STD2 (Standard 2) Series
Unheated
ModelLengths36”–144”
14716 S. BROADWAY, GARDENA, CA 90248 ●Ph: (310)532-1555 Fax: (310)-532-3030 ●www.marsair.com
© Copyright Mars Air Systems, LLC 2014
NOTE:MARSAIRSYSTEMS,LLCreservestherighttochangespecificationsandproductdesignwithoutnotice.Suchrevisionsdonotentitlethebuyertocorrespondingchanges,improvements,additions,orreplacements
forpreviouslypurchasedequipment.
MARSAIRSYSTEMS,LLC
●
GARDENA,CA
●
USA
VM,04/07/22
Model Distance from
nozzel (in)
Avg. Core Velocity
(FPM)
40 1207
80 856
120 710
160 637
200 588
Projection Velocity
STD236-1U*
STD2
Series: Standard 2
72 2 UHOB
LENGTH OF UNIT
# OF MOTORS
U = UNHEATED
VOLTAGE CODE
COLOR
EXAMPLE
115v/1Ø
(A)
208/230v/1Ø
(D)
208/230v/3Ø
(G)
460v/3Ø
(H)
575v/3Ø
(I)
STD236-1U*-OB 5.1 2.5 1.8/1.6 0.8 0.7
STD242-1U*-OB 5.1 2.5 1.8/1.6 0.8 0.7
STD248-1U*-OB 5.1 2.5 1.8/1.6 0.8 0.7
STD260-2U*-OB 10.2 5.0 3.6/3.2 1.6 1.4
STD272-2U*-OB 10.2 5.0 3.6/3.2 1.6 1.4
STD284-2U*-OB 10.2 5.0 3.6/3.2 1.6 1.4
STD296-2U*-OB 10.2 5.0 3.6/3.2 1.6 1.4
STD2108-3U*-OB 15.3 7.5 5.4/4.8 2.4 2.1
STD2120-3U*-OB 15.3 7.5 5.4/4.8 2.4 2.1
STD2144-3U*-OB 15.3 7.5 5.4/4.8 2.4 2.1
* - Use corresponding letters in "Electrical Data" colum ns to complete the model numbers.
F or tota l FL A, m u ltip ly m o tor F LA b y # of m o tor s; Am p ac ity ( M CA) = to tal F LA X 1.2 5
Electrical Data
Full Load Amp
(FLA)
Single Phase Three Phase
Unit Voltage (Voltage Code)
AlternatevoltagecodeswithFLAdata:
277v/1Ø/60Hz(L)‐ 2.7Apermotor
220v/1Ø/50Hz(U)‐ 2.5Apermotor
380/415v/3Ø/50Hz(W)‐ 1.1Apermotor
ExplosionproofmotorFLAdata(INS‐XP‐STD2):
115v/1Ø/60Hz(A)‐ 7.4Apermotor
208/230v/1Ø/60Hz(D)‐ 3.7Apermotor
208/230v/3Ø/60Hz(G)‐ 1.8/1.6Apermotor
460v/3Ø/60Hz(H)‐ 0.8Apermotor
WashdownmotorFLAdata(INS‐WD‐STD2):
115v/1Ø/60Hz(A)‐ 7.4Apermotor
208/230v/1Ø/60Hz(D)‐ 3.9/3.7Apermotor
208/230v/3Ø/60Hz(G)‐ 2.1/2.0Apermotor
460v/3Ø/60Hz(H)‐ 1.0Apermotor
MARS Air Systems, LLC certifies that the Air Curtains shown on this data
sheet are licensed to bear the AMCA seal. The ratings shown are based
on tests and procedures performed in accordance with AMCA Publication
211 and comply with the requirements of the AMCA Certified Ratings
Program.
The AMCA Certified Ratings Seal applies to airflow rate, average outlet
velocity, outlet velocity uniformity, velocity projection and power rating at
free delivery only.
NOTE: Models STD260-2, STD264-2, STD278-2, STD296-3, and
STD2108-2 are not AMCA Certified.
