Masibus Automation & Instrumentation Pvt. Ltd.
B/30, GIDC Electronics Estate,
Sector-25, Gandhinagar-382044, Gujarat, India
+91 79 23287275- -82
Email: support@masibus.com
Web: www.masibus.com

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 2 of 53
Contents
1. INTRODUCTION ..................................................................................4
Foreword................................................................................................................ 4
Notice..................................................................................................................... 4
Trademarks............................................................................................................ 4
Checking the Contents of the Package.................................................................. 4
Product Ordering Code .......................................................................................... 4
List of Accessories ................................................................................................. 5
Safety Precautions................................................................................................. 5
2. INSTALLATION DETAILS ..................................................................6
2.1 How to Install.................................................................................................... 6
2.2 External Dimensions and Panel Cutout Dimensions ....................................... 7
2.3 How to connect wires ...................................................................................... 8
3. HARDWARE SPECIFICATION DETAILS...........................................9
3.1 Inputs............................................................................................................... 9
3.2 Display & Keys .............................................................................................. 10
3.3 Output............................................................................................................ 10
3.4 Communication Details.................................................................................. 11
3.5 Power Supply................................................................................................ 12
3.6 Physical......................................................................................................... 12
3.7 Environmental ............................................................................................... 12
4. WIRING DIAGRAM ...........................................................................13
4.1 BACK PLATE WIRING DETAIL .................................................................... 13
4.2 TRASMITTED POWER SUPPLY WIRING DIAGRAM.................................. 14
4.3 VALVE POSITION FEEDBACK WIRING...................................................... 14
5. FRONT PANEL DETAILS.................................................................15
5.1 Key Function Description............................................................................... 16
6. MENU LAYOUT ................................................................................18
6.1 RUN TIME INDICATION/FUNCTION............................................................ 18
6.2 Set Point Setting............................................................................................ 18
6.3 LEVEL - 1...................................................................................................... 18
6.4 LEVEL - 2...................................................................................................... 19
6.5 LEVEL - 3...................................................................................................... 22

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 3 of 53
6.6 LEVEL - 4...................................................................................................... 24
6.7 LEVEL –5..................................................................................................... 26
6.8 Calibration..................................................................................................... 27
6.9 Factory Reset Parameters............................................................................. 28
7. PARAMETER FLOW CHART ............................................................30
8. ALARMS & DIGITAL OUTPUTS........................................................33
9. DIGITAL INPUTS ..............................................................................36
10. CONTROL FUNCTION DETAILS....................................................37
11. CALIBRATION PROCEDURE..........................................................42
11.1 Ambient temperature adjustment ................................................................ 42
11.2 PV input sensor calibration.......................................................................... 42
11.3 Remote set point calibration........................................................................ 43
11.4 Position Feedback Calibration..................................................................... 43
11.5 Retransmission output calibration (Voltage/current output)......................... 44
11.6 Control output calibration (current output)................................................... 44
12. COMMUNICATION DETAILS..........................................................45
12.1 Function codes use for Modbus .................................................................. 45
12.2 Exception responses for Modbus ................................................................ 45
12.3 Modbus parameters .................................................................................... 45
13. Appendix ........................................................................................49
13.1 Troubleshooting........................................................................................... 49
13.2 PV INPUT STATUS DISPLAY DURING BURNOUT CONDITION.............. 49
13.3 RSP (REMOTE SET POINT) BURNOUT CONDITION............................... 50
13.4 VALVE POSITION FEEDBACK OPEN CONDITION .................................. 50
13.5 RETRAMISSION OUTPUT TABLE FOR OPEN /OVER /UNDER
CONDITION......................................................................................................... 51
13.6 CONTROL OUTPUT TABLE OPEN/OVER/ UNDER CONDITION............. 52
13.7 Digital Input & Retransmission Output Type Selection Settings.................. 53

