Safety Instructions
AWARNING AWARNING
Improl_er installation, adjustment, alteration, service At the time of manufacture this water heater was pro-
or maintenance can causeDEATH, SERIOUS BODILY vided with a combination temperature-pressures relief
INJURY,OR PROPERTYDAMAGE. Refer to this manu- valve certified by a nationally recognized testing labo-
alfor assistance consult yourlocalgas utility or call ratory that maintainsperiodic inspectionof production
Maytag Customer Service at %800-788-8899 for an of listed equipment or materials, as meeting the
authorized servicer for further information, requirements for Relief Valves and Automatic Gas
Shutoff Devices for Hot Water SupplySystems, and
the latest edition of ANSI Z21.22 and the code require-
ments of ASME. If replaced, the valve must meet the
•,WARNING requirements of localcodes, but not lessthan a combi-
WATER HEATERS EQUIPPED FORONE TYPE GAS nation temperature and pressure relief valve certified
ONLY: This water heater is equipped for one type as meeting therequirements for Relief Valves and
gasonly. Check the model rating plate near the gas IAutomatic GasShutoff Devices for Hot Water Supply
control valve for the correctgas. DONOT USE THIS Systems, ANSI Z21.22 by a nationally recognized test-
WATER HEATER WITH ANY GAS OTHER THAN THE ing laboratory that maintains periodic inspection of
ONE SHOWN ON THE MODEL RATING PLATE.Failureproduction of listed equipment or materials.
to use the correct gas can cause problems which can I The valve must be marked with amaximum sat pres-
result in DEATH, SERIOUS BODILY INJURY, OR PROP- surenot to exceed themarked hydrostatic working
ERTYDAMAGE. If youhave any questionsor doubts pressure of the water heater (150Ibs./sq. in.) and a
consult your gas supplier or local utility, discharge capacity not less than the water heater
input rate asshown on the model rating plate.
(Electric beaters - watts divided by 1000 x 3415equal
BTU/Hr. rate.)
AWARNING Your local jurisdictional authority, whilemandating the
INSTALLATIONS IN AREAS WHERE FLAMMABLELIQ- use of a temperature-pressure relief valve complying
UIDS (VAPORS)ARE LIKELYTOBEPRESENTOR STORED with ANSI Z21.22 and ASME,may require a valve model
different from theone furnished with the water heater.
(GARAGES, STORAGE, AND UTILITY AREAS, ETC):
Flammable liquids (such as gasoline, solvents,propane Compliance with such local requirements must be sat-
(LP) or butane, etc.), all of which emit flammable isfied by the installer or end user of the water heater
vapors, may be improperly stored or used in such with a locally prescribed temperature-pressure relief
areas. The gas water heater ignitor or main burner can valve installed in the designated opening in the water
ignite suchvapors. The resulting flashback and fire can heater in place of the factory furnished valve.
causedeath or serious burns to anyone in the area, as Forsafe operation of the water heater, the relief valve
must notbe removed from it's designated opening or
well as property damage.
If installation in such areas is your only option, then plugged.
the installation must be accomplished in a way that The temperature-pressurerelief valve must be
the ignitor and mainburner flameare elevatedfrom installed directly into the fitting of the water heater
the floor at least 18 inches. While this may reduce the designated for the relief valve. Position thevalve
chances of flammable vapors from a floor spill being downward and providetubing so that any discharge
ignited, gasoline and other flammablesubstances will exit only within 6 inches above, or at any distance
should never be stored or used in thesame room or below the structural floor. Be certain that no contact is
area containing a gas water heater or other open madewith any live electrical part. The dischargeopen-
flame or sparkproducing appliance, ing must not be blocked or reduced in size under any
NOTE: Flammable vapors may bedrawn by air currents circumstances.Excessivelength, over 30 feet, oruse of
from other areas of the structure to the appliance, morethan four elbows can cause restriction and
reduce thedischarge capacity of the valve.
No valveor other obstruction isto beplaced between
the relief valve and the tank. Do not connect tubing
AWARNING directly to discharge drain unlessa 6"air gap isprovid-
IIf this water heat_in beauty shops, ed. To prevent bodily injury, hazard to life, or property
]barber shops, cleaning establishments, or self-ser-damage, the relief valve must be allowed to discharge
Jvice laundries with dry cleaning equipment, it is water in quantities should circumstances demand. If
imperative that the water heater or water heaters the discharge pipe is not connected to a drain or other
be installed so that combustion and ventilation air suitable means, the water flow may cause property
be taken from outside these areas.Refer to the damage.
"Locating The New Water Heater"section of this The Discharge Pipe:
manual and also the latest edition of the National •Must not be smaller in size than the outlet pipe size
Fuel Gas Code, ANSI Z223.1, also referred to asNFPA of the valve, orhave any reducing couplings or
54 for specifics provided concerning air required, other restrictions.
• Must not be plugged or blocked.
•Must be of material listed for hotwater distribution,
AWARNING *Must be installed so as to allow complete drainage
of both the temperature-pressure relief valve, and
A fire can start if combustible materials such as the discharge pipe.
clothing, cleaning materials, or flammable liquids *Must terminate atan adequate drain.
are paced aga nst or next to the water heater.* Must not have any valve between the relief valve
and tank.
2