Instructions
INSTRUCTIONS 730308 Rev. -
Surge-Trap®Type 1 SPD for NEMA Type 2 Applications
DANGER
Hazard of Electric Shock, Burn or Explosion
• Thisequipmentmustbeinstalledandservicedonlyby
qualiedelectricalpersonnelinaccordancewithnational
andlocalelectricalcodes.
• Turnoffallpowersupplyingthisequipmentbefore
workingonequipment.
• Alwaysuseaproperlyratedvoltage-sensingdeviceto
conrmpowerisoff.
• Replacealldevices,doorsandcoversbeforerestoring
powertothisequipment.
• Donotapplypetroleum-basedproductsto
non-metallicparts.
Improperinstallationormisapplicationofthesedevices
mayresultinseriousinjurytotheinstallerand/ordamage
toelectricalsystemorrelatedequipment.Protectiveeye
wearandclothingshouldbewornwheneverworking
aroundhazardousvoltages.
Failuretofollowtheseinstructionscouldresultinserious
injuryordeath.
CAUTION
• DonotattempttoopenortampertheSurge-Trap
deviceinanywayasthismaycompromiseperformance
andwillvoidthewarranty.
• Meggerandhi-potentialtestsmaydamagethedevice.
• Disconnectallpowersupplyingtheequipmentand
isolatetheSurge-Trapdevicebeforetesting.
• Priortoinstallation,conrmthattheSurge-Trapisrated
forthecorrectvoltage,currentandfrequencyequivalent
totheapplication.
• ForuseinNEMAType2ApplicationsOnly.
PANEL MOUNT AND WIRING
1. Turnoffallpowersupplyingthisequipment.
2. PanelMount:Removelocknutfromproduct.Punch
outa1/2″enclosureknockoutfromthepanelorthe
mountinglocationascloseaspossibletothewherethe
wireswillterminate.Whereothertypesofmountingare
required,pleaseconsultthefactory.
3. InsertSurge-Trap®SPDwirescarefullythroughthe
knockoutholeandtightenthelocknutto20ft-lb
(2.3Nm)maximumtosecuretheSurge-Trap®SPDto
theenclosure.(AsshowninFigure1)
4. Connectthewiresasshownintheappropriatewiring
diagram.
INSTALLATION Figure1PanelMount
NUT
374MerrimacStreet,Newburyport,MA01950
88HornerAvenue,Toronto,Ontario,CanadaM8Z5Y3
ep-us.mersen.com ep-ca.mersen.com
5. OvercurrentProtection:Type1SPDsareULListed
andtestedtobeself-protecting.Theydonotrequire
upstreamprotectionaccordingtoUL1449andSection
285oftheNEC.However,werecommendanupstream
disconnectorbreakerformaintenanceandsafety.
Manyswitchesandcircuitbreakershavelimitations
regardingmorethanonewireinaconnector.Breaker
manufacturerscanprovideinformationonthelimitations
oftheiravailableterminals.Whereadditionalwires
areprohibitedunderthesameterminal,manytimes
installinganewcircuitbreakerisconvenient.Typical
sizesare15,20and30amps.
6. Foroptimaldeviceperformance,useshortestwire
lengthofwireaspossible.Cutofftheexcesswire
insteadofcoilingitup.Avoidsharpbends.
7. Beforeenergizing,installershallverifyserviceand
separatelyderivedsystemNeutraltoGroundbonding
jumperpertheNECrequirements.