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 4 of 53
1. INTRODUCTION
Foreword
Thank you for purchasing 5040 series PID controller. This manual describes the basic
functions and operation methods of 5040.Please read through this user’s manual
carefully before using the product.
Notice
The contents of this manual are subject to change without notice as a result of
continues improvements to the instrument’s performance and functions
Every effort has been made to ensure accuracy in the preparation of this manual.
Should any errors or omissions come to your attention, however, please inform
MASIBUS Sales office or sales representative. Under no circumstances may the
contents of this manual, in part or in whole, be transcribed or copied without our
permission.
Trademarks
Our product names or brand names mentioned in this manual are the trademarks or
registered trademarks of Masibus Automation and Instrumentation (P) Ltd. (herein
after referred to as MASIBUS).
Adobe, Acrobat, and Postscript are either registered trademarks or trademarks of
Adobe Systems Incorporated. All other product names mentioned in this user's
manual are trademarks or registered trademarks of their respective companies.
Checking the Contents of the Package
Unpack the box and check the contents before using the product. If the product is
different from which you have ordered, if any parts or accessories are missing, or if the
product appears to be damaged, contact your sales representative.
Product Ordering Code
Ordering Code
Model
Input
Power Supply
Control O/P
Rx O/P
5040
1
E
U1
85-265VAC/
100-300VDC
1
Relay
1
4-20mA
2
J
U2
18-36VDC
2
Pulse
2
0-20mA
3
K
3
Linear
3
1-5V
4
T
4
MOV
4
0-5V
5
B
5
0-10V
6
R
7
S
8
N
9
Pt-100
A
-10 to 20mV
B
0 to 75mV
C
0 to 100mV
D
0.4 to 2V
E
0 to 2V
F
0 to 5V
G
1 to 5V
H
0 to 10 V

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 5 of 53
The Single Loop Controller unit has a nameplate affixed to the one side of the
enclosure.Check the model and suffix codes inscribed on the nameplate to confirm
that the product received is that which was ordered.
List of Accessories
The product is provided with the following accessories according to the model and
suffix codes (see the table below). Check that none of them are missing or damaged.
No
Item name
Part number
Qty
Remarks
1
Mounting Clamps
-
2
Safety Precautions
The product and the instruction manual describe important information to prevent
possible harm to users and damage to the property and to use the product safely.
Understand the following description (signs and symbols), read the text and
observe Descriptions.
DESCRIPTION OF SIGNS

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 6 of 53
2. INSTALLATION DETAILS
2.1 How to Install
Mounting method: Panel mounting
To install the controller select a location where:
no one may accidentally touch the terminals
mechanical vibrations are minimal
corrosive gas is minimal
temperature can be maintained at about 25˚C to 35˚C and the fluctuation is
minimal
no direct radiant heat is present
no magnetic disturbances are caused
no wind blows against the terminal board
no water splashed
no flammable materials are around
Turn off the power to the controller before installing it on the panel because there is
a possibility of electric shock

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 7 of 53
2.2 External Dimensions and Panel Cutout Dimensions
Unit: mm

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 8 of 53
2.3 How to connect wires
Before carrying out wiring, turn off the power to the controller and check that the
cables to be connected are not alive because there is a possibility of electric shock.
NOTE:
All wiring must confirm to appropriate standards of good practice and local
codes and regulations. Wiring must be suitable for Voltage, Current and
temperature rating of the system.
Provide power from a single-phase instrument power supply. If there is a lot of
noise in the power line, insert an insulating transformer into the primary side of
the line and use a line filter on the secondary side. Do not place the primary
and secondary power cables close to each other.
For thermocouple input, use shielded compensating lead wires for wiring. For
RTD input, use shielded wires that have low conductor resistance and cause no
significant differences in resistance between the three wires. Do not connect
Terminal –23 when thermocouple or Linear input is selected.
Use repeater after each set of 32 instruments connected in RS-485
Communication.
Unused terminals shouldnot be used as jumper points asthey may be internally
connected, which may cause damage to the unit.
CAUTION:
High voltage transients may occur when switching inductive loads such as some
contactors or solenoid valves. Through the internal contacts, these transients may
introduce disturbances which could affect the performance of the instrument.
For this type of load it is highly recommended that a “snubber” is connected across the
normally open contact of the relay switching through load. The snubber recommended
consists of a series connected resistor/capacitor (typically 15nF/100Ohms). A snubber
will also prolong the life of the relay contacts. A snubber should also be connected
across the output of a tric output to prevent false triggering under line transient
conditions.

