INSTRUCTION MANUAL
WEB-ENABLED REMOTE TERMINAL UNIT MODEL DL30
BEFORE USE ....
Thank you for choosing M-System. Before use, please check
contents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact M-System’s Sales Office or representatives.
■PACKAGE INCLUDES:
Web-enabled remote terminal unit ....................................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
For detailed explanations to operate this product, please
refer to Users Manual (EM-8571-G), downloadable at M-
System’s web site: http://www.m-system.co.jp
POINTS OF CAUTION
■CONFORMITY WITH EU DIRECTIVES
• The equipment must be mounted inside the instrument
panel of a metal enclosure.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures to ensure the CE conform-
ity.
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
24V DC rating: 24V ±10%, approx. 18W
■GENERAL PRECAUTIONS
• Before you remove the unit or mount it, turn off the power
supply for safety.
• The unit is not hot swappable. When the unit is used in
combination with R30 I/O modules, the R30 I/O modules
also cannot be hot swapped.
• Before you remove the terminal block or mount it, turn off
input signal for safety.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within 0 to 50°C (32
to 122°F) with relative humidity within 10 to 90% RH in
order to ensure adequate life span and operation.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
• Max. wiring length for FE terminal should be 3 m.
• Be sure to attach the terminal cover for safety.
■ABOUT SD CARDS
• Do not turn off the power of the unit during writing data.
Insert or eject an SD card according to the specified pro-
cedure.
• Confirm the front and back side when inserting an SD
card to the unit.
■CALENDAR CLOCK
• A backup battery is employed for calendar clock IC. Back-
up period without power supply is approx. 2 years.
• In order to prevent battery drain, battery back up is OFF
at factory default. Turn it ON prior to start using.
• With power on, the battery is not drained. When total
power off period is approx. 2 years, the battery cannot
backup the calendar clock. The calendar clock cannot
keep correct date and time.
• The battery is not replaceable by customer. When re-
placement is required, consult M-System.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.

DL30
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8571-A P. 2 / 6
COMPONENT IDENTIFICATION
Status Indicator LEDs
RJ-45 Connector
for Ethernet
Lock Tab
Specifications
Ethernet Indicator LEDs
SD Card Slot
■FRONT VIEW
■BOTTOM VIEW
■SIDE VIEW
Configuration Select SW
Logging Button
SD Button
Function Setting DIP SW
Terminal Block for
RUN Contact Output,
Power Supply
Terminal Fixing Screw
Base Fixing Screw
ON
4
3
2
1
DL30 RUN
LOGGING
SD CARD
MAINT
PWR
RUN
ERROR
CFG
DPX
LNK
LOGGING
SD CARD
DL30
2
I/O
On
4
3
1
Configuration Connector
U
(
+
)
NC
V
(
-
)
FE
Positioning Guide
Terminal Cover

DL30
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8571-A P. 3 / 6
■STATUS INDICATOR LED
LED COLOR FUNCTION
PWR Green ON when power supply is on
OFF when power supply is off
RUN Green ON in normal operation *1
OFF in abnormality (internal memory error, SD card error, R30 module error) *1
DL30 RUN Green
ON after boot-up
OFF in abnormality (IP address unassigned)
Blinking while the DL30 module is in communication.
LOGGING Green OFF when logging is stopped.
ON while logging
SD CARD Green
ON when SD card is recognized.
Blinking while the SD card is being accessed.
OFF when SD card is not recognized or removed.
MAINT Orange ON when the mail reporting is disabled or in the maintenance mode.
OFF in normal operation
ERROR Red
Blinking in abnormality
(internal memory error, SD card error, R30 module error) *1
OFF in normal operation *1
*1. RUN contact output turns on in normal operation, and turns off when the power is not supplied or in abnormality
(internal memory error, SD card error, R30 module error).
■ETHERNET INDICATOR LED
LED COLOR FUNCTION
DPX Green ON during full duplex transmission
LNK Amber ON while link is established.
■CONFIGURATION SELECT SW
(*) Factory setting
SW POSITION CONFIGURATION OBJECT
DL30 DL30 configuration (*)
I/O R30 I/O modules configuration
■DIP SW
(*) Factory setting
• DL30 CONFIGURATION USB CONNECTION SETTING
SW1
DL30 CONFIGURATION USB CONNECTION
OFF DL30GCFG
ON Terminal software program
• MAIL REPORTING SETTING
SW2 MAIL REPORTING
OFF Enable (*)
ON Disable
• MAINTENANCE MODE SETTING
SW3 MAINTENANCE MODE
OFF Disable (*)
ON Enable (Logging and e-mailing halted)
• CALENDAR CLOCK BATTERY BACKUP SETTING
SW4 CALENDAR CLOCK BATTERY BACKUP
OFF Disable (*)
ON Enable
Note: In order to prevent battery drain, battery back up is
OFF at factory default. Turn it ON prior to start using.
■LOGGING BUTTON
Pressing and holding 1 second starts and stops logging.
■SD BUTTON
Pressing and holding for 4 seconds turns SD CARD LED off
and makes the card removable.
■TERMINAL ASSIGNMENT
4
5
NC
FE
6
1
2
U(+)
3
V(
-
)
NO. ID FUNCTION
1 RUN contact output RUN contact output
2 U (+) Power supply (24 V DC)
3 V (-) Power supply (0 V DC)
4 RUN contact output RUN contact output
5 NC Not used
6 FE Functional earth

