microguard 414 User manual

MICROGUARD414
OPERATOR'S MANUAL
LATTICE BOOM
INFORMATION
TEST
W
MAX
W
100%
MicroGuard 414
VIEW SET CLEAR DOWN UP
CONTRASTOPERATOR ALARMS
CRANE
SETUP
DEDUCT
WORKING
AREA
ERECTED TARE
SELECT
TARE
5.82
3.46 60%
ROPE LIMIT
57.2 8 M 49.1
OUTRIGGERS 360
Lifting Point
150 FT Main Boom

MicroGuard 424 OPERATOR'S MANUAL Lattice/Horizontal Display
MG424 OPERATOR MANUAL Page 2 of 14 December 7, 2000
OPERATOR'S INSTRUCTION MANUAL
TABLE OF CONTENTS
SYSTEM DESCRIPTION PAGE 3
DISPLAY WINDOWS PAGE 4
PUSH BUTTONS/TERMINOLOGY PAGE 6
SYSTEM OPERATION PAGE 9
CONFIGURATION SELECTION PAGE 10
OPERATOR SETTABLE ALARMS PAGE 11
EXAMPLES OF SETTING ALARMS PAGE 13
CANCELING ALARMS PAGE 14
SYSTEM CHECKS PAGE 14

MicroGuard 424 OPERATOR'S MANUAL Lattice/Horizontal Display
MG424 OPERATOR MANUAL Page 3 of 14 December 7, 2000
OPERATOR'S INSTRUCTION MANUAL
This manual describes the function and operation ofthe MicroGuard Rated CapacityIndicator (RCI)
system for lattice boomcranes. The systemis intended to aid the crane operator in the efficient operation
ofhis crane bycontinuouslymonitoring the load and warn ofan approach to an overload or two-block
condition. The systemmonitors crane functions bymeans ofhigh accuracysensors and continuously
compares the load suspended belowthe boomhead with acopyofthe crane capacitychart which is
stored in the computer memory.If an overload is approached, the systemwarns bymeans of audible and
visual alarms and can be configured to cause function kick-out.
System Description
The MicroGuard 414 indicator provides the operator with a continuous displayof:
♦Rated Capacity
♦Actual Load
♦Percentage ofRated Capacity
♦Radius ofthe Load
♦Angle ofthe Main Boom
♦Working Area (ifapplicable)
♦Crane Configuration
and bymeans ofalternate displaypush-buttons it provides the operator with:
♦Length ofthe Main Boom.
♦Height ofthe BoomHead.
On screen messages provide the operator with visual indications ofthe various alarmswhich mayoccur
during normal operation ofthe system.These values are displayed on the leftand upper right display.
The lower right displaygives information about the currentlyselected crane configuration.
INFORMATION
TEST
W
MAX
W
100%
MicroGuard 414
VIEW SET CLEAR DOWN UP
CONTRASTOPERATOR ALARMS
CRANE
SETUP
DEDUCT
WORKING
AREA
ERECTED TARE
SELECT
TARE
5.82
3.46 60%
ROPE LIMIT
57.2 8 M 49.1
OUTRIGGERS 360
Lifting Point
150 FT Main Boom

MicroGuard 424 OPERATOR'S MANUAL Lattice/Horizontal Display
MG424 OPERATOR MANUAL Page 4 of 14 December 7, 2000
LEFT DISPLAY WINDOW
1 MAXIMUMRATED CAPACITY is a
digital displayofthe maximumpermitted
capacity.It is derived fromacopyofthe
crane's capacitychart which is stored in the
computer memoryand is the reference
capacityfor anylifting operation. It is
dependent on the configuration currently
selected which is shownin the lower right
displayand which determines the section of
the capacitychart to be used as the capacity
reference. Ifmaximumrated capacityis
limited byparts ofline then the displayed
MAXIMUM RATED CAPACITYis the rope
capacityand the message ROPE LIMITis
displayed in the information area.
2 The BAR-GRAPH is an analog
bar-graph in the upper displaywhich gives a
visual indication ofhowmuch ofthe machine
capacityis being used and the rate at which an
overload is being approached. This bar-graph
in conjunction with the 100% capacitymarker gives avisual indication ofwhen the overload point is
reached.
3 PERCENTAGE OF RATED CAPACITY is a part ofthe bar-graph display. A digital read-out within
the bar-graph displayexpresses Actual Load as apercentage ofMaximumRated Capacity.For
percentages ofless than 100% the displaywill be at the right side of the bar-graph. For percentages over
87% the displaywill move to the center ofthe bar-graph in order to make space for the leading edge ofthe
bar-graph.
4 The INFORMATION AREA provides the operator with avisual indication ofthe various alarms
which mayoccur during normal operation ofthe system.For example PRE-ALARM or OVERLOAD,
ROPE LIMIT.
5 ACTUALLOAD is adigital displaywhich showstotal load suspended belowthe boomor jib head.
It includes the load, slings, pins or tackle used to secure the load and the hookblock.
INFORMATION
TEST
W
MAX
W
100%
MicroGuard 414
VIEW SET CLEAR DOWN UP
CONTRASTOPERATOR ALARMS
1
2
3
45
5.82
3.46 60%
ROPE LIMIT

