for the rst algorithm is adjusted by potentiometer
(LUX) on the device. Very small light amounts, which shine
directly to the detector, have as result that the set value brightness
is exceeded.
The second algorithm has an integrated daylight compensation.
Therefore, it is necessary that the detector analyses the switched
light quantity. This algorithm can only be used by remote control.
The programming of the set value and the measurement of the
light quantity is carried out in two steps:
In the open state
• The set value is adjusted without daylight (please darken the
room) by using the remote control.
• Measuring the light quantity will be initiated by a long press
(> 3 sec.) of the test button. The detector turns the light on
for 5min. at 100 %. Then the light will turn on and off for a
short time and stays on after that. This measuring process
is shown by a ashing green LED (10 sec. off/ 1sec. on).
This measuring process is required for each change of the
set value.
If the setting “permant orientation light” is chosen, the func-
tion only will be active after the measuring process is done.
If the measuring process is not performed, the detector performs
it automatically when the ambient light is less than 50 lux for 1h.
MAN 8680_PD4-M-DALI/DSI-HVAC_FC_010616_2
18. Full / Semi-automatic mode
max
50
Lux
1500
Lux
ON
OFF
The mode is changed using the button "Light" in the open state.
Each time the button is pressed, the current operating mode is
indicated by the LEDs:
Red shines for 3 sec. = Full automatic mode
Green shines for 3 sec. = Semi-automatic mode
Full automatic operation
In this operating mode, the lighting switches automatically on
and off for increased comfort, depending on presence and
brightness.
Semi-automatic operation
In this operating mode, the light turns on only after a manual
switching, for an increased savings success (see section 22).
Switching off is automatically or manually
(
see section 22
).
The semi-automatic mode basically behaves like the full automatic
mode. The only difference is that the switching on has to be done
by hand.
In case motion is detected within the 10 sec. after elapse of the
follow-up time, the detector switches the light on again and the
follow-up time starts again. If there is no motion detected within
the 10 s after elapse of the follow-up time, the light has to be
turned on manually.
INI-OFF/ON mode:
Turn off or turn on the light during the self-test cycle of
60sec. The last state is active. Factory setting is that the
light is on during initialisation.
When INI OFF is chosen, the detector does not switch
on the light after voltage supply. Even upon detected
movement the light is switched on only after 60sec.
Startup behavior
:
The set value can be reached in two ways after
switching on. The detector switches the lights on at 10 %
and then adjusts upwards (min button) or it switches the
light on at 100 % and regulates down (max button).
This is confirmed by a short flashing of the red and
white LED as well as the lighting. Factory setting is that
the detector switches the light on at 100 %.
Reset of electronic ballasts
If required the connected EB can be reset and preset
parameter can be deleted. Press the button “Reset”
for 3 seconds in initialisation mode.
!
19. Settings during the Self-test cycle
In the rst 60 seconds after connecting the AC voltage, the
following functions can be set:
20. Test mode/Reset
Test mode
Use “Test” button for activating the test mode.
Use the “Reset” button to deactivate it.
Reset in closed state
The lighting is switched off, and the follow-up times are
reset.
Reset in open state
Pressing the button for >3 sec. deletes all settings
(except of INI ON/OFF) and the detector is reset to
factory state.
!
21. 100 h function
(long press (> 3 sec.) when closed)
max
50
Lux
1500
Lux
ON
OFF
Before the lamp can be dimmed, the dimming function has
to be suppressed for a certain time in order to burn in the
lamps.
T5 uorescent lamps: 80 h
T8 uorescent lamps: 100 h
For activating the function, press button
“Light ON/OFF”
in closed
state. During this time, the detector only switches the light ON or
OFF. A dimming to the set value does not take place. After having
activated the function, the red and green LED ash alternately.
By pressing the button
“Light ON/OFF”
again, it is possible to
deactivate the function before the time has elapsed.
Failure to comply to the burn-in would lead to reducing the life of
the lamp. A further disadvantage could be unwanted random vari-
ations in light intensity.
!
This manual suits for next models
2
Other LUXOMAT Security Sensor manuals

LUXOMAT
LUXOMAT PD4-M-1C-C-PS User guide

LUXOMAT
LUXOMAT PD4-M-TRIO-2DALI/DSI-1C-SM User guide

LUXOMAT
LUXOMAT PD3-2C-FC Micro User guide

LUXOMAT
LUXOMAT PD2-M-DALI/DSI-SM User manual

LUXOMAT
LUXOMAT PD9-M-1C-SDB-IP65 Supplement

LUXOMAT
LUXOMAT PD2-M-DALI/DSI-HVAC User guide

LUXOMAT
LUXOMAT PD4-M-DALI/DSI-1C-FC User guide

LUXOMAT
LUXOMAT PD2N-LTMS-RR User guide