Unheated Data Sheet
Applications: Environmental Separation (up to 12’) andInsect Control (up to 10’)
Features:
1/2HPContinuousDutyTEAOMotors(NEMA1)
Sleekself‐containedone‐pieceheavygaugecorrosionproofpaint
lockmetaldesign
ETLCertifiedtoconformtoUL507(US)andCSA22.2(Canada)Standards(Indoor/OutdoorUse)
AMCACertifiedtoAMCA211(seetableaboveformodelsavailable)
(4)7/16”topandwallmountingholesprovided,(2)oneachend
Cabinethassufficientstrengthforfasteningtowallonbothendswithoutintermediatesupport
Adjustableairdirectionalvaneswith40°sweepfronttoback
StandardcolorisObsidianBlack
Rustpreventativeelectrostaticpolyurethanepowdercoating
5‐yearpartswarranty
FreightIncluded(FOBContinentalUSA)
ProudlyMadeintheUSA
Note:AllSTD2(1)motorunitsupto48”areshippedwiththeMotorFanAssembly(MFA)factoryinstalledinsidetheaircurtain
housing.Forallothermodels,theMFAareshippedloosetominimizefreightdamage
MarsRecommendedAccessories(SeeSubmittalsforadditionaldetails):
DoorLimitSwitches
o99‐014,Combinationmechanicalswitch,250v,1HPMax
o99‐125,Industrialsurfacemountedmagneticswitch(controllerrequired)
Controllers
oMCPA‐†U*,MotorControlPanel,120Vcontrolvoltage(†=#ofMotors,*=VoltageCode)
oMCP‐TD,Adjustabletimedelay,1sec‐100hr(panelrequired)
oMCP‐24V,Lowvoltagecontroloption(panelrequired)
oBMS‐303,BMSformonitorandcontrol(panelrequiredwithMCP‐24V)
Note:Drycontactprovidedinpanelformonitoringmotor.24Vacsignalprovidedfrompanelforcontrollingmotor
oSK‐UU,SimpleLink,115V‐230V,1PH,2Mtr&1HPmax,IntegralControl,Nema1(housingdepthwill
be173/8”deep)
Brackets
oB0004,Adjustablemountingbracketset,3½”clearance
oB0005,Adjustablemountingbracketset,7”‐13”clearance
oB0041,TransommountingbracketsetforSTD2
Filters
oJ21**‐Ɨ,¼”aluminumpressedframebankfilters(**=ModelLength,Ɨ=#ofMotors)
CleanAirSeriesSections
oHEC2**‐OB,HEPACSection(**=ModelLength)
oUVCS**‐*‐OB,UVSection(**=ModelLength,*=VoltageCode)
SevereDutyandFinish
oHSG‐304SS‐STD,304Stainlesssteelhousingconstruction
oINS‐WD‐STD2,Washdownmotorfanassembly,IP54
oINS‐XP‐STD2,Explosionresistantmotorfanassembly,
Class1,Division1,GroupD(TENV)
Note:Washdownandexplosionproofunitswillrequirehighermotor
amperage.ControlpanelwillrequireOL/MPwithhigheramperagerange(use
MCP‐MWDorMCP‐MXPaccessory)
SoundLevels:(measuredat10’inanopenfield)
1MotorUnit=66dBA,2MotorUnit=68dBA,3MotorUnit=71dBA,&
4MotorUnit=73dBA
STD2 (Standard)
Series 2
Model Number Nozzle Length
(in)
Length
(in)
Depth
(in)
Height
(in)
Motor
(hp)
Weight
(lbs)
Max Core Velocity
at Nozzle (fpm)
Avg Velocity
(fpm)
Volume
(cfm)
Uniformity
(%)
Power Rating
(watts)
STD236-1U*-OB 36 36 13 11 1/2 60 5960 2206 1379 84 500
STD242-1U*-OB 42 42 13 11 1/2 65 4865 1945 1418 87 510
STD248-1U*-OB 48 48 13 11 1/2 70 4247 1730 1442 85 550
STD260-2U*-OB 60 60 13 11 Two 1/2 90 6737 2592 2700 93 940
STD272-2U*-OB 72 72 13 11 Two 1/2 120 5960 2206 2758 84 1000
STD284-2U*-OB 84 84 13 11 Two 1/2 125 4865 1945 2836 87 1020
STD296-2U*-OB 96 96 13 11 Two 1/2 135 4247 1730 2884 85 1100
STD2108-3U*-OB 108 108 13 11 Three 1/2 175 5960 2206 4137 84 1500
STD2120-3U*-OB 120 120 13 11 Three 1/2 185 4660 2084 4341 92 1570
STD2144-3U*-OB 144 144 13 11 Three 1/2 200 4247 1730 4326 85 1650
Note: Data above for 1725 RPM at 60 Hz, 50 Hz is 1425 RPM with a 17%
reduction in the performance data.
* - Use corresponding letters in "Electrical Data" columns to
complete the model numbers.
AMCA Certified Lab DataMechanical Data
1.TheAMCACertifiedRatingsSealappliestoairflowrate,averageoutletvelocity,outletvelocityuniformity,velocityprojectionandpowerratingatfreedeliveryonly.
2.Rateddatashownareonlyforbase(unheated)units,asshown.