MicroGuard 424 OPERATOR'S MANUAL Lattice/Horizontal Display
MG424 OPERATOR MANUAL Page 5 of 14 December 7, 2000
RIGHT SIDE DISPLAYS
1The RADIUS/HEIGHT displaygives a
continuous indication ofthe radius ofthe load
which is the horizontal distance fromthe center
line ofrotation to the center line ofthe hook.
When the Radius/Height push-button is pressed
the displaywill give amomentaryread-out display
of the height of the boomhead above ground level
i.e. the vertical distance fromthe ground to the
boom/jib head. Information about height is only
displayed while the Radius/Height push-button is
pressed and held.
2 PARTSOF LINE displaysthe parts ofline
currentlyselected. If the parts of line selected has
alower safeworking strength than the actual
capacitythen the MAXIMUM RATED CAPACITY
displaywill showthe reduced capacityAND THE
MESSAGE rope limit is displayed in the
information area.
3The WINCH IN USE displayindicates the selected winch. "M" indicates Main, "A" indicates
Auxiliary.
4The ANGLE/LENGTH displaygives acontinuous indication of the angle ofthe main boomrelative
to horizontal. When the angle/length push-button is pressed and held the displaywill give amomentary
read-out ofthe length ofthe Main Boomfromthe boomfoot pin to the shaftofthe head machinery.
Information about length is onlydisplayed while the Angle/Length push-button is pressed and held.
5 The WORKING AREA is displayed in the lower right ofthe upper right displayand descriptions
conformto the current configuration selected and to the swing position ofthe crane upper
6 OUTRIGGERS or TIRES selection is displayed in the lower leftofthe middle displayand is
determined bythe current dutyselection.
7The Lifting point will be displayed in the bottomdisplay.This will either be the Main Boomor the
AuxiliaryTip.
CRANE
SETUP
DEDUCT
WORKING
AREA
TARE
ERECTED TARE
SELECT
57.2 8 M 49.1
Lifting Point
1
23
4
6
7
OUTRIGGERS
150 FT Main Boom
5
360

