EDUS39-605 Control Devices
Controls 9
2.1.7 Field Setting Wired Remote Controller BRC1C71
Field Setting Contents and Code No.
If optional accessories are mounted on the indoor unit, its settings may have to be changed. Refer to the instruction manual
for each setting. Procedure
1. When in the normal mode, press the
button for a minimum of four seconds, and the
FIELD SET MODE is entered.
2. Select the desired MODE NO. with the
button O.
3. During group control, when setting by each
indoor unit (mode No. 20, 21 and 23 have
been selected), push the button (P) and
select the INDOOR UNIT NO to be set. This
operation is unnecessary when setting by
group.
4. Push the upper button Qand select
FIRST CODE NO.
5. Push the lower button Rand select the
SECOND CODE NO.
6. Push the button Sonce and the present
settings are SET.
7. Push the button Tfor about one second
to return to the NORMAL MODE.
Example: If set for group setting and the time to clean air filter is set to: FILTER CONTAMINATION-HEAVY,you should set
MODE NO. to [10], FIRST CODE NO. to [0] and SECOND CODE NO. [02].
Mode No.
Note)1
FIRST
CODE No. Description of Settings SECOND CODE NO. Note)4
01 02 03 04
10(20)
0
Filter Contamination-Heavy/
Light: Setting for display time
to clean air filter. Time alert to
clean air filter is cut in half
when heavy filter
contamination.
UltraLong-Life
Type
Light
Approx.
10,000
hours
Heavy
Approx.
5,000
hours
——
Long-Life Type
Approx.
2,500
hours
Approx.
1,250
hours
Standard Type Approx.
200 hours
Approx.
100 hours
1
Long-life or Standard filter type: Setting of filter
indication time. Change setting to Ultralong-life
filter if one is installed
Long-Life
Filter
Ultra-Long-
Life Filter ——
2 Thermostat Sensor in Remote Controller Use Not Use — —
3Display Time to Clean Air Filter Calculation (Set
when filter sign is not to be displayed Display Do not
Display ——
12(22)
0Optional accessories output selection field
selection of output for adaptor for wiring
Indoor Unit
Turned ON by
Thermostat
—Operation
Output
Malfunction
Output
1ON/OFF Input from Outside: Set when ON/OFF is
to be controlled from outside. Forced Off ON/OFF
Control
External
Protection
Device
—
2
Thermostat Differential Changeover: Set when
remote sensor is to be used.
FXFQ only
1°C 0.5°C — —
4
Automatic mode differential: Automatic
temperature differential setting for VRV system
heat recovery series cool/heat
01 : 0 02 : 1 03 : 2 04 : 3 05 : 4 06 : 5 07 : 6 08 : 7
5 Power failure automatic reset: Auto Restart Not equipped Equipped — —
13(23)
1Selection of Air Flow Direction: Set when a blocking
pad kit has been installed FXFQ only
F
(4 directions)
T
(3 directions)
W
(2 directions) —
4 Field set airflow position setting Draft
Prevention Standard Ceiling Soiling
Prevention —
5Field set fan speed selection: Fan speed control by
air discharge outlet for phase control Standard Optional
Accessory 1
Optional
Accessory 2 —
TEST
SETTIING
Unit NO.
UNIT NO.
SECOND
CODE NO.
MODE NO.
FIELD
SET
MODE
FIRST
CODE NO.
2P068938
1 7
6
34
52