
MCAC-CTSM-2018-1 Flooded type water cooled screw chiller (MIC) 
3 
 
I. Safety precautions 
Before use, carefully read these instructions . 
1. Installation safety considerations 
(1) Only authorized personnel, qualified and trained in HVAC system maintenance can access the unit. The 
access limitation device must be installed by the customer (e.g. cut-off, enclosure). Units should be 
inspected for damage upon receipt, before installation, and before powered on.Check the refrigerant 
circuit(s) is (are) intact and in place, especially components and pipes. If in doubt, carry out a leak 
tightness check and verify with the manufacturer that the circuit integrity has not been impaired. If 
damage is detected upon receipt, immediately submit a claim with the shipping company. Midea 
strongly recommends employing a specialist company to unload the machine. 
(2) It is compulsory to wear personal protection equipment. Do not remove the skid or the packaging 
until the unit is in its final position. Move these units with a fork lift truck, providing the forks are in the 
right place. 
(3) The units can also be lifted with slings, using only the designated lifting points marked on the unit. 
Use slings that are the correct capacity, and always follow the lifting instructions on the certified 
drawings supplied with the unit. Safety is only guaranteed, if these instructions are followed carefully. 
If this is not the case, there is a risk of damage or injury. Never cover any safety devices. This 
applies to the relief valve(s) in the refrigerant circuit(s). Ensure that the valves are correctly installed, 
before operating the unit. 
(4) The relief valves are designed and installed to ensure protection against overpressure caused by 
fire. The relief valve must only be removed if the fire risk is fully controlled and after checking that 
doing so is allowed by local regulations and authorities. This is the responsibility of the operator. If 
the unit is installed in a room, the safety valves must be connected to discharge pipes. 
Note: 
These pipes must be installed in a way that ensures that people and property are not exposed to 
refrigerant leaks. These fluids may be diffused in the air, but far away from any building air intake, or they 
must be discharged in a quantity that is appropriate for a suitably absorbing environment. Install an 
indicating device to show if part of the refrigerant has leaked from the valve. The presence of oil in the 
outlet is a useful indicator that refrigerant has leaked. Keep the outlet clean to ensure that any leaks are 
obvious. The calibration of a valve that has leaked is generally lower than its original calibration. The 
new calibration may affect the operating range. To avoid tripping or leaks, replace or re-calibrate the 
valve. Periodically check the relief valves. Ensure good ventilation, as an accumulation of refrigerant in 
an enclosed space can displace oxygen and cause asphyxiation or explosions. Inhalation of high 
concentrations of vapor is harmful and may cause heart irregularities, unconsciousness, or death. Vapor 
is heavier than air and reduces the amount of oxygen available for breathing. These products cause eye 
and skin irritation. Decomposition products are hazardous. 
2. Maintenance safety considerations 
2.1 Engineers safety considerations