LUXOMAT PD2-M-DALI/DSI-SM User manual

3. Putting into operation / Settings
Follow-up time for light control
The time can be set infinitely variably at between
1 and 30 minutes.
Symbol TEST: Test mode (Every movement switches on
the light for a period of 1 second, switching it off for a
period of 2 seconds after that regardless of the level of
brightness)
Twilight-switch for light control (relay 1)
The switch-on value for the light can be set at between 10
and 2000 Lux. Using the rotary control, the luminance set
points can be set as desired.
Symbol : Night-time operation
Symbol : Daytime/Night-time operation
Orientation lighting
The orientation lighting can be set at between 5 and
60min. This rotary controller serves to determine the work-
ing time of the orientation lighting.
“ON” for permanent orientation lighting.
“OFF” for deactiviation of orientation lighting.
Pulse spacing PD-Slave
2 or 9 seconds can be set for the pause between 2 pulses
sent to the master. The setting can be made with activated
() or deactivated ( ) LED indicator.
For devices with a separate slave input, 2 sec. can be set.
Installation and Operating Instruction for B.E.G.-Occupancy detectors PD2-M-DALI/DSI-SM/-FC and PD4-M-DALI/DSI-SM/-FC
A circular opening of diameter 68mm
must be produced in the ceiling. Having
connected up the cables in accordance
with regulations, the detector is inserted
into the opening as shown in the drawing
opposite and fixed into position with the
assistance of the spring clips.
2a. Installation of the LUXOMAT®PD2/PD4-M-
DALI/DSI-SM
2b.
Installation of the LUXOMAT
®
PD2/PD4-M-DALI/DSI
-FC
The detector must be installed on a solid and level surface.
The circular cover ring must be removed prior to assembly.
To do this, twist the lens (C) of the PD4 or (D) of the PD2
anticlockwise through approximately 5° and lift off.
Having connected up the wires in accordance with regula-
tions, secure the detector with 2 screws. After installation
replace the lens and lock (turn clockwise). Mains to be
connected
.
4. Settings carried out using remote control (optional)
Remote control LUXOMAT®IR-PD-DALI
1. Check Battery:
open battery compartment by pressing the plastic
springs together and removing the battery-holder.
2. IMPORTANT
Please pay attention, that the setting is Potentio-
meter 1 at “TEST” and Potentiometer 2 not at
“SUN”. All values which have been programmed
using the remote control will be deleted in the
event of power failure in the position “TEST/
SUN”. Please switch Potentiometer 2 over to
“MOON” or any other value.
Caution:
Settings with remote control override the
potentiometer settings.
LUXOMAT®PD2/PD4-M-DALI/DSI
1b. Mounting preparations
Work on the 230V mains supply
may only be carried out by quali-
fied professionals or by instructed
persons under the direction and
supervision of qualified skilled elec-
trical personnel in accordance with
electrotechnical regulations.
Disconnect supply before installing!
When in Master/Slave mode of
operation, the Master-appliance
must always be installed at the
location where there is least
daylight.
5. Option:
Wall bracket for remote control
IR-PD-DALI
The product enters an initial 60-second
self-test cycle, when the supply is first
connected. The occupancy detector is
ready for operation.
2c. Self test cycle
1a. Features
*
For connection of up to 50 lamps
* Suitable for dimmable electronic
ballasts and control modules
* DALI output
* Constant light control
* Manual switching/dimming
* Semi or completely automatic
operation
*
Luminance (brightness) set point,
switch-off delay time for LIGHT and
orientation-light adjustable
* Sensor and power sections in one
housing
* Infrared remote control
close
open
25 22
18
1
6
10
3
1
TEST 6
30
R1
120 6050
40
30
15
10
A
16 10 5
2
1
30
15
TEST
2000
1200
600
200
40
5
60
5
10
30
50
ON
OFF
GB
1
1 2
2
25 22
18
1
6
10
3
1
TEST 6
30
R1
120 6050
40
30
15
10
A
16 10 5
2
1
30
15
TEST
2000
1200
600
200
40
5
25 22
18
1
6
10
3
1
TEST 6
30
R1
2000
1200
600
200
40
C
D
2000
1200
600
200
40
68 mm
9s 2s
LED ON
LED OFF
IR-PD-DALI
6. Settings by remote control when open 7. Key functions in closed state
Unlocking device - Activation of
the programming mode
Locking device – Exit program-
ming mode
Resetting when
open
: Deletes
all values set
with the remote
control, light
OFF.
Follow-up time light
Orientation lighting on/off
Automatic reading in the
current light value as new
luminance set point
Permanent protection against
sabotage
LED ashes
or Dimming of the lighting on the
desired luminance value
Adjusting of the luminance set point
+ / – small steps
+/ –big steps
1
min to 30
min
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
DSI/
DA LI
Switching between DSI and
DALI program
or
+–
Fully automatic/semi automatic
mode => (see page 2, point 8)
Preset/user mode
=> (see page 2, point 9)
max
50
Lux
1500
Lux
ON
OFF
Orientation lighting and its
follow-up time
to
1
min
10
min
max
50
Lux
1500
Lux
ON
OFF
t < 5 sec.
Lock device
Test mode
Reset to deactivate
Resetting when closed
The lighting relay is switched off, i.e. opened and the
follow-up times reset.
Permanent protection against sabotage
This function blocks the unit permanently (green LED is illumi-
nated). This operating mode can only be activated during the
period of 5 seconds after pressing the “lock“ button. This status
will only permit actuating the function “Light on/Light off”.
The procedure for leaving this mode is as follows:
1. Switch off the current
2. Apply current for 31 – 59 seconds
3. Switch of the current again
4. Apply current
5. Open detector
Light on/off when closed
=> (see page 2, point 10)
The light will remain switched on/off for as long as movements
are detected in the areas of coverage. Once the last movement
has been detected, the light will remain on for the duration of
the follow-up time as per setting.
The appliance will then return independently to the mode
selected (Fully or Semi-automatic).
max
50
Lux
1500
Lux
ON
OFF
t < 5 sec.