MicroGuard 424 OPERATOR'S MANUAL Lattice/Horizontal Display
MG424 OPERATOR MANUAL Page 6 of 14 December 7, 2000
PUSH-BUTTONS ICONS AND LAMPS
LEFT DISPLAY
1 TEST is apush-button used to initiate a system
selftest and also press and hold to displayfault
codes.
2 CANCEL ALARM is apush-button used to
silence the audible alarmwhen the alarmhas
occurred as aresult ofeither an Overload or an
Operator Settable alarmhas been exceeded.
3 The PRE-ALARM(AMBER) indicator
illuminates at apre-set value of90% ofMaximum
Rated Capacityand provides avisual indication of
an approach to an overload.
4 The OVERLOADINDICATOR (RED)
illuminates at apre-set value of100% ofMaximum
Rated Capacityand provides a visual indication ofMaximumAllowed Load. It will also illuminate
whenever the wire rope limit is exceeded or an operator settable alarmhas been reached or exceeded.
5The BAR-GRAPH ICON is apart ofthe analog bar-graph in the leftdisplay.This displaybar-graph
gives avisual indication ofhowmuch ofthe crane's capacityis being used and the rate at which an
overload is being approached. The leading edge ofthe bar-graph aligns with three colored bands in the
bar-graph indicator. Red indicates an overload. Between the red and amber is ablacknotch which
indicates 100% ofrated capacity.The 100% RATED CAPACITY indicator is above the bar-graph in the
left displayand marks the point at which 100% ofthe rated capacityofthe crane has been reached.
6The INFORMATION AREA indicates the area ofthe leftdisplaywhich provides the operator with a
visual indication ofthe various alarms which mayoccur during normal operation ofthe system.
7 The ACTUALLOADICON Indicates the area ofthe displaywhich showsthe total load suspended
belowthe boom,flyor jib head. It includes the load, anyslings, pins or tackle used to secure the load and
also includes the weight ofthe hookblock.
8MAXIMUMRATED CAPACITY icon indicates the area ofthe left displaywhich gives aread-out of
maximumrated capacityfor the currentlyselected configuration.
9 VIEW is apush-button used during the setting ofoperator alarms. It is used to start the routine and
to viewthe current alarmsettings.
10 SET is a push-button used during the setting ofoperator alarms to set a newalarmsetting.
11 CLEAR is a push-button used during the setting ofoperator alarms to clear the current alarmsetting.
12 CONTRAST(DOWN) This is a push-button which is used to decrease the displaycontrast.
13 CONTRAST(UP) This is a push-button which is used to increase the displaycontrast.
W
TEST
W
MAX 100%
INFORMATION
LEFTDISPLAY
8
7
3
5
2
1 4
6
VIEW SET CLEAR DOWN UP
910 11 12 13

MicroGuard 424 OPERATOR'S MANUAL Lattice/Horizontal Display
MG424 OPERATOR MANUAL Page 7 of 14 December 7, 2000
UPPER RIGHT DISPLAY
1 RADIUS/HEIGHT indicates
the area ofthe displaywhich gives
aread-out ofradius and height. It
is also amomentarypush-button
used to select the alternate display
ofheight. Height is displayed only
when the push-button is pressed
and held. When the push-button
is not pressed the displayis
always the radius ofthe load.
2 PARTS-OF-LINE indicates the
area ofthe displaywhich gives a
read-out ofthe parts ofline
currentlyselected. It is also a
push-button used to select the
parts ofline in use on the selected
winch.
3 WINCH SELECT indicates the area ofthe displaywhich gives aread-out ofthe winch currently
selected. It is also the push-button which is used to select the Main or Auxiliarywinch. When switching
between winches the parts ofline previouslyselected for the other winch is remembered and displayed
whenever the alternate winch is selected.
4 ANGLE/LENGTH indicates the area ofthe displaywhich gives aread-out ofangle or length. It is also
amomentarypush-button used to select the alternate displayofLength. Length is displayed onlywhen
the push-button is pressed and held. When the push-button is not pressed the displayis alwaysthe Angle
ofthe main boom.
5 WORKING AREA indicates the part ofthe displaywhich showsthe working area. Messages in this
area will conformto the current dutyselection and the swing position ofthe crane upper for
machines which have swing and multiple working swing areas.
6 TARE is apush-button, which is used to “tare”out the weight ofhookand slings. The actual load
displaywill then displaythe actual weight ofthe load being lifted. The bargraph displaywill continue to
reflect the percentage ofthe total weight belowthe boomhead.
Toset the tare: With the hookand slings lifted, press and hold the TARE button for three seconds.
The displayconsole will beep after three seconds and will “zero”the actual load display.The TARE
lamp (#3 on next page) will then illuminate to indicate that a tare has been set.
Toclear the tare: Press the TARE button momentarily.The displayconsole will immediatelybeep,
the actual load displaywill showthe total weight belowthe boomhead and the TARE lamp (#3 on next
page) will be off.
7 CRANE SETUP indicates the area ofthe displaywhich gives aread-out ofthe selected on or off rail
configuration. It is also apush-button used to start the selection ofthe machine configuration.
CRANE
SET UP WORKING
AREA
TARE
1
2 3 4
5
6
7
UPPER RIGHT DISPLAY

