Mircom MS-700AP Series User manual

www.mircom.com LT-2071 Rev. 1 Dec. 2015
MS-700AP(U) Series
Fire Alarm Manual Station
1
Mircom’s MS-700AP(U) Series Fire Alarm Manual Stations
provide manual fire alarm activation. These high quality, die-cast
metal stations are available as single or dual-action devices. Each
station has a permanently attached AP addressable module,
which has a pair of dials for setting the address.
Specifications & Dimensions
Compatible with Mircom Fire Alarm Control Panels
Electrical Rating:
Dimensions:
MS-702AP: 4.93” H x 3.56” W x 2.56” D
MS-710AP(U): 4.93” H x 3.56” W x 2.9” D
Converting Double Action Manual Stations to Single
Action (MS-710AP(U) only):
1. Using a reset key, unlock and open the manual station.
2. Remove the smaller two screws and accompanying
brackets fastening the PUSH bar.
3. Hold the manual station vertically with one hand with the
keyhole at the bottom. Tilt the manual station towards
you and remove the PUSH bar.
Installing the manual station
This guide covers these models:
MS-702AP Intelligent Two Stage Manual Station AP
MS-710AP(U) Intelligent Dual Action Manual Station AP
The suffix Uindicates a USA version.
Contents of kit
MS-702AP: 4 mounting screws, 2 reset keys (black), 2 stage two
keys, 1 glass rod
MS-710AP(U): 4 mounting screws, 2 reset keys (black), 1 glass
rod
A. Wiring
Note: The maximum wire size is 12 AWG.
1. Connect the black (-) wire from the previous station to
the terminal that is connected to the black (-) wire from
the addressable module.
2. Connect the black (-) wire leading the next station to the
other side of the terminal that is connected to the black
(-) wire from the addressable module.
Note: The wires must be on opposite sides of the set screw.
Refer to Figure 2 for the location of the wires.
3. Tighten the (-) terminal.
4. Connect the red (+) wire from the previous station to the
terminal that is connected to the red (+) wire from the
addressable module.
5. Connect the red (+) wire leading to the next station to the
other side of the terminal that is connected to the red (+)
wire from the addressable module.
Note: The wires must be on opposite sides of the set screw.
Refer to Figure 2 for the location of the wires.
6. Tighten the (+) terminal.
MS-702AP MS-710AP(U)
Nominal Operating Voltage:
15-32 VDC Nominal Operating Voltage:
15-32 VDC
Maximum alarm current @ 24V:
5.4 mA Maximum alarm current @ 24V:
600 µA
Average operating current @
24V: 600 µA Average operating current @
24V: 400 µA
Notes
• Wire as shown so that supervision of connections is
maintained.
• Maximum wire size: 12 AWG
• ADA compliant.
• To be installed per ADA 4.27.1 to 4.27.4 inclusive.
• All manual fire alarm stations shall be installed as per
the specific requirements outlined in the UL/ULC codes,
as well as all other applicable national or local codes.
Final acceptance is subject to the local authority having
jurisdiction.
ScrewsScrews
Figure 1: Wiring Diagram
TO ADDRESSABLE
MODULE
WRONG: BOTH
WIRES ON THE
SAME SIDE AS
THE SET SCREW
TO ADDRESSABLE
MODULE
CORRECT: BOTH
WIRES ON
OPPOSITE SIDES
OF THE SET SCREW
X
Figure 2: Close-up of terminals showing correct wiring
FROM
TO NEXT STATION OR
END OF LINE DEVICE
-BLACK
+RED
}
-
-
+
+
ADDRESSABLE
MODULE
PREVIOUS
STATION
}
Canada
25 Interchange Way
Vaughan, ON L4K 5W3
Tel: (888) 660-4655
Fax: (888) 660-4113
U.S.A
4575 Witmer Industrial Estates
Niagara Falls, NY 14305
Tel: (888) 660-4655
MS-700AP(U) Series
Fire Alarm Manual Station
www.mircom.com LT-2071 Rev. 1 Dec. 2015
2
B. Setting the addressable module
Note: MS-702AP: Pull the module out of the bracket to set the
address.
MS-710AP(U): Slide the module sideways out of the
bracket to set the address.
The AP addressable module allows for an address range of 1 to
159. The TENS dial goes to 15 (unlike the CLIP module, where
the TENS dial goes to 9).
Note: The module is set to 1 by default. For proper operation,
you must change this to a different address.
The following table shows how to set the dials for some example
addresses.
If the dials are set to a number higher than 99, and the panel
supports only CLIP, then the panel will see the device as an
unrecognized device at address 0.
The MS-710AP(U) counts as one address, which is set by the
dials on the addressable module.
The MS-702AP counts as two addresses. The first address
represents the PULL handle, and is set by the dials on the
addressable module. The second address is one number higher
than the dial setting and represents the switch activated by the
stage two key.
For example, if you set the dials on the MS-702AP to the address
M, then M represents the PULL handle, and M+1 represents the
stage two key switch.
Note: Because the MS-702AP counts as two addresses,
always set the dial address at least 1 below the
maximum value. If the panel supports only CLIP, set the
address no higher than 98, and if the panel supports AP,
set the address no higher than 158.
C. Mounting
1. Open the station with the reset key.
2. Mount the station to a surface mounted box with 2 of the
included screws. Refer to Figure 3.
D. Inserting the glass rod
Inside the station, there is an opening below the white PULL
handle. This is where the glass rod sits.
1. Pull down the PULL handle part way.
2. Carefully insert the glass rod into the opening below the
PULL handle.
3. Move the PULL handle back to the upright position. The
PULL handle should now be holding the glass rod in
place.
4. Close and lock the station.
Using the manual station in
case of fire
Activating the alarm
• MS-702AP
1. Pull down the PULL handle.
• MS-710AP(U)
1. Push in the PUSH bar.
2. Pull down the PULL handle.
The handle is now hanging down. A qualified person must reset
the station by opening it with the reset key. See Resetting the
manual station below.
Activating the stage two alarm (MS-702AP only)
• Insert the stage two key into the keyhole above the PULL
handle, and then turn the key.
The stage two alarm activates.
Note: The stage two alarm will activate automatically a certain
amount of time after the handle has been pulled. This
time is set in the Fire Alarm Control Panel. You can
prevent the stage two alarm from activating automatically
by using the Automatic Alarm Signal Timer Cancel
feature on the Fire Alarm Control Panel. Refer to the Fire
Alarm Control Panel manual for instructions.
Resetting the manual station
You use the reset key to open the station in order to reset it.
Note: Resetting the station does not reset the alarm.
1. Open the station with the reset key. The switch is now reset.
2. If you want to insert a glass rod, see Inserting the glass rod
above.
3. Move the PULL handle back to its upright position.
4. Close and lock the station.
5. Reset the Fire Alarm Control Panel to reset the alarm.
Address TENS dial ONES dial
202
21 2 1
135 13 5
150 15 0
MANUAL STATION 4” GANG BOX
SCREW
SCREW
SCREW HOLE
SCREW HOLE
BACK OF MANUAL STATION
Figure 3: Mounting the manual station