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 9 of 53
3. HARDWARE SPECIFICATION DETAILS
3.1 Inputs
Analog Input
Input Type
Thermocouple (E, J, K, T, B, R, S, N), RTD (Pt100),
Current, Voltage
Display Range
Table-3.1
Accuracy
TC, RTD: ± 0.1% of F.S ± 1 degC
Current, Voltage: ± 0.1% of F.S ± 1 Count
ADC Resolution
17 bits
Display Resolution
0.1°C / 1 Count
Sampling Rate
4 Samples/Sec
CJC Error
±2.0 °C Max
Sensor Burnout current
0.25uA
RTD excitation current
1mA Max
Allowable wiring resistance for
RTD
Maximum 15 ohms/wire (Conductor
resistance between three wires should be equal)
NMRR
> 40 dB
CMRR
> 120 dB
Temp-co
< 100ppm/°C
Input Impedance
> 1MΩ
Max Voltage
20VDC
Protection
Wire beak detection of any wire
Resolution
0.1%
Table-3.1: Input Display Range
Input Type
Range
Thermocouple
E
-200 to 1000°C
J
-200 to 1200°C
K
-200 to 1370°C
T
-200 to 400°C
B
450 to 1800°C
R
0 to 1750°C
S
0 to 1750°C
N
-200 to 1300°C
RTD
Pt-100
-199.9 to 850.0°C
Voltage
-10 to 20mV
-1999 to 9999
0 to 75mV
0 to 100mV
0 to 5V
1 to 5V
0 to 10 V
0.4 to 2V
0 to 2V
Current
4 to 20mA (Ext. 100Ω)
0 to 20mA (Ext. 100Ω)

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 10 of 53
Remote Input Signal
Input Type
Settable in a range from 0-5 V or 1-5 V DC.
The input type can be selected with the front keypad.
For 0 –20mamp (0-5v) and 4 –20mamp (1-5v)
250ohms (0.1%, low ppm) resistor should be connected
externally.
Input sampling time for remote input is 3 times the PV
input.
Input Range
-1999 to 9999 counts
Resolution
17-bit
Input Resistance
> 1Mohm
Input Accuracy
±0.1% instrument range, ±1 Count
Feedback Resistance Input
Slide resistance value
100 ohms to 1K ohms of overall resistance
(burnout detection for all the three wires provided)
Measuring resolution:
0.1% of overall resistance (After User’s adjustment).
3.2 Display & Keys
Front Panel Details
PV Display
4-digits, 7-segment, Red LEDs, character height of 0.56’’
SV Display
4-digits, 7-segment, Green LEDs, character height of 0.4’’
Bar Display
20 Orange LEDs for %POWER, Valve position indication
Status Indication
Red LEDs for RELAY and Alarm status, Manual mode
status, Remote status.
Green LEDs for Communication,
Red LEDs for Set Point selection 1 and 2, Auto-tune
status, Valve Position Feedback status
Keys
5 keys for configuration, calibration and operation
3.3 Output
Output Types
RELAY OUTPUT(PID and ON/OFF control)
SSR OUTPUT
LINEAR OUTPUT (4-20mAmp)
VALVE POSITION WITH FEEDBACK CONTROL (VPFB)
VALVE POSITION WITHOUT FEEDBACK CONTROL (VPFN)
Digital Input
No of DI
4
Input Type
Non-Voltage Contact or Pulse Input(24VDC,@5mA)
Rating
24VDC@5mA Max
Purpose
Target Set point selection,
Auto/Manual selection,
Remote /Local mode switching,
Run/Stop mode selection
Minimum status detection Holds
Time
About 1 Second