MicroGuard 424 OPERATOR'S MANUAL Lattice/Horizontal Display
MG424 OPERATOR MANUAL Page 8 of 14 December 7, 2000
LOWER RIGHT PUSH BUTTONS AND ICONS
1/4 UP/DOWN ARROWS are push-buttons which are used as arrows for scrolling.
2 ERECTED DEDUCTINDICATOR is an amber lamp which indicates erected deducts. When a
erected deduct has been selected, the lampwill be illuminated to warn the operator that adeduct has
been applied to the allowed load. The deduct function onlyapplies on machines which have boom
attachments.
3 TARE INDICATOR is an amber lampwhich indicates to an operator that the actual load value
displayed has been “tared”out.. (See #6 on previous page)
5 SELECT is a push-button used to terminate all selections and calibration routines.
6/7 RIGHTand LEFTARROW are push-buttons used in calibration routines.
DEDUCT
ERECTED TARE
SELECT
1
2 3
4
5
67
LOWER RIGHT DISPLAY

MicroGuard 424 OPERATOR'S MANUAL Lattice/Horizontal Display
MG424 OPERATOR MANUAL Page 9 of 14 December 7, 2000
SYSTEMOPERATION
At start-up the systemautomaticallyperformsaself-test after which it goes directlyto the normal working
screen. The self-test can be initiated at anytimeduring normal operation ofthe systembyuse ofthe
TESTpush-button.
TEST
One press (press and release) will cause the systemto execute aselftest routine during which all lamps,
audible alarmsand digital displayswill be functionallytested and all memoryareas checked for accuracy.
Iffaults in the systemare detected during atest, the information area in the upper displaywill showthe
word FAULT.Ifthe word FAULToccurs, press and continue to hold the TESTbutton. This will cause
the displayto change to the FAULT mode. In this mode information about the fault condition will be
displayed in the upper right displaybymeans ofan error code.
CANCEL ALARM
Used to cancel the audible alarmwhen the alarmhas occurred as aresult ofeither an Overload or an
Operator Settable alarm.The audible alarmmaybe canceled bypressing and releasing the CANCEL
ALARM button. The audible alarm remains canceled until the condition which caused the alarmhas been
removed. For example, ifthe audible alarmwas canceled because ofan overload condition it will remain
canceled until the overload condition is removed. However, ifadifferent alarm,e.g. operator settable
alarm,was to occur when the audible alarmwas still canceled for an earlier overload condition, the new
alarmcondition would cause the audible alarmto be re-started.
CANCEL ALARM is also used to reset the function kick-out relaywhen it is necessaryto by-pass function
kick-out which has occurred as aresult ofeither an overload or an A.T.B. alarm.The relayisre-set by
first canceling the audible alarm[as described above] and then pressing and holding the CANCEL ALARM
button for about 5seconds after which the function kick-out relaywill be set to normal operation.
However, should another different alarmcondition occur when the relayhad previouslybeen over-ridden
then the newlyoccurring alarmcondition would cause the motion cut to be re-started.
CANCEL ALARMis atemporary function. The audible alarm or function kick-out is automatically reset
when the condition which caused the alarm is no longer present.
WHEN FUNCTION KICK-OUT IS RESET BY MEANS OF THE CANCEL ALARM
BUTTON YOU ARE NO LONGER PROTECTED AGAINST THE CONDITION WHICH
CAUSED THE FUNCTION KICK-OUT.
WARNING

MicroGuard 424 OPERATOR'S MANUAL Lattice/Horizontal Display
MG424 OPERATOR MANUAL Page 10 of 14 December 7, 2000
CONFIGURATION SELECTION
In the normal operational mode the systemis programmed to remember the configuration last selected.
Each time the systemis powered up it will automaticallychoose that configuration.
The menu for the crane set up consists ofup to four consecutive steps.
1. Select Outriggers, Tires, Rigging/Travel mode..
2. Select Main BoomLength.
3. Select Lifting Attachments.
4. Select lifting point Main winch.
STARTTHE SELECTION OF CRANE CONFIGURATION BYPRESSING "CRANE SETUP"
CRANE
SETUP
Select the
Chassis Config.
ñOR òOutriggers Pick and Carry Tires Rigging/Travel Mode
SELECT
Select the
Main BoomLength
ñOR ò40’–250’
SELECT
Select the
Lifting
Attachments
ñOR ò20’Jib 30’Jib 40’Jib 50’Jib
SELECT
Select the Main
Winch Lifting Pnt
ñOR òMain Boom 20’Jib 30’Jib 40’Jib 50’Jib
SELECT
Select the Aux
Winch Lifting Pnt
ñOR òMain Boom 20’Jib 30’Jib 40’Jib 50’Jib
SELECT
WINCH
The current selection is shownin the displaybyuse ofthe letter Mfor Main winch and the letter Afor
Auxiliarywinch. Tochange the selection press the WINCH select push-button. Successive pressing of the
button will change the selection fromone to the other. After the initial setup the systemremembers the
Parts-of-Line and Lifting Point and Deducts for each winch.
PARTS-OF-LINE