DL30
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8571-A P. 4 / 6
INSTALLATION
■INSTALLATION TO THE BASE
Use the Installation Base Model: R30BS.
Mount the unit to the PWR and COM slot in the base.
PWR COM I/O1 I/O n
■HOW TO MOUNT THE MODULE ON THE BASE
1) Engage the positioning guide of the module with the In-
stallation Base.
2) Pivot the module on the positioning guide and press it
down until the lock tab sits into place.
Positioning Guide
3) Tighten the base fixing screw with a screw driver (stem
length: 70 mm/2.76” or more) (torque 0.5 N·m)
Base Fixing
Screw
■HOW TO REMOVE THE MODULE
1) Loosen the base fixing screw with a screw driver (stem
length: 70 mm/2.76” or more).
Base Fixing
Screw
2) While pressing the projection on the lock tab, push the
module upward.
3) Detach the positioning guide of the module from the In-
stallation Base.
Lock Tab

DL30
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8571-A P. 5 / 6
TERMINAL CONNECTIONS
Connect the unit as in the diagram below.
■EXTERNAL DIMENSIONS unit: mm (inch)
50 (1.97)
110 (4.33)
6–M3
SCREW
6
(.24)
1
2
3
4
5
6
DIN RAIL
35mm wide
[5 (.20)]
110 (4.33)
98 (3.86)
■CONNECTION DIAGRAM
In order to improve EMC performance, bond the FE terminal to ground.
Caution: This terminal is NOT a protective conductor terminal.
INTERNAL
POWER
INTERNAL
BUS
INTERNAL
POWER
Ethernet
Configuration
2
3
6
1
SD CARD SLOT
CONNECTOR
RJ-45 CONNECTOR
4
U (+)
V (–)
FE
POWER SUPPLY
RUN CONTACT OUTPUT
CONNECTORCONNECTOR

DL30
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
EM-8571-A P. 6 / 6
WIRING INSTRUCTIONS
■TORQUE
Wiring screw for separable terminal: 0.5 N·m
Fixing screw for separable terminal: 0.5 N·m
■SOLDERLESS TERMINAL unit: mm (inch)
Refer to the drawing below for recommended ring tongue terminal size.
Spade tongue type is also applicable.
Solderless terminals with insulation sleeve do not fit.
Recommended manufacturer: Japan Solderless Terminal MFG.Co.Ltd, Nichifu Co.,Ltd
Applicable wire size: 0.25 – 0.75 mm2
12 max.
6 max.
3 max.
3.2 dia.
■HOW TO REMOVE THE SEPARABLE TERMINAL
The separable terminal of the unit is 2 piece constructions.
It is possible to remove the terminal by loosening two screws of terminal alternately.
Table of contents
Popular Remote Control manuals by other brands

Universal Remote Control
Universal Remote Control UR3-EXP operating instructions

TANDBERG
TANDBERG RC 20 operating instructions

Fujitsu
Fujitsu Airstage UTY-DCGYZ1 operating manual

GRAUPNER
GRAUPNER X-8E manual

Advent Controls
Advent Controls A5 Installation and setup manual

Daikin
Daikin BRC52B61 operating manual