3.12.3 PMBus Control Setting
3.12.4 Factory Resetting
3.12.5 Initial Operational Behavior Setting
There are two means to control the power supply, analog signals and digital communication. Analog is the default setting
Users can follow the steps below to restore factory settings for commands: 01h, 22h, 22h, 46h, BEh, B0~B7.
Initial behavior of the power supply can be changed by setting SYSTEM_CONFIG(BEh), for OPERATION_INIT of
for the supply, signals including PV, PC and SVR can be used immediately once receiving the supply. The digital
1.Set the rotary switch at position 1.
example: power on without output. For detailed information, please refer to 3.13.6 PMBus Command List.
communication of PMBus is initially uncontrollable but readable. To activate the adjustment commands of OPEREATION
2.Turn on the AC without remote on, there should be no voltage at the output.
(01h, regarding remote ON-OFF function), VOUT_TRIM(22h, regarding output voltage programming function) and
IOUT_OC_FAULT_LIMIT (46h, regarding output current programming function), set PM_CTRL of SYSTEM_CONFIG(BEh)
at "1" and then reboot the supply. Once the digital communication dominates the supply, the analog signals become invalid.
3.Within 15 seconds, rotate the switch from position 1 to position 4 and then back to position1.
4.The green LED flashing 3 times means the process is successfully done.
5.Restart the supply to load factory settings.
3.12 6 . PMBus Command List
◎The command list of the HEP-1000 is shown in Table 3-3. It is compliant with the standard protocol of PMBus Rev. 1.1.
For detailed information, please refer to PMBus official website http://pmbus.org/specs.html).(
Table 3-3
Command
Code
01h
02h
19h
20h
21h
# of data
Bytes
1
1
1
1
2
Description
Remote ON/OFF control
ON/OFF function configuration
Capabilities of a PMBus device
Define data format for output voltage
(format: Linear, 24/48V:N= -9; 100V:N=-7)
Output voltage setting value
(format: Linear, 24/48V:N= -9; 100V:N=-7)
Command
Name
OPERATION
ON_OFF_CONFIG
CAPABILITY
VOUT_MODE
VOUT_COMMAND
Transaction
Type
R/W Byte
Read Byte
Read Byte
R Byte
R Word
22h 2 Output voltage trimmed value
(format: Linear, 24/48V:N= -9; 100V:N=-7)
VOUT_TRIM R/W Word
47h
79h
7Ah
7Bh
7Ch
7Dh
1
2
1
1
1
1
Define protection and response when an
output overcurrent fault occurred
Summary status reporting
Output voltage status reporting
Output current status reporting
AC input voltage status reporting
Temperature status reporting
IOUT_OC_FAULT_RESPONSE
STATUS_WORD
STATUS_VOUT
STATUS_IOUT
STATUS_INPUT
STATUS_TEMPERATURE
R Byte
R Word
R Byte
R Byte
R Byte
R Byte
7Eh 1 Communication, logic,
Memory status reporting
STATUS_CML R Byte
46h 2Output overcurrent setting value
(format: Linear, 24/48V:N= -4; 100V:N=-6)
IOUT_OC_FAULT_LIMIT R/W Word
80h
88h
8Bh
8Ch
1
2
2
2
Manufacture specific status reporting
AC input voltage reading value
(format: Linear, N=-1)
Output voltage reading value
(format: Linear, 24/48V:N= -9; 100V:N=-7)
Output current reading value
(format: Linear, 24/48V:N= -4; 100V:N=-6)
STATUS_MFR_SPECIFIC
READ_VIN
READ_VOUT
READ_IOUT
R Byte
R Word
R Word
R Word
98h 1 The compliant revision of the PMBus
(default: 11h for Rev. 1.1)
PMBUS_REVISION R Byte
8Dh 2 Temperature 1 reading value
(format: Linear, N= -3)
READ_TEMPERATURE_1 R Word
99h
9Ah
9Bh
9Ch
9Dh
9Eh
12
12
24
3
6
12
Manufacturer's name
Manufacturer's model name
Firmware revision
Manufacturer's factory location
Manufacture date. (format: YYMMDD)
Product serial number
MFR_ID
MFR_MODEL
MFR_REVISION
MFR_LOCATION
MFR_DATE
MFR_SERIAL
Block Read
Block Read
Block Read
Block R/W
Block R/W
Block R/W
9