EM-5025 Rev.9 P. 1 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
INSTRUCTION MANUAL
Mini-M™
CURRENT LOOP SUPPLY
(isolated, isolator usable) MODEL M2DYS
BEFORE USE ....
Thank you for choosing us. Before use, please check con-
tents of the package you received as outlined below.
If you have any problems or questions with the product,
please contact our sales office or representatives.
■PACKAGE INCLUDES:
Signal conditioner (body + base socket).............................(1)
■MODEL NO.
Confirm Model No. marking on the product to be exactly
what you ordered.
■INSTRUCTION MANUAL
This manual describes necessary points of caution when
you use this product, including installation, connection and
basic maintenance procedures.
POINTS OF CAUTION
■WARNING
• If equipment is used in a manner not specified by us, the
protection provided by the equipment may be impaired.
■NONINCENDIVE APPROVAL OPTION
• This equipment is suitable for use in Class I, Div. 2,
Groups A, B, C and D or Non-Hazardous Locations only.
• WARNING! Before You Remove the Unit from Its Base
Socket or Mount It, Turn Off the Power Supply and Input
Signal for Safety.
• WARNING! – Explosion Hazard –
Substitution of Components May Impair Suitability for
Class I, Div. 2.
• WARNING! – Explosion Hazard –
Do Not Disconnect Equipment Unless Power Has Been
Switched Off or The Area is Known To Be Non-Hazardous.
• The equipment was evaluated for use in the ambient tem-
perature and relative humidity as mentioned in ‘ENVI-
RONMENT’ section.
• The input and output wiring must be in accordance with
Class I, Div. 2 wiring methods and in accordance with the
authority having jurisdiction for use in these hazardous
locations.
■CONFORMITY WITH EU DIRECTIVES OR UL
• This equipment is suitable for Pollution Degree 2 and In-
stallation Category II (transient voltage 2500V). Rein-
forced insulation (signal input or output to power input:
300V) and basic insulation (signal input to output: 300V)
are maintained. Prior to installation, check that the insu-
lation class of this unit satisfies the system requirements.
• Altitude up to 2000 meters.
• The equipment must be mounted inside a panel.
• The equipment must be installed such that appropriate
clearance and creepage distances are maintained to con-
form to CE/UL requirements. Failure to observe these
requirements may invalidate the CE/UL conformance.
• The actual installation environments such as panel con-
figurations, connected devices, connected wires, may af-
fect the protection level of this unit when it is integrated
in a panel system. The user may have to review the CE
requirements in regard to the whole system and employ
additional protective measures* to ensure the CE con-
formity.
* For example, installation of noise filters and clamp fil-
ters for the power source, input and output connected
to the unit, etc.
• Install lightning surge protectors for those wires connect-
ed to remote locations.
■POWER INPUT RATING & OPERATIONAL RANGE
• Locate the power input rating marked on the product and
confirm its operational range as indicated below:
100 – 240V and 85 – 264V AC rating: 85 – 264V
(90 – 264V for UL), 47 – 66 Hz, approx. 3 – 5VA
24V DC rating: 24V ±10%, approx. 3W
11 – 27V DC rating: 11 – 27V, approx. 3W
110V DC rating: 85 – 150V (110V ±10% for UL), approx. 3W
■GENERAL PRECAUTIONS
• Before you remove the unit from its base socket or mount
it, turn off the power supply and input signal for safety.
■ENVIRONMENT
• Indoor use.
• When heavy dust or metal particles are present in the
air, install the unit inside proper housing with sufficient
ventilation.
• Do not install the unit where it is subjected to continuous
vibration. Do not subject the unit to physical impact.
• Environmental temperature must be within -5 to +55°C
(23 to 131°F) with relative humidity within 30 to 90% RH
in order to ensure adequate life span and operation.
• Be sure that the ventilation slits are not covered with ca-
bles, etc.
■WIRING
• Do not install cables close to noise sources (relay drive
cable, high frequency line, etc.).
• Do not bind these cables together with those in which
noises are present. Do not install them in the same duct.
■AND ....
• The unit is designed to function as soon as power is sup-
plied, however, a warm up for 10 minutes is required for
satisfying complete performance described in the data
sheet.
• With voltage output, do not leave the output terminals
shortcircuited for a long time. The unit is designed to
endure it without breakdown, however, it may shorten ap-
propriate life duration.
M2DYS
EM-5025 Rev.9 P. 2 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
COMPONENT IDENTIFICATION
Model
SPAN
ZERO
Zero Adj.
Span Adj.
Body Base Socket
Connection
Diagram
Specifications
Fixing Screw
INSTALLATION
Loosen the fixing screw at the front of the unit in order to
separate the body from the base socket.
DIN Rail
35mm wide
Spring Loaded
DIN Rail Adaptor
■DIN RAIL MOUNTING
Set the base socket so that
its DIN rail adaptor is at
the bottom. Hang the up-
per hook at the rear side
of base socket on the DIN
rail and push in the lower.
When removing the socket,
push down the DIN rail
adaptor utilizing a minus
screwdriver and pull.
■WALL MOUNTING
Refer to “EXTERNAL DIMENSIONS.”
TERMINAL CONNECTIONS
Connect the unit as in the diagram below or refer to the connection diagram on the side of the unit.
■EXTERNAL DIMENSIONS unit: mm (inch)
5
9
21.5 (.85)
70.5 (2.78)
84 (3.31)10 (.39) 15 (.59)
6 (.23)
59 (2.32)
DIN RAIL
35mm wide
[4 (.16)]
8–M3
SCREW
72 (2.83)
23 (.91)
2–4.2x5
(.17x.20)
MTG HOLE
6 (.24) deep
114 (4.49)
• When mounting, no extra space is needed between units.
4
8
12
14 13
1
4 (.16)
■CONNECTION DIAGRAM
5
1
8
4
+
–
–
INPUT
+
+
2-WIRE XMTR
PWR SUPPLY
MONITOR
1 – 5V DC
V
50Ω
250Ω
50Ω
8
5
+
–
INPUT
1
4
+
+
1
8
4
2-WIRE
TRANSMITTER
–
+
5
+
–
■When Used as DC Supply ■When Used as Isolator
250Ω
+
–
OUTPUT
9
12
U(+)
V(–)
POWER
13
14
WIRING INSTRUCTIONS
■SCREW TERMINAL
Torque: 0.8 N·m
■SOLDERLESS TERMINAL
Refer to the drawing below for recommended ring tongue
terminal size. Spade tongue type is also applicable.
Applicable wire size: 0.25 to 1.65 mm2(AWG 22 to 16)
Recommended manufacturer: Japan Solderless Terminal
MFG.Co.Ltd, Nichifu Co.,ltd
6 (.24) max
3.3 (.13) max
mm (inch)
M2DYS
EM-5025 Rev.9 P. 3 / 3
MG CO., LTD. www.mgco.jp
5-2-55 Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
CHECKING
1) Terminal wiring: Check that all cables are correctly con-
nected according to the connection diagram.
2) Power input voltage: Check voltage across the terminal
13 – 14 with a multimeter.
3) Input: Check that the input signal is within 0 – 100% of
the full-scale.
4) Output: Check that the load resistance meets the de-
scribed specifications.
ADJUSTMENT PROCEDURE
This unit is calibrated at the factory to meet the ordered
specifications, therefore you usually do not need any cali-
bration.
For matching the signal to a receiving instrument or in case
of regular calibration, adjust the output as explained in the
following.
■HOW TO CALIBRATE THE OUTPUT SIGNAL
Use a signal source and measuring instruments of sufficient
accuracy level. Turn the power supply on and warm up for
more than 10 minutes.
1) ZERO: Apply 0% input and adjust output to 0%.
2) SPAN: Apply 100% input and adjust output to 100%.
3) Check ZERO adjustment again with 0% input.
4) When ZERO value is changed, repeat the above proce-
dure 1) – 3).
MAINTENANCE
Regular calibration procedure is explained below:
■CALIBRATION
Warm up the unit for at least 10 minutes. Apply 0%, 25%,
50%, 75% and 100% input signal. Check that the output
signal for the respective input signal remains within accu-
racy described in the data sheet. When the output is out of
tolerance, recalibrate the unit according to the “ADJUST-
MENT PROCEDURE” explained earlier.
LIGHTNING SURGE PROTECTION
We offer a series of lightning surge protector for protec-
tion against induced lightning surges. Please contact us to
choose appropriate models.