MicroGuard 424 OPERATOR'S MANUAL Lattice/Horizontal Display
MG424 OPERATOR MANUAL Page 11 of 14 December 7, 2000
Press and hold the PARTS-OF-LINE push-button to scroll through the available parts ofline. The new
value is automaticallyregistered when the button is released. The number chosen applies onlyto the
winch currentlyselected and a value must be programmed for both winches.
OPERATOR SETTABLE ALARMS
Aadditional feature of the system is the provision of Operator Settable Alarms. These alarms, when
properly set by the operator, provide amethod of obstacle avoidance. This is achieved by means of
minimum and maximum angle and maximum height alarms. These alarms can be programmed for each
job site and set rapidly for the prevailing site conditions thereby aiding the operator in safe operation of the
crane.
Most alarmswill occur automaticallyas aresult of limitations imposed bythe capacitychart. The operator
has control over additional alarmswhich are set to define the working range ofthe machine for particular
site requirements and which will provide a measure ofobstacle avoidance.
Three alarms are available for operator use.
MINIMUM ANGLE
MAXIMUM ANGLE
MAXIMUM HEIGHT
TEST
100%
INFORMATION
WORKING
AREA
TARE
CRANE
DEDUCT
ERECTED TARE
VIEW SET CLEAR
SELECT
DOWN UP
OPERATOR ALARMS CONTRAST
W
W
MAX
MicroGuard 414 MAXHEIGHT OFF
MIN ANGLE
MAXANGLE 31.5
OFF
SETUP
→

MicroGuard 424 OPERATOR'S MANUAL Lattice/Horizontal Display
MG424 OPERATOR MANUAL Page 12 of 14 December 7, 2000
METHOD OF SETTING
THE FOLLOWING EXAMPLES ARE GIVEN TOILLUSTRATETHE USE OF THE METHODS OF
SETTING ALARMS. THE ACTUAL VALUES GIVEN SHOULD NOTBE USED WITHOUTFIRST
CHECKING THE CAPACITYCHARTTOENSURE SAFE, STABLE OPERATION UNDER THE
CONDITIONS DESCRIBED.
OPERATOR ALARMS WILL BE STORED IN THE COMPUTER MEMORY,EVEN IF THE CRANE IS
SHUTDOWN. THE FOLLOWING PROCEDURES WILL DESCRIBE THE METHOD OF SETTING OR
CANCELING ALARMS.
Alarmscan onlybe SETor CLEARED fromwithin the alarm
screen. Fromthe main working screen press VIEW to access the
Operator Alarmscreen. The cursor is an arrowwhich points to
the alarmwhich maybe set or cleared and is alwaysat the first
position when entering the alarm screen. It maybe moved to any
position on the alarmscreen byuse ofthe UP/DOWN arrows.
When the cursor is pointing to an alarm,the numerical value
displayed will be the current position ofthe crane except when
that alarmhas previouslybeen SET.In this case the SETvalue
will be indicated and will alternate with the word SET.Alarmswhich are set but to which the cursor is not
pointing indicate the previouslyset value. Other alarmswhich are NOTSETare indicated bythe word
OFF.
The functions ofthe push-buttons when in the alarmscreen are:
♦VIEW Used to access the alarmscreen to viewthe currentlyset alarms.
♦SET Used to SET the alarm value. The alarm value is determined bythe position ofthe crane
at the time the SETbutton is pressed.
♦CLEAR Used to clear apreviouslySETalarm.Alarmscan onlybe CLEARED when the cursor is
pointing to the itemto be cleared. Use the UP/DOWNarrowsto move the cursor to the desired alarm.
Press CLEAR to cancel that alarm.
♦UP/DOWN ARROWS Used to move the cursor up or downthe screen to the alarmwhich is to
be viewed, SETor CLEARED.
♦SELECT Used to return to the normal operating screen.
WARNING
NOTE
INFORMATION
VIEW SET CLEAR DOWN UP
W
LEFTDISPLAY

