Mect TP1043 02 series User manual

ME7056_11
07/21
USER’S MANUAL
TP1043 02 series
HMI –Operator panel


HMI - Operator panel: TP1043 02 Mect srl
ME7056_11 07/21
INDEX
1. Introduction.............................................................................................................. 1
1.1. Staff skill............................................................................................................ 1
1.2. Simbols............................................................................................................... 1
1.3. Terms ................................................................................................................. 1
1.4. Security .............................................................................................................. 2
1.5. Reference Manual.............................................................................................. 2
2. System description................................................................................................... 3
2.1. Specification....................................................................................................... 4
2.2 Mechanical dimensions........................................................................................... 5
2.3 Panel mount........................................................................................................ 8
2.3.1 Distance........................................................................................................ 8
2.4 TP1043 02 wiring .............................................................................................. 9
2.5 Connections .......................................................................................................... 9
2.6 Power supply....................................................................................................10
2.6.1 System power supply ................................................................................. 10
2.6.2 Fuse ............................................................................................................10
2.7 ModBus wiring ................................................................................................11
2.8 CANOpen wiring.............................................................................................12
3Peripherals .............................................................................................................13
3.1 USB.....................................................................................................................13
3.2 Ethernet...............................................................................................................13
3.3 Micro SD-Card................................................................................................... 13
3.4 Configuration DIP switches.............................................................................13
3.5 UART debug....................................................................................................14
4HMI / PLC............................................................................................................. 15
4.1 System variables .............................................................................................. 15
5How to order.......................................................................................................... 16

HMI - Operator panel: TP1043 02 Mect srl
ME7056_11 07/21
1
1. Introduction
To grant a fast setup of the device please follow carefully the information in this
manual.
1.1. Staff skill
Products described in this manual are devoted to PLC programmers or automation
experts only. MECT S.r.l. declines any responsibility about malfunctioning or
damage caused by incorrect use of MECT devices, due to noncompliance to this
manual information. MECT S.r.l has an help desk.
1.2. Simbols
Danger
Follow this advice to avoid people injury.
Warning
Follow this advice to protect the device.
Caution
Follow this advice to have a more effective performance.
ESD ( Electrostatic discharge)
Danger: possibly damage due to Electrostatic discharge.
Note
Step to follow for a correct installation.
Additional information
1.3. Terms
PLC: TP1043 02
Terminals: MPNC006, MPNC020, MPNC030, MPNC035
MPNE series
System: PLC (TP1043 02) with terminals

HMI - Operator panel: TP1043 02 Mect srl
ME7056_11 07/21
2
1.4. Security Attention
Switch off devices before connecting them.
ESD (Electrostatic discharge)
Modules have electronic components that can be damaged by.
electrostatic discharge. Be sure to be connected to ground when
handle the devices.
The instrument has no power switch and no internal fuse, but it powers on
immediately after connecting a correct power supply input (check the power supply
value on the instrument label). Keep the power supply line as short as possible and
keep it separate from other power lines.
For safety reasons it is necessary to have a 2 section power switch with a fuse near
the instrument easily replaceable.
Avoid the presence of other power actuators in the same control panel, high humidity,
excessive heat and corrosive gas.
Instruments must have a power supply from safety transformers or SELV
transformers.
1.5. Reference Manual
The Quick Start (downloadable from the web site)
and MectSuite Tutorial are reference manuals for
MectSuite to develop HMI and PLC applications.

