5. Recommended Screwdriver, Wire and Torque Setting
Type
Solid wire
Stranded wire
American wire gauge
Wire stripping length
Screwdriver
Recommended tightening torque
Suggested push-down strength
-----
-----
-----
-----
-----
6mm Philips
4kgf-cm (3.47 lb-in)
Clamp connector Push terminal
(ACL/N, PUSH, DA )
±
ЈЈ0.8 - 1.8mm
0.5 - 2.5mm2
14 - 20AWG
10mm (0.39")
3mm Slotted
-----
3 - 4 kp (6.61-8.81 lb )
F
ЈЈ0.8 - 1.382mm
0.5 - 1.5mm2
16 - 20AWG
7mm (0.27")
3mm Slotted
-----
1.5 - 2.4 kp (3.31-5.29 lb )
F
Push terminal
(Vo , DIM )
±±
a. KNX System b. Push dimming
c. Synchronization operation
Note: ONLY use open push button without indicator light.
KNX+
KNX- KNX bus
Push Button
AC/N(or Backup DC- input)
AC/L(or Backup DC+ input)
PUSH
AC/N
AC/L
The detailed function of PUSH dimming, please refer to the database.
The maximum length of the cable between the push button and driver is 20 meters.
The additive push button can be connected only between the PUSH terminal, as displayed in the diagram,
and AC/L (in brown or black); it will lead to short circuit if it is connected to AC/N.
Synchronization up to 10 drivers (1 master + 9 slaves)
Dimming operating range : 6%~100%
Sync cable length : < 5m
Sync cable type : Flat cable
Sync cable cross section area : 22 – 24 AWG (0.2~0.3mm )
2
LCM-25
(Slave 2)
---
+
+
+
SYN. SYN. SYN.
LCM-25KN
(Master)
LCM-25
(Slave 1)
5m 5m
NOTE:1. Please make sure all units are set to 100% dimming setting (factory default) before synchronizing.
2. Max Dimming & Min. Dimming operating range depends on database setting.
KNX bus need to be connected in when using PUSH dimming.
3. Connection of Dimming Functions
AC/N (or Backup DC- input)
AC/L (or Backup DC+ input)
PUSH
AC/N
AC/L
The detailed function of AC/DC input monitor, please refer to the database
and instruction manual.
KNX bus need to be connected when using AC/DC input monitor
4. AC/DC input monitor
6. Suggested Maximum Number of the LCM Units that can be Connected to a MCB ( circuit breaker) at 230Vacminiature
Note: These calculated values are based on MCB S201 series manufactured by ABB.
Model B10 B16 C10 C16
LCM-25KN 20 32 34 54
7. Configuration and Commissioning
The application program(database) can be downloaded via Online Catalogs from ETS
or via http://www.meanwell.com/productCatalog.aspx
In case the PUSH dimming is set locally, up to 10 drivers can perform the PUSH dimming at the same time when utilizing
one common push button.
In case the PUSH dimming is set independently via ETS, the number of drivers is done through group address and determined by
the ETS project designer.