MicroGuard 424 OPERATOR'S MANUAL Lattice/Horizontal Display
MG424 OPERATOR MANUAL Page 13 of 14 December 7, 2000
SETTING THE ALARMS.
Setting the alarm point is achieved bypositioning the crane at the point at which the alarmis to sound and
then, when in the operator alarmscreen, using the SETpush-button to set the alarm.The following
examples illustrate the use ofthe procedures.
EXAMPLE A
To have an alarmwhenever the boomis below30 degree angle, use the following procedure:
Press VIEW to access the alarmscreen. The cursor will be at MIN ANGLE.
Move the boomto 30 degree angle.
Press SET to enter the alarm.The displayed value will be the alarmsetting and it will alternate with the
word SET.
When the alarmis set press SELECT to return to the working screen. The red lampand the audible
alarmwill operate whenever the boomis below30 degrees. The message MIN ANGLE will appear in the
INFORMATION area on the left display.
EXAMPLE B
To have an alarmwhenever the boomis above 60 degree angle, use the following procedure:
Press VIEW to access the alarmscreen. The cursor will be at MIN ANGLE. Press the DOWNARROW
to move the cursor to MAX ANGLE.
Move the boomto 60 degree angle.
Press SET to enter the alarm.The displayed value will be the alarmsetting and it will alternate with the
word SET.Press SELECT to return to the working screen. The red lampand the audible alarmwill
operate whenever the boomis above 60 degrees. The message MAX ANGLE will appear in the
INFORMATION area on the left display.
EXAMPLE C
To have an alarmwhenever the boomtip height exceeds 75 feet, use the following procedure:
Extend the boomand/or adjust the boomangle so that the tip height is 75 feet.
Press VIEW to access the alarmscreen. The cursor will be at MIN ANGLE. Press the DOWNARROW
to move the cursor to MAX HEIGHT.
Press SET to enter the alarm.The displayed value will be the alarmsetting and it will alternate with the
word SET.Press SELECT to return to the working screen. The red lampand the audible alarmwill
operate whenever the boomtip height exceeds 75 feet. The message MAX HEIGHTwill appear in the
INFORMATION area on the left display.

MicroGuard 424 OPERATOR'S MANUAL Lattice/Horizontal Display
MG424 OPERATOR MANUAL Page 14 of 14 December 7, 2000
CANCELING ALARMS
CLEAR is used to cancel apreviouslySETalarm.Alarmscan onlybe CLEARED when the cursor is
pointing to the item to be cleared. Canceling of alarmscan be carried out regardless of the position of the
crane.
Press VIEW to access the alarm screen.
Move the cursor to point to the alarmto be canceled.
Press CLEAR to cancel the alarm.The displayed value will be the current position ofthe crane and the
word SETwill no longer be displayed.
Move the cursor to point to the next alarmto be canceled.
When all the chosen alarms are canceled press SELECT to return to the working screen.
SYSTEM CHECKS
♦Checkthat the displayed boomangle agrees with the measured angle.
♦Checkthat the displayed radius agrees with the measured operating radius.
♦Ifaknowntest weight is available, checkthat the displayed weight agrees with the test load. The
displayed load includes the hookblock and any lifting attachments such as slings, pins and
shackles.
ROUTINE MAINTENANCE
The systemhas built-in self-test facilities and checksitselfeach timethe systemis switched on. Onlya
minimumlevel of preventive maintenance is required. This is restricted to visual inspections ofcables and
sensors for obvious signs ofwear and tear and inspection ofmechanical parts such as line riders.
Other manuals for 414
1
Table of contents
Popular Measuring Instrument manuals by other brands

Pulsar
Pulsar 22 user manual

Crosby
Crosby SP Handheld Plus SW-HHP user manual

PCB Piezotronics
PCB Piezotronics IMI SENSORS ICP 628F01/ICS-43 Installation and operating manual

AquaMaster Tools
AquaMaster Tools Combo pen P160 Pro user manual

Electroswitch
Electroswitch 25-1000 Operation manual

Anderson
Anderson IZMSG instruction manual