3. Putting into operation / Settings
Follow-up time for light control
The time can be set infinitely variably at between
1 and 30 minutes.
Symbol TEST: Test mode (Every movement switches on
the light for a period of 1 second, switching it off for a
period of 2 seconds after that regardless of the level of
brightness)
Twilight-switch for light control (relay 1)
The switch-on value for the light can be set at between 10
and 2000 Lux. Using the rotary control, the luminance set
points can be set as desired.
Symbol : Night-time operation
Symbol : Daytime/Night-time operation
Orientation lighting
The orientation lighting can be set at between 5 and
60min. This rotary controller serves to determine the work-
ing time of the orientation lighting.
“ON” for permanent orientation lighting.
“OFF” for deactiviation of orientation lighting.
Pulse spacing PD-Slave
2 or 9 seconds can be set for the pause between 2 pulses
sent to the master. The setting can be made with activated
() or deactivated ( ) LED indicator.
For devices with a separate slave input, 2 sec. can be set.
Installation and Operating Instruction for B.E.G.-Occupancy detectors PD2-M-DALI/DSI-SM/-FC and PD4-M-DALI/DSI-SM/-FC
A circular opening of diameter 68mm
must be produced in the ceiling. Having
connected up the cables in accordance
with regulations, the detector is inserted
into the opening as shown in the drawing
opposite and fixed into position with the
assistance of the spring clips.
2a. Installation of the LUXOMAT®PD2/PD4-M-
DALI/DSI-SM
2b.
Installation of the LUXOMAT
®
PD2/PD4-M-DALI/DSI
-FC
The detector must be installed on a solid and level surface.
The circular cover ring must be removed prior to assembly.
To do this, twist the lens (C) of the PD4 or (D) of the PD2
anticlockwise through approximately 5° and lift off.
Having connected up the wires in accordance with regula-
tions, secure the detector with 2 screws. After installation
replace the lens and lock (turn clockwise). Mains to be
connected
.
4. Settings carried out using remote control (optional)
Remote control LUXOMAT®IR-PD-DALI
1. Check Battery:
open battery compartment by pressing the plastic
springs together and removing the battery-holder.
2. IMPORTANT
Please pay attention, that the setting is Potentio-
meter 1 at “TEST” and Potentiometer 2 not at
“SUN”. All values which have been programmed
using the remote control will be deleted in the
event of power failure in the position “TEST/
SUN”. Please switch Potentiometer 2 over to
“MOON” or any other value.
Caution:
Settings with remote control override the
potentiometer settings.
LUXOMAT®PD2/PD4-M-DALI/DSI
1b. Mounting preparations
Work on the 230V mains supply
may only be carried out by quali-
fied professionals or by instructed
persons under the direction and
supervision of qualified skilled elec-
trical personnel in accordance with
electrotechnical regulations.
Disconnect supply before installing!
When in Master/Slave mode of
operation, the Master-appliance
must always be installed at the
location where there is least
daylight.
5. Option:
Wall bracket for remote control
IR-PD-DALI
The product enters an initial 60-second
self-test cycle, when the supply is first
connected. The occupancy detector is
ready for operation.
2c. Self test cycle
1a. Features
*
For connection of up to 50 lamps
* Suitable for dimmable electronic
ballasts and control modules
* DALI output
* Constant light control
* Manual switching/dimming
* Semi or completely automatic
operation
*
Luminance (brightness) set point,
switch-off delay time for LIGHT and
orientation-light adjustable
* Sensor and power sections in one
housing
* Infrared remote control
close
open
t < 5 sec.
Lock device
Test mode
Reset to deactivate
Resetting when closed
The lighting relay is switched off, i.e. opened and the
follow-up times reset.
Permanent protection against sabotage
This function blocks the unit permanently (green LED is illumi-
nated). This operating mode can only be activated during the
period of 5 seconds after pressing the “lock“ button. This status
will only permit actuating the function “Light on/Light off”.
The procedure for leaving this mode is as follows:
1. Switch off the current
2. Apply current for 31 – 59 seconds
3. Switch of the current again
4. Apply current
5. Open detector
Light on/off when closed
=> (see page 2, point 10)
The light will remain switched on/off for as long as movements
are detected in the areas of coverage. Once the last movement
has been detected, the light will remain on for the duration of
the follow-up time as per setting.
The appliance will then return independently to the mode
selected (Fully or Semi-automatic).