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 11 of 53
Control Output (Field Programmable)
Relays
1 (Relay-1) for Relay and ON-OFF Output Type
2 (Relay-1 & Relay-2) for VPFB & VPFN Output Type
Type
Single Change over (C, NO, NC)
Rating
2A @ 230VAC / 30VDC
Pulse Output (SSR)
Output signal
Pulse output
Load resistance
500 ohms Max. Or less
Output signal On-condition
16mAmp DC or more
Off-condition
3mAmp DC or less
Resolution
10 ms
Linear Output
Output Signal
4-20mA@500Ω Max, Accuracy: 0.25% of FS
Retransmission Output
Number of output
1
Output According to
Process Value, Set point, Control output or Valve Position
Output Signal
4-20mA/ 0-20mA/1-5VDC/ 0-10V DC
Load resistance
For Current o/p
For Voltage o/p
500Ω Max.
3KΩ Min.
Output accuracy
±0.25% of span
Alarm Output
Number of Outputs
4 if Output Type is Linear or Pulse (Relay-1 to Relay-4),
3 if Output Type is Relay or ON-OFF (Relay-2 to Relay-4)
2 if Output Type is VPFB or VPFN (Relay-3 & Relay-4)
Control relays are available as alarm outputs
Output signal
Three terminals (NC, NO, and C)
Purpose
Alarm output and others.
(See Alarm and Digital outputs function)
Relay contact rating
250 V AC or 30 V DC, 2A (resistive load)
Contact Digital Outputs
Number of outputs
4
Output type
Open collector
Output Contact rating
24V DC, 50 mA, with inbuilt current limit protection
Purpose
Various Alarm outputs such as PV High / Low etc. Also,
fault diagnosticoutputs such as PV Input OPEN, RSP
Input OPEN, and VPFB Input OPEN areavailable
Loop Power Supply
Supply Voltage
24VDC (±1V) @30mAwith Inbuilt Short Circuit Protection
Minimum load resistance
800 ohms
3.4 Communication Details
Communication
Interface
RS485 (2 Wire)
Protocol
Modbus-RTU
Baud rate
9600, 19200

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 12 of 53
3.5 Power Supply
Standard
85-265VAC/ 100-300VDC
Optional
18-36VDC
Power consumption
<12 VA
Isolation (Withstanding voltage)
Between primary terminals* and secondary terminals**:
At least 1500 V AC for 1 minute
Between primary terminals* and grounding terminal:
At least 1500 V AC for 1 minute
Between grounding terminal and secondary terminals**:
At least 1500 V AC for 1 minute
Between secondary terminals**:
At least 500 V AC for 1 minute
* Primary terminals indicate power terminals and relay output terminals.
** Secondary terminals indicate analog I/O signal and Communication O/P.
Insulation resistance: 20MΩ or more at 500 V DC between power terminals and grounding
terminal.
3.6 Physical
Size
96(W) x 96(H) x 110(D)mm
Front Bezel
96 x 96 mm
Panel Cutout
92.5 + 0.8(W) x 92.5 + 0.8(H) mm
Depth behind Panel
110 mm
Installation
Panel-mounting type. With Top and Bottom mounting
hardware (1 each)
Weight
< 1 Kg.
Case color
Black
Enclosure Material
ABS
Terminal Cable Size
2.5mm2
Accessories
Two mounting clamps
3.7 Environmental
Operating temperature
0-55 °C
Storage temperature
0-80 °C
Humidity
30-95 %RH non-condensing
Tempco
FOR PV (Main input), RSP (Remote input) and
Position Feedback Input < 100ppm.
FOR Retransmission(Current and Voltage) and Control
Output < 150ppm
Instrument Warm-up Time
15 minutes or more after power on