Sensor and power supply in one case
Power supply: 230 V~ ±10 %
Power consumption: < 1W
Ambient temperature: -25°C to +50°C
Degree of protection/class:
PD2-M-DALI/DSI-SM IP20, with accessory IP54
PD2/PD4-M-DALI/DSI-FC IP20 / II
Settings:
locally and by remote control
Light values - IR-PD-DALI:
50 - 1500Lux
Parallel operation:
Master/Slave
Area of coverage:
circular 360°
Range of coverage Ø H 2.5m / T=18°C:
PD2-M-DALI/DSI seated 4m / tangential 10 m /
radial 6 m
PD4-M-DALI/DSI seated 6.4m / tangential 24 m /
radial 8 m
Recommended height for mounting:
2 - 3 m
Light measurement: Mixed light, daylight + artificial
light
Lux values-Potentiometer:
10 - 2000 Lux
• DALI-Output
digital BUS control wire, 2-core, no polarity (broadcast only)
Max. no. of series-connected electronic ballasts:
PD2/PD4-M-DALI/DSI-DE up to 50
PD2/PD4-M-DALI/DSI-AP up to 50
Time-settings:
1 - 30min. / test
Dimensions HxØ [mm]
SM FC
PD2-M-DALI/DSI 50x 97 84,5 x 74
PD4-M-DALI/DSI 73 x 101 97 x 103
Technical data PD2/PD4-Slave
Power supply: 230 V~ ±10 %
Impulse output: Optocoupler max. 2W
Impulse duration: 2 sec. or 9 sec.
Dimensions: see above
Declaration of Conformity:
The product complies with the
low voltage recommendation 2006/95/EC and the EMV
recommendation 2004/108/EC.
14.
Technical data
PD2/PD4-M-DALI/DSI
12. Wiring diagram
10.
PD2/PD4-M-DALI/DSI
- Connections
Type SM FC
PD2-M-DALI/DSI-Master 92280 92258
PD4-M-DALI/DSI-Master 92279 92275
PD2-Slave 92152 92166
PD4-Slave 92142 92254
LUXOMAT®Remote control:
IR-PD-DALI (incl. wall bracket) 92094
Accessory:
BSK Ball basket guard 92199
Wall bracket for remote control as replacement
92100
SM-Socket IP54 92161
15. Article / Part nr. / Accessory
MAN 5632 – 120711–3
16. LED-functional indicators
LED function indicators
Process Standard
mode Double-locked
Initialisation time
unprogrammed Red flashes Green
flashes
Initialisation time
programmed
Red flashes
quickly
Green flashes
quickly
Motion detection
Red flashes
on each
detected
movement
Green flashes
on each
detected
movement
Too bright detected
Red flashes
2x each
second
Green flashes
2x each
second
Too bright / too dark /
undefined in opened state
Red flashes
very quickly
Green flashes
very quickly
Switching DALI/DSI
DSI active
Red shines
3 sec.
Switching DALI/DSI
DALI active
Green shines
3 sec.
Switching HA/VA
VA active
Red shines
3 sec.
Switching HA/VA
HA active
Green shines
3 sec.
Switching Preset/User
Preset active
Red shines
3 sec.
Switching Preset/User
User active
Green shines
3 sec.
IR signal valid received Red shines
3 sec.
IR signal invalid received Red shines
0,5 sec.
1
2
quer zum Melder gehen
frontal zum Melder gehen
Unterkriechschutz
walking across
walking towards
seated
11. Range of Coverage
9. Manual Dimming – Preset / User
(for IR-PD-DALI functions see page 1)
You can dim manually by pressing the pushbutton for
a long time (> 2 sec.). When the button is released,