HMI - Operator panel: TP1043 02 Mect srl
ME7056_11 07/21
3
2. System description
TP1043 02 is a device composed by a PLC and a HMI with touch-screen monitor
4.3” width and 480 x 272 pixel resolution with 262.000 colors.
TP1043 allows the supervision of networked Modbus RTU and Modbus TCP
devices. The networks are managed simultaneously by TP1043 and data from a
network can be sent to another in order to create a bridge between the two networks.
A Micro-USB host port allows, with a special adapter, the use of an USB-pen drive
for software updates and data log. Through a GPRS/UMTS or Wi-Fi key (optionally
sold by Mect) is possible to connect the operator panel to a Wi-Fi or Mobile
network. Settings under MENU OPTIONS NETWORK_CFG tab “Wi-Fi”
or tab “Mobile”
On TP1043 02 there are up to 1 Kbyte for retentive variables stored on the internal
flash memory.
The device is also able to manage an up to 64GB wide, micro SD card. The SD card
is factory mounted on request.
A real-time clock buffered RAM maintains the date and time up to four months with
the device turned off.
TP1043 02 is equipped with a micro PLC to make a small automation of the process.
The device can be applied in horizontal or in vertical design with the option "V" (see
following pictures).
Figure 1: Front view TP1043 (horizontal version)
Figure 2: Front view TP1043 (vertical version)

HMI - Operator panel: TP1043 02 Mect srl
ME7056_11 07/21
4
2.1. Specification
TP1043 02 is based on a multiprocessor system. PLC and HMI are based on a
454MHz ARM9.
Table 1
Hardware characteristics
PLC Processor
ARM926JE 454MHz
RAM
128MB
FLASH
128MB
Non volatile variables
On FLASH memory
Real Time Clock
Yes with rechargeable battery
Screen
TFT 480 x 272 pixel 262k colors
Touch screen
Resistive 4 wires
Ethernet
10Mbit/s - 100Mbit/s self recognition
Micro-USB
Host 2.0
Micro SD
Max 64GB
Software characteristics
OS
LINUX 2.35
PLC
IEC61131-3
Graphics
Based on QT library
CAN
CanOpen 2.0
ModBus
Modbus RTU master
Storage memory
Possibility of history storage
Field bus main features
RTU Modbus
Master 2 wires
TCP Modbus
Client
Power supply
Power Supply 24Vac/Vdc
12÷36Vdc - 150mA (24Vdc)
24Vac ±20% - 150mA
Electromagnetic compatibility
The electromagnetic compatibility tests have been carried out at accredited
laboratories, according to EN 61326-1, EN 61131-2 and EN 61000-6-2standards.

HMI - Operator panel: TP1043 02 Mect srl
ME7056_11 07/21
5
2.2 Mechanical dimensions
In the following figures see the TP1043 dimensions.
Panel with frame mounting and hooks fastening:
Encumbrance
Front view Side view
Mounting plate

HMI - Operator panel: TP1043 02 Mect srl
ME7056_11 07/21
6
Panel with frame mounting and screws fastening:
Encumbrance
Front view Side view
Mounting plate

HMI - Operator panel: TP1043 02 Mect srl
ME7056_11 07/21
7
Panel without frame mounting:
In this case, the display has to be exactly at the same height of the panel, so for metal
panels below 2,5mm it needs to insert a spacer to reach the exact height.
Front view Side view
Technical specification
Table 2
Mechanical
Material
ABS, Polycarbonate
Dimensions W x L x H
27 mm x 156 mm x 80 mm
Mounting plate
127mm x 68mm
Installation
Panel installation
Environmental conditions
Operative temperature
0 °C ... 55 °C
Storage Temperature
-20 °C ... +85 °C
Relative Humidity
5 % a 95 % no condensation
Electric isolation
Air clearance
According to IEC 60664-1
Pollution
According to IEC 61131-2
2
Protection
Rear protection
IP 20
Front protection
IP65
Attention
Install the device in a panel with no more than 55 °C.

