2.0 Configuration and Modbus map
User’s Manual GW-DLMS-485-ELSA15 Page 9
2.3 Modbus Mapping Area
The data read from the meters are placed in the Holding Register area.
A copy of the values is also present in the 4x20000 holding register area.
Refresh time of the values is approximately: Time between readouts * N, where N is the number of
energy meters connected to gateway and configured with a serial number different from zero in
HomeDLMS.
Modbus addresses in the table are base 1; depending on used Modbus master, sometimes is
required to swap words to read data correctly.
OBIS
INDEX METER 1
DATA
TYPE OBIS
TYPE NOTES
- 4x40000 UINT DI_00 Digital Input 00
- 4x40001 UINT DI_01 Digital Input 01
- 4x40002 UINT DO_00 Digital Output 00
- 4x40003 UINT DO_01 Digital Output 01
- 4x40004 4x40006 4x40008 4x40010 UDINT SERIAL
Error number from gateway
0 4x40016 4x40216 4x40416 4x40616 DINT 0.9.1 Time
1 4x40018 4X40218 4x40418 4x40618 DINT 0.9.2 Date
2 4x40020 4x40220 4x40420 4x40620 DINT F.F Error code
3 4x40022 4x40222 4x40422 4x40622 DINT F.F.1 Error code
4 4x40024 4x40224 4x40424 4x40624 DINT F.F.2 Error code
5 4x40026 4x40226 4x40426 4x40626 DINT F.F.3 Error code
6 4x40028 4x40228 4x40428 4x40628 FLOAT C.1.0
7 4x40030 4x40230 4x40430 4x40630 FLOAT 0.2.1
8 4x40032 4x40232 4x40432 4x40632 FLOAT C.3
9 4x40034 4x40234 4x40434 4x40634 FLOAT C.4
10 4x40036 4x40236 4x40436 4x40636 FLOAT C.5
11 4x40038 4x40238 4x40438 4x40638 FLOAT 1.8.0 Sum Li Active Energy+ (QI+QIV)
12 4x40040 4x40240 4x40440 4x40640 FLOAT 1.8.0* Sum Li Active Energy+ (QI+QIV) - prev. period
13 4x40042 4x40242 4x40442 4x40642 FLOAT 1.6.1 Max Active Power - Import - Tariff 1 (kW)
14 4x40044 4x40244 4x40444 4x40644 FLOAT 1.6.1* Max Active Power - Import - Tariff 1 (kW) - previous period
15 4x40046 4x40246 4x40446 4x40646 FLOAT 1.2.1 Max Cumulative Active Power - Import - Tariff 1 (kW)
16 4x40048 4x40248 4x40448 4x40648 FLOAT 1.2.1* Max Cumulative Active Power - Import - Tariff 1 (kW) - prev. period
17 4x40050 4x40250 4x40450 4x40650 FLOAT 5.8.0 Sum Li Reactive Energy QI
18 4x40052 4x40252 4x40452 4x40652 FLOAT 5.8.0* Sum Li Reactive Energy QI - previous period
19 4x40054 4x40254 4x40454 4x40654 FLOAT 8.8.0 Sum Li Reactive Energy QIV
20 4x40056 4x40256 4x40456 4x40656 FLOAT 8.8.0* Sum Li Reactive Energy QIV - previous period
21 4x40058 4x40258 4x40458 4x40658 FLOAT 2.8.0 Sum Li Active Energy- (QII+QIII)
22 4x40060 4x40260 4x40460 4x40660 FLOAT 2.8.0* Sum Li Active Energy- (QII+QIII) - previous period
23 4x40062 4x40262 4x40462 4x40662 FLOAT 2.6.1 Max Active Power - Export - Tariff 1 (kW)
24 4x40064 4x40264 4x40464 4x40664 FLOAT 2.6.1* Max Active Power - Export - Tariff 1 (kW) - prev. period
25 4x40066 4x40266 4x40466 4x40666 FLOAT 2.2.1 Max Cumulative Active Power - Export - Tariff 1 (kW)
26 4x40068 4x40268 4x40468 4x40668 FLOAT 2.2.1* Max Cumulative Active Power - Export - Tariff 1 (kW) - prev. period
27 4x40070 4x40270 4x40470 4x40670 FLOAT 7.8.0 Sum Li Reactive Energy QIII