Other MG Power Supply manuals

MG W5DY User manual

MG

MG W5DY User manual

MG F2DY User manual

MG

MG F2DY User manual

MG M6NPS2 User manual

MG

MG M6NPS2 User manual

MG MDC6 User manual

MG

MG MDC6 User manual

MG 10DU User manual

MG

MG 10DU User manual

MG M80DY User manual

MG

MG M80DY User manual

MG 10DNY User manual

MG

MG 10DNY User manual

MG Mini-M M2DY User manual

MG

MG Mini-M M2DY User manual

MG 10DY User manual

MG

MG 10DY User manual

MG R8-PS1 User manual

MG

MG R8-PS1 User manual

MG HDY2 User manual

MG

MG HDY2 User manual

MG 18KDU User manual

MG

MG 18KDU User manual

Popular Power Supply manuals by other brands

Phoenix Contact UNO POWER UNO-PS/1AC/24DC/30W Installation notes

Phoenix Contact

Phoenix Contact UNO POWER UNO-PS/1AC/24DC/30W Installation notes

Powerwerx SS-30DV user manual

Powerwerx

Powerwerx SS-30DV user manual

Teledyne T3PS40381P quick start guide

Teledyne

Teledyne T3PS40381P quick start guide

Horizont 10613 operating instructions

Horizont

Horizont 10613 operating instructions

SoundCraft DPS-2 user manual

SoundCraft

SoundCraft DPS-2 user manual

Pulsar EN54-3A17 manual

Pulsar

Pulsar EN54-3A17 manual

3B SCIENTIFIC PHYSICS 1012819 instruction sheet

3B SCIENTIFIC PHYSICS

3B SCIENTIFIC PHYSICS 1012819 instruction sheet

Bosch PBC-60 Quick manual

Bosch

Bosch PBC-60 Quick manual

Sony CP-EL operating instructions

Sony

Sony CP-EL operating instructions

Siemens PSU300B manual

Siemens

Siemens PSU300B manual

LEF LIGHTING FARO-500/ONE manual

LEF LIGHTING

LEF LIGHTING FARO-500/ONE manual

iseg ECH 128 Operator's manual

iseg

iseg ECH 128 Operator's manual

EXAIR 7961 Installation & maintenance

EXAIR

EXAIR 7961 Installation & maintenance

Allied Telesis AT-RPS3204 installation guide

Allied Telesis

Allied Telesis AT-RPS3204 installation guide

Puls PIANO PIM90.245 manual

Puls

Puls PIANO PIM90.245 manual

Pyle PSL462X instruction manual

Pyle

Pyle PSL462X instruction manual

Altronix SMP1012 Series installation guide

Altronix

Altronix SMP1012 Series installation guide

Ultra Products ULT33062 Features

Ultra Products

Ultra Products ULT33062 Features

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.