HMI - Operator panel: TP1043 02 Mect srl
ME7056_11 07/21
8
2.3Panel mount
2.3.1 Distance
The device must be installed with some space between other devices to allow the
right dissipation and cabling.
In order to avoid EMC issues, you should not overlap cables.
Figure 6A: Horizontal mounting
Figure 6B: Vertical mounting

HMI - Operator panel: TP1043 02 Mect srl
ME7056_11 07/21
9
2.4TP1043 02 wiring
2.5 Connections
In the following figure see the wiring diagram.
Figure 7
Table 3
TP1043 02
Power Supply
24Vdc/Vac
12÷36Vdc - 150mA (24Vdc) or 24Vac ±20% - 150mA
Micro-USB
2.0
Ethernet
Bit rate: 100Mbit/sec
Serial ouputs
RS485 Modbus half duplex (hardware configuration) or
CANopen

HMI - Operator panel: TP1043 02 Mect srl
ME7056_11 07/21
10
2.6Power supply
2.6.1 System power supply
TP1043 02 has a 12÷36Vdc or 24Vac (see the model purchased) according to the
scheme in the figure. System is protected against reverse power supply.
2.6.2 Fuse
The device has no internal fuse protection, so the use of an external 500mA fuse for
the panel power supply is recommended.
Figure 8
Attention
A wrong power supply voltage can damage the device

HMI - Operator panel: TP1043 02 Mect srl
ME7056_11 07/21
11
2.7ModBus wiring
ModBus on TP1043 02 is a 2 wire RS485 serial line, at the following pins of the
terminal board:
Table 4
Pin
Signal
Description
3
GNDiso / GND
2
D +
Linea +
1
D -
Linea -
Example of wiring for a system composed by:
MPNC006
MPNC020
MPNC030
TP1043 02
Figure 9

HMI - Operator panel: TP1043 02 Mect srl
ME7056_11 07/21
12
2.8CANOpen wiring
The CANopen interface on TP1043 02 must be connected to the terminal block on
the pins shown in the table.
Table 5
Pin
Signal
Description
3
GNDiso
2
CAN H
Line +
1
CAN L
Line -
Example of wiring for a system composed by:
MPNC010
MPNC030
TP1043 02
Figure 10

HMI - Operator panel: TP1043 02 Mect srl
ME7056_11 07/21
13
3Peripherals
3.1 USB
TP1043 02 has a Micro-USB 2.0 host for:
software update
data storage: datalogger
USB peripherals as printers, mouse, etc
Wi-Fi or Mobile key interface (optionally supplied by Mect) to connect to a
different network from LAN
Specific connection of external peripherals are implemented on request.
3.2 Ethernet
TP1043 02 has a 10/100Mbit/s ethernet port with auto-configuration, the connection
cable between TP1043 02 and a personal computer can be either straight either cross.
3.3 Micro SD-Card
On TP1043 02 is it possible to insert a micro SD card up to 64 GB used by
applications and/or data logging. The memory will be handled automatically by the
device itself.
3.4Configuration DIP switches
In the rear of the panel, there is a DIP switch, used for the boot configuration.
Three boot options are allowed:
Internal FLASH
SD card
USB
Set accordingly the switches before the power up, to select the wanted boot mode.

HMI - Operator panel: TP1043 02 Mect srl
ME7056_11 07/21
14
Switches configuration is shown in the following table
Table 6
SW1
SW2
Boot mode
Note
OFF
OFF
Internal Flash (default)
Default configuration
OFF
ON
USB
Factory firmware upgrade do
not use
ON
ON
SD card
ON
OFF
SD card
3.5UART debug
In the bottom side of the rear panel there is a six pole header used for debug purpose.
The port is a TTL UART with the following pinout:
A commercial adapter is available from FTDI: TTL-232R.

HMI - Operator panel: TP1043 02 Mect srl
ME7056_11 07/21
15
This interface is only available for debugging, it cannot be absolutely used for any
functional purposes at all.
The use of this port is recommended for advanced users only.
4HMI / PLC
The device is programmed by a development suite (Mect Suite - QT based), tailored
to MECT products.
A tutorial specifically made for the device is available.
The Mect suite software run on Windows operative system.
4.1System variables
The system can use 5472 interchange variables between HMI and automation (at
maximum) which include:
internal variables, interchange variables on Modbus network, retentive variables.
The variables are defined by a software “Mect Suite”.

HMI - Operator panel: TP1043 02 Mect srl
ME7056_11 07/21
16
5How to order
Other manuals for TP1043 02 series
1