the current dimming value is retained. Upon renewed
dimming, the dimming direction is reversed.
PRESET –the luminance set point is set during start-up
operation by the installer and remains unchanged.
The luminance set- point congured through manual
dimming is only applied for the time being.
Caution:
The constant light regulation is now deactivated!
The currently set articial light is retained independent
of the ambient/daylight brightness!
After switching off and then back on, the originally set
luminance set-point is reset = constant light regulation
is activated.
USER – can only be activated via the remote control!
The luminance set-point is changed upon each manual
dimming and re-adjusted by the user.
The constant light regulation remains activated!
8. Fully/ Semi automatic mode
(for IR-PD-DALI functions see page 1)
Toggle between fully and semiautomatic operation by
switching the button in opened state. The relevant status
is shown by ashing of the red and green LED.
Fully automatic operation
In this operating mode, the lighting switches automati-
cally on and off for increased comfort, depending on
presence and brightness.
Semiautomatic operation
(Semiautomatic can only be activated via the remote
control!)
In this operating condition, in order to gain increased
savings, the lighting is energized only after being manu-
ally switched on.
Switch-off takes place automatically.
The semiautomatic mode basically behaves like the fully
automatic one. However, the difference is that switching-
on must always be carried out manually!
As many (closer-contact) buttons as desired can be wired
in parallel on the “S” button input (ON/OFF Dimm).
10. Manual Switching
You can switch the lighting on and off manually by
pressing the pushbutton for a short time. It will stay on or
off as long as people are detected plus the congured
follow up time.
PD4-M-DALI/DSI
24 m
8 m
6.40 m
24 m
360°
2.50 m
2
1
PD2-M-DALI/DSI
10 m
6 m
4 m
10 m
360°
2.50 m
2
1
WE RECOMMEND THAT BEFORE DIMMING OF THE CONNECTED
LIGHTS A 100h BURN IN (T5 TUBES OR 80 HOURS FOR T8 TUBES)
FUNCTION TAKES PLACE.
THE LIFESPAN OF THE LAMPS CAN BE REDUCED IF THE BURN IN
DOES NOT TAKE PLACE.
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
max
50
Lux
1500
Lux
ON
OFF
13. PD2/PD4-M-DALI/DSI – Connections
Standard mode with master DALI occupancy detectors
L
N
L
N
R
R
Slave
Slave
L L
L
S
S
N N
N
–
–
+
+
R
R
T1
T1
DA +
DA –
DA +
DA –
PD2/PD4-M-DALI/DSI-SM
PD2/PD4-M-DALI/DSI-FC
This manual suits for next models
3
Other LUXOMAT Security Sensor manuals

LUXOMAT
LUXOMAT PD3-2C-FC Micro User guide

LUXOMAT
LUXOMAT PD2N-LTMS-RR User guide

LUXOMAT
LUXOMAT PD9-M-1C-SDB-IP65 Supplement

LUXOMAT
LUXOMAT PD4-M-1C-C-PS User guide

LUXOMAT
LUXOMAT LUXOMAT net PD4-M-DALI User guide

LUXOMAT
LUXOMAT PD4-M-TRIO-2DALI/DSI-1C-SM User guide

LUXOMAT
LUXOMAT PD2-M-DALI/DSI-HVAC User guide

LUXOMAT
LUXOMAT PD4-M-DALI/DSI-1C-FC User guide