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 13 of 53
4. WIRING DIAGRAM
4.1 BACK PLATE WIRING DETAIL

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 14 of 53
4.2 TRASMITTED POWER SUPPLY WIRING DIAGRAM
4.3 VALVE POSITION FEEDBACK WIRING
(FOR INTERLOCK FORWARD AND REVERSE RELAY)

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 15 of 53
5. FRONT PANEL DETAILS
Name of Part
Function
Process Value
Display(PV)
Display process value.
Display parameter name when userset parameter.
Display error message when an error occurs.
Set Value Display
(SV)
Display set value.
Display parameter value of parameter in process value
field when user set parameter.
Display control output value when in manual mode.
Control Output Value
Bar Display(MV)
Display control output value in form of Bar scaled in 20
segments.
Output Indicator
Lamps(RL1 & RL2)
In Heat action, RL1 lamp will Indicate the on status of
the heat output.
In Valve Position Feedback action & Without Valve
Position Feedback action; RL1 lamp will indicate the
status of the Heat Or Forward Output And RL2 lamp
will indicate the status of Cool Or Reverse Output.
In Control applications with Linear Control Output, RL1
and RL2 will work as Normal Alarms (Alarm 1 & 2).
When Alarm 1 & 2 Occurs, Respective Alarm lamp
willlight (In Red).
Alarm Indicator
Lamps(RL3 & RL4)
When Alarm 3&4 occurs, respective Alarm lamp (RL3
& RL4) will light (In Red).
Remote/Local Set point
Indicator Lamp(REM)
It indicates whether Remote Set Point is selected or
not. It will light when Remote Set Point is selected.
Manual Mode
Lamp(MAN)
Indicator lamp will light when Manual Mode is selected
Communication
Indicator Lamps(T,R)
Indicator lamps will blink when the communication is
on.
Auto-Tune Indicator
Lamp(A-T)
Indicator lamp will blink when Auto tune Process is on.

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 16 of 53
5.1 Key Function Description
MENU/ENTER KEY:
It is used to enter in the sub menu (various levels) and save the parameters to
nonvolatile memory, when user setting a proper data by Increment and shift key for
parameter configuration.
ESCAPE KEY:
It is used to come out from any sub menu (various levels) to the run mode.
INCREMENT KEY:
It is used to increment the parameter for selection. Value of parameter can be
incremented by pressing this key. When first time increment key pressed, DP (decimal
point) in SV display blink, so user can modify the value with increment key. It is used
to increment the value in particular digit. Value can be incremented from 0- 9 and
from ‘9’ again it rollovers to ‘0’.
SHIFT KEY/DECREMENT KEY:
It is used to Shift the digit to set the parameter as describe in increment key when DP
(decimal point) started to blink. Menu key is used to go forward to show next
parameter and Shift key is used to go backward to show previous parameter. Also, in
manual mode control output (%power) can be decreased using Shift/Decrement key.
AUTO/MANUAL KEY:
It is used to switch between auto to manual mode and manual to auto mode. During
manual mode Increment key is used to increase to power and Shift/Decrement key is
used to decrease the power.
Name of Part
Function
Set Point –1 (SP-1)
Indicator lamp will on when Set Point 1 is selected. All
controller action with respect to SP-1
Set Point –2(SP-2)
Indicator lamp will on when Set Point 2 is selected. All
controller action with respect to SP-2
Valve Position
Feedback(VPFB)
Indicator Lamp will on when output type is VPFB
selected.

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 17 of 53
Example:
How to change SET POINT:-
SP.1 and SP.2 will be shown in operator mode if they are selected in one of the
SELECT Display Parameter from LEVEL-5 Menu.
Here SELECT display 1(D.S.1) is set forSP-1and SELECT display 2(D.S.2)is set
forSP-2and D.T.1 & D.T.2 is R+W. So they can be editable.
NOTE: ALL other parameters can EDIT according to the above steps.

