McQuay International Proprietary Information - Subject to Change
9MicroTech Absorption Chiller Open Protocol Data Information
Description Address Range Units D
C
H
D
CS
D
C
U
N
C
U
L
C
U
Hot Water Inlet Temperature (Only
for DC-S & DC-H units)
11BA
11BB
Hi Byte
Lo Byte
0.1*X+0=°F X X
Hot Water Outlet Temperature
(Only while in Heating)
11B4
11B5
Hi Byte
Lo Byte
0.1*X+0=°F X
Hot Water Outlet Temperature
(Only for DC-S & DC-H units)
11B6
11B7
Hi Byte
Lo Byte
0.1*X+0=°F X X
Invertor Output Signal 119E 0-200 0.303*X+0 =Hz XXXXX
Low Temperature Generator
Temperature
11BC
11BD
Hi Byte
Lo Byte
0.1*X+0=°F XXXX
Remote Reset Current Signal 1196
1197
Hi Byte
Lo Byte
0.1*X+0=mA XXXXX
Steam Control Valve Output Signal 11E0
11E1
Hi Byte
Lo Byte
0.1*X+0=% X X
Chilled Water Inlet Temperature 11B2,11B3
This is the Chilled Water Inlet Temperature. These locations contain valid data only when the
Chiller/Heater is in the cooling mode or in the Simultaneous mode. This location is read by forming
the high byte (11B2) and the low byte (11B1) into a two byte number and dividing by 10 (0.1 * X +
0 = °F).
Chilled Water Outlet Temperature 11B0,11B1
This is the Chilled Water Outlet Temperature. These locations contain valid data only when the
Chiller/Heater is in the cooling mode or Simultaneous mode. These locations are read by forming
the high byte (11B0) and the low byte (11B1) into a two byte number and dividing by 10 (0.1 * X +
0 = °F).
Condensed Refrigerant Temperature 11C2,11C3
This is the Condensed Refrigerant Temperature. These locations are read by forming the high byte
(11C2) and the low byte (11C3) into a two byte number and dividing by 10 (0.1 * X + 0 = °F).
Cooling Water Inlet Temperature 11BE,11BF
This is the Cooling Water Inlet Temperature. These locations are read by forming the high byte
(11BE) and the low byte (11BF) into a two byte number and dividing by 10 (0.1 * X + 0 = °F).
Cooling Water Outlet Temperature 11C0,11C1
This is the Cooling Water Outlet Temperature. These locations are read by forming the high byte
(11C0) and the low byte (11C1) into a two byte number and dividing by 10 (0.1 * X + 0 = °F).
Exhaust Gas Temperature/Steam Condensate Temperature 11C6,11C7
This is the Exhaust Gas (DC-H, DC-S, DC-U) or Steam Condensate Temperature (NC-U). This
location is the Exhaust Gas Temperature for DC units or the Steam Condensate Temperature for NC
units. These locations are read by forming the high byte (11C6) and the low byte (11C7) into a two
byte number and dividing by 10 (0.1 * X + 0 = °F).
Fuel Control Valve 1 Output Signal 119A,119B
This is the Fuel Control Valve 1 Feedback Signal. These locations are read by forming the high byte
(119A) and the low byte (119B) into a two byte number and dividing by 10 (0.1 * X + 0).
Fuel Control Valve 2 Output Signal 119C,119D
This is the Fuel Control Valve 2 Feedback Signal. These locations are applicable on Simultaneous
units only (DC-S). These locations are read by forming the high byte (119C) and the low byte
(119D) into a two byte number and dividing by 10 (0.1 * X + 0).
High Temperature Generator Temperature 11C4,11C5
This is the High Temperature Generator Temperature. These locations are read by forming the high
byte (11C4) and the low byte (11C5) into a two byte number and dividing by 10 (0.1 * X + 0 = °F).