This manual suits for next models

2

Other Mircom Fire Alarm manuals

Mircom flexnet User manual

Mircom

Mircom flexnet User manual

Mircom FleXNet FNC-2000 User manual

Mircom

Mircom FleXNet FNC-2000 User manual

Mircom MS-700ID SERIES User manual

Mircom

Mircom MS-700ID SERIES User manual

Mircom RAM-300LCD Series User manual

Mircom

Mircom RAM-300LCD Series User manual

Mircom MPS-800MP Series User manual

Mircom

Mircom MPS-800MP Series User manual

Mircom MPS-800MP Series User manual

Mircom

Mircom MPS-800MP Series User manual

Mircom MS-400MP Series User manual

Mircom

Mircom MS-400MP Series User manual

Mircom FleX-Net BBX-1024DS User guide

Mircom

Mircom FleX-Net BBX-1024DS User guide

Mircom MPS-800 Series User manual

Mircom

Mircom MPS-800 Series User manual

Mircom FX-350 Series User manual

Mircom

Mircom FX-350 Series User manual

Mircom FleX-Net FX-2003-12NDS User manual

Mircom

Mircom FleX-Net FX-2003-12NDS User manual

Mircom FX-350 Series User manual

Mircom

Mircom FX-350 Series User manual

Mircom RAM-300LCD Series User manual

Mircom

Mircom RAM-300LCD Series User manual

Mircom FleX-Net FX-4000 User manual

Mircom

Mircom FleX-Net FX-4000 User manual

Mircom QX-mini User manual

Mircom

Mircom QX-mini User manual

Mircom FA-1000 SERIES User manual

Mircom

Mircom FA-1000 SERIES User manual

Mircom FA-102T User manual

Mircom

Mircom FA-102T User manual

Mircom MPS-800MPU Series User manual

Mircom

Mircom MPS-800MPU Series User manual

Popular Fire Alarm manuals by other brands

Apollo SA5900-948 installation guide

Apollo

Apollo SA5900-948 installation guide

Convoy Security DG333 user manual

Convoy Security

Convoy Security DG333 user manual

Cooper Wheelock E50 installation instructions

Cooper Wheelock

Cooper Wheelock E50 installation instructions

Bosch FSM-2000 installation guide

Bosch

Bosch FSM-2000 installation guide

Advanced MxPro4 Series Installation Sheet & Quick Reference Guide

Advanced

Advanced MxPro4 Series Installation Sheet & Quick Reference Guide

Notifier IFS-2600 Product installation document

Notifier

Notifier IFS-2600 Product installation document

Edwards MPSR Series Installation sheet

Edwards

Edwards MPSR Series Installation sheet

SILENT KNIGHT INTELLIKNIGHT 5820XL Installation and operation manual

SILENT KNIGHT

SILENT KNIGHT INTELLIKNIGHT 5820XL Installation and operation manual

Cooper Notification ET70-24MCCH Series installation instructions

Cooper Notification

Cooper Notification ET70-24MCCH Series installation instructions

Notifier FS-WST Installation and maintenance instruction manual

Notifier

Notifier FS-WST Installation and maintenance instruction manual

Fire-Lite BG-12SL Installation

Fire-Lite

Fire-Lite BG-12SL Installation

Simplex 4100ES-S1 Installation & maintenance

Simplex

Simplex 4100ES-S1 Installation & maintenance

Teledata s.r.l. ONEMINI User and installation manual

Teledata s.r.l.

Teledata s.r.l. ONEMINI User and installation manual

Ei Electronics Ei2110 User instructions

Ei Electronics

Ei Electronics Ei2110 User instructions

Tyco MZX125 user manual

Tyco

Tyco MZX125 user manual

Honeywell Fire-Lite BG-12LX quick start guide

Honeywell

Honeywell Fire-Lite BG-12LX quick start guide

Funke+Huster Fernsig 2014/2 manual

Funke+Huster Fernsig

Funke+Huster Fernsig 2014/2 manual

Simplex SafeLINC 4020 installation instructions

Simplex

Simplex SafeLINC 4020 installation instructions

manuals.online logo
manuals.online logoBrands
  • About & Mission
  • Contact us
  • Privacy Policy
  • Terms and Conditions

Copyright 2025 Manuals.Online. All Rights Reserved.