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 18 of 53
6. MENU LAYOUT
6.1 RUN TIME INDICATION/FUNCTION
Following parameters can view or change during run time.
Press Shift/Dec key to show percentage power (0.0 to 100.0%)
For Thermocouple input type, Press Inc key to show ambient temperature.
During manual mode, Inc key and Shift key/Decrement Key will use to modify
the percentage power.
During manual mode, If VPFB/VPNA output type is selected, Inc key and Shift
key will use to OPEN or CLOSE the Valve.
Press Escape key to show percentage Valve Position(0.0 to 100.0%) in SV
display (available only if Valve position feedback is selected)
6.2 Set Point Setting
Pressing MENU key PV Display shows sp.1(SP.1) message (if d.s.1 is selected for
sp.1). SV display shows Set Point Value Use Inc and shift key to modify value. OR
press MENU key again to set value for next parameter.
6.3 LEVEL - 1
Pressing MENU key for 3 seconds (approx.) PV Display shows Mode (mode)
message. SV display shows LvL1 (LvL1) Use Inc key to move to other menu levels.
Or Press MENU key again to scroll through the menu items of Level - 1.
This level allows user to auto tune a process or manually set the PID values and some
other parameters as shown below.
LEVEL 1: Control Parameters Configuration
Parameter
(PV display)
Setting name and
Description
SV Display
Default
value
Shows only if
Reg.No
Symbol
Name
PWD
(Pwd)
Password
0 to 9999(Password
Protection for Level-1)
-
LOCK-1 set on
in Level-4
-
a.tun
(A.tUn)
Auto tune
Yes/no
1:(YES)
0:(no)
no
Output Type is
RLY, SSR,
CUR
-
Pb
(Pb)
Proportional
Band
0.1 to 999.9
50.0
Not available
for Output type
OnOF
3
Set Point Setting:
Parameter
(PV display)
Setting name and description
(SV display)
Default
value
Reg.No
Symbol
Name
Sp.1
(SP.1)
Target Set point-1
Depending on PV sensor type
selected
200
1
SP.2
(SP.2)
Target Set point-2
Depending on PV sensor type
selected
300
2

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 19 of 53
Ti
(ti)
Integral Time
0 to 1000 seconds
120
Not available
for Output type
OnOF
4
Td
(td)
Derivative Time
0 to 250 seconds
30
Not available
for Output type
OnOF
5
d.fCt
(d.FCt)
Derivative Factor
0.01 to 1.00
0.01
Not available
for Output type
OnOF
6
Ct
(Ct)
Cycle Time
1 to 250 seconds
10
Not available
for Output type
OnOF
7
dC
(DC)
Duty Cycle
10% to 100%
20%
Not available
for Output type
OnOF
8
db
(db)
Position
Proportional
Dead Band
0.1 to 50.0
1.0
Not available
for Output type
OnOF
9
Pb.SH
(Pb.SH)
P band shift
(Overshoot
suppression)
-50 to 50 %
0%
Not available
for Output type
OnOF
10
Ti.l
(TI.L)
Integral Inihibit
Low
1 to 100
100
Not available
for Output type
OnOF
mr
(MR)
Manual Reset
-50 to 50 %
0%
Not available
for Output type
OnOF
11
HY
(HY)
hysteresis (For
On/Off control)
1 to 250
2
Control type is
on/off
12
RAMP
(Ramp)
Ramp Rate type
none/min.r/hr.r
0:none
1:min.r
2:hr.r
None
Not available
for Output type
OnOF
13
Rmp.R
(rmp.r)
Ramp rate value
0.1 to 999.9 Degree
per minutes or hour
0.1
Not available
for Output type
OnOF
14
6.4LEVEL - 2
Pressing MENU key for 3 seconds (approx.) PV Display shows Mode (mode)
message. SV display shows Lvl2(LvL2) Use Inc key to move to other menu levels.
Please refer Alarm / Digital output section for better understanding and selection of
alarm types.
LEVEL 2: Alarm AND Digital Output Settings
Parameter
(PV display)
Setting name and
description
SV Display
Default
value
Shows
only if
Reg.No.
Symbol
Name
PWD
(Pwd)
Password
0 to
9999(Password
Protection for
-
LOCK-2 set
on in Level-
4
-

PID CONTROLLER -5040
REF NO: m53A/om/101
Issue NO: 08
User’s Manual Page 20 of 53
Level-2)
A1.SP
(A1.SP)
Alarm 1 Set point
PV range selected1
0
15
A1.tP
(A1.tP)
Alarm 1 Type
0 to 18. Refer alarm
type Table-8.1
0 (none)
16
A1.HY
(A1.HY)
Alarm 1 Hysteresis
1 to 250
2
17
A1.lC
(A1.LC)
Alarm 1 Logic
(normal or fail safe
selection)
norm/ flsf
0:(norm)
1: (FLSF)
Normal
18
A1.dY
(A1.Dy)
Alarm 1 Delay
1 to 99 seconds
10
19
A2.SP
(A2.SP)
Alarm 2 Set point
PV range selected1
0
20
A2.tP
(A2tP)
Alarm 2 Type
0 to 18. Refer alarm
type Table-8.1
0(none)
21
A2.HY
(A2.HY)
Alarm 2 Hysteresis
1 to 250
2
22
A2.LC
(A2.LC)
Alarm 2 Logic
(normal or fail safe
selection)
norm/ flsf
0:(norm)
1: (FLSF)
Normal
23
A2.dY
(A2.Dy)
Alarm 2 Delay
1 to 99 seconds
10
24
A3.SP
(A3.SP)
Alarm 3 Set point
PV range selected1
0
25
A3.tP
(A3.tP)
Alarm 3 Type
0 to 18. Refer alarm
type Table-8.1
0(none)
26
A3.HY
(A3.HY)
Alarm 3 Hysteresis
1 to 250
2
27
A3.LC
(A3.LC)
Alarm 3 Logic
norm/ flsf
0:(norm)
1: (FLSF)
Normal
28
A3.Dy
(A3.Dy)
Alarm 3 Delay
1 to 99 seconds
10
29
A4.SP
(A4.SP)
Alarm 4 Set point
PV range selected1
0
30
A4.tP
(A4.tP)
Alarm 4 type
0 to 18. Refer alarm
type Table-8.1
0(none)
31
A4.HY
(A4.HY)
Alarm 4 Hysteresis
1 to 250
2
32
A4.LC
(A4.LC)
Alarm 4 Logic
norm/ flsf
0:(norm)
1: (FLSF)
Normal
33
A4.Dy
(A4.Dy)
Alarm 4 Delay
1 to 99 seconds
10
34
d1.SP
Digital Output 1 Set
PV range selected1
0
35
Table of contents
Other Masibus Controllers manuals
Popular Controllers manuals by other brands

digitalview
digitalview DD-1920-HDMI instructions

Timeguard
Timeguard E269H-Synchronous Installation & operating instructions

Hobby-Wing
Hobby-Wing XERUN XR8 Plus user manual

Goldline
Goldline SP-30 product manual

Harmonic Drive
Harmonic Drive SC-610 Series Operation manual

R/Evolution
R/Evolution RLC1 owner's manual

Timeguard
Timeguard TRTD7N Installation & operating instructions

STEEL-PLAY
STEEL-PLAY Adventure Twin Pads manual

Kieback&Peter
Kieback&Peter MD15-FTL-902 operating instructions

Eding CNC
Eding CNC CNC760 Hardware manual

Tolomatic
Tolomatic Axidyne AXIOM PLUS PV Series user manual

Smartswitch
Smartswitch NV-2000 installation manual