Mircom FleXNet MIX-4000 User manual

FX-4000 Intelligent Fire Detection and Voice Evacuation System
Installation and Operation Manual LT-894MP Rev 2
November 2022
All MGC MIX-4000 Series Detectors are not FM Approved

i
Table of Contents
1.0 Introduction 1
2.0 System Components 6
3.0 Mechanical Installation and Dimensions 15
4.0 Display and Adder Modules Mounting Locations 23
5.0 Module Settings 28
6.0 Field Wiring 50
7.0 System Checkout 68
8.0 Indicators, Controls, and Operation 69
9.0 Configuration 79
10.0 Typical FleX-Net™ System Layouts with Audio 80
11.0 System Components for the Integrated Fire/Audio Cabinet 82
12.0 FleX-Net™ Mass Notification System (BBX-FXMNS) Enclosure 84
13.0 Mechanical Installation for the QBB-5001(R) Expansion Audio Cabinet 88
14.0 BBX-FXMNS Audio Module Placement and Internal Wiring 89
15.0 Integrated Fire Alarm Connection 90
16.0 QBB-5001(R) Expansion Audio Cabinet Module Placement 91
17.0 Installing and Removing Amplifiers 93
18.0 Multiple QBB-5001/R Cabinet Connections 94
19.0 Audio Network Card and Telephone Network Card 95
20.0 Audio Amplifier Wiring 96
21.0 Amplifier Displays & Controls 106
22.0 QBB-5001(R) Amplifier Installation 107
23.0 Audio Configuration 108
24.0 ANC-4000 Audio Network Controller Module 109
25.0 ANC-4000 Wiring 110
26.0 QMP-5101NV Vertical Paging Control Module 112
27.0 QMP-5101N Network Master Paging Control Module 113
28.0 QMP-5101NV/N Network Paging Wiring 115
29.0 QAZT-5348DS and QAZT-5302DS Zoned Paging Selector Panels 116

ii
30.0 Paging Operation 117
31.0 TNC-5000 Telephone Network Controller Module 119
32.0 QMT-5302NV Vertical Master Telephone 124
33.0 QMT-5302N Master Firefighters’ Telephone 126
34.0 QMT-5302N Connections 127
35.0 QAZT-5348DS and QAZT-5302DS Firefighters’ Telephone Selector Panel 128
36.0 Telephone Operation 130
37.0 Appendix A: Specifications 131
38.0 Appendix B: Power Supply and Battery Calculations 136
39.0 Appendix C: DIP Switch Settings 138
40.0 Appendix D: Alarm Verification Timing 139
41.0 Appendix E: Wiring For Addressable Supervised Output Module 140
42.0 Appendix F: Power Supply & Batteries for Audio 141
43.0 Appendix G: FXMNS Used as a Mass Notification System (ACU) 142
44.0 Appendix H: APB-200/COA Sounder Bases 146
45.0 Appendix I: Label Requirements for Zone Identification 147
46.0 Warranty and Warning Information 148

1
1.0 Introduction
1.1 About the FleX-Net™ FX-4000 Intelligent Fire Detection and Voice
Evacuation System
Mircom’s FleX-Net™ FX-4000 Intelligent Fire Detection and Voice Evacuation System offers
modular components for network systems providing a wide variety of applications. Designed
for peer to peer network communications, using industrial standard ARCnet protocol. FleX-
Net™ allows for a maximum of 63 nodes (a node can be acontrol center or a floor panel) while
providing reliability and flexibility.
Each base panel consists of 4 Class Aor B Indicating Circuits or notification appliance circuit
(NACs) rated at 1.7 amperes each. Alarge 4 x 20 back-lit alphanumeric 8- line LCD display
and a 24 line graphical display are available. Additional SLC loops are available with MGC
Protocol Quad Loop Adder module ALCN-960MISO for expanding addressable loops (SLC)
by 2; together with daughter board ALCN-960D expanding addressable loops by a total of 4.
Also available is the Quad Loop Adder module ALCN-4792MISO for expanding addressable
loops (SLC) by2; with daughter board ALCN-792D expanding addressable loops by a total
of 4.
The configuration allows the FleX-Net™ Fire Alarm Control Panels to be connected to a
Mircom network which provides additional input circuits, visual zones, programmable
notification appliance circuits and relays. In addition, a FleX-Net™ Integrated Fire and Audio
panel can be used to provide a fully distributed audio and/or integrated telephone system.
The FleX-Net™ FX-4000 provides zoned emergency multi-channel audio providing
emergency paging and fire evacuation, and an optional firefighters’ telephone communication
to and from CACF (Central Alarm and Control Facilities) location to all remote telephone
handsets. The system consists of an Integrated Fire and Audio Network Panel or FX-MNS
nodes. Each Integrated Fire and Audio Network Panel or FX-MNS contains an audio portion
which consists of a QMB-5000N motherboard and card cagewhich holds an ANC-4000
Audio Network Card, a TNC-5000 Telephone Network Card and up to 4 amplifiers, a fire
alarm portion FX-4000MNS Main Chassis, a PS-2040 power supply and batteries. The
QBB-5001(R) expansion audio cabinet (connected to a Integrated Fire and Audio Network
Panel or FX-MNS node) contains a card cage motherboard which holds up to 7amplifiers,
has an audio power supply, battery charger and batteries all housed in an audio backbox
enclosure.
For communication and annunciation there is a microphone for paging, a paging selector
panel, a firefighters’ telephone and associated selector panels. The master paging and
telephone modules are intended for installation in a CACF. Note that the paging microphone
and firefighters’ telephone may be used together or independently, connected to a FleX-Net™
Network Central Alarm and Control Facility (CACF).
1.2 Overall Features
• Large System Capacity and Modular Design.
• Provides peer-to-peer network communications
• Supports up to 63 nodes (including lobby panel).
• Supports copper and/or fiber optic network cable.
• Supports a request, grant, or deny system with all controls disabled on node
annunciators (ancillary displays only) as per ULC 527-11.
• Supports a degraded mode of operation (more than one operating node) and a
standalone mode of operation (only one operating node) as per ULC 527-11.
All MGC MIX-4000 Series Detectors are not FM Approved

2
• MGC Protocol Quad Loop Adder module ALCN-960MISO for expanding addressable
loops (SLC) by 2; with daughter board ALCN-960D expanding addressable loops by a
total of 4. Each SLC Loop is set to function with MGC MIX-4000 Series addressable
modules (240 sensors and modules) and can be wired as Class A (Class X) or Class B.
• AP Protocol Quad Loop Adder module ALCN-4792MISO for expanding addressable
loops (SLC) by 2; with daughter board ALCN-792D expanding addressable loops by a
total of 4.
• 12 Ampere Power Supply.
• Four Class A or B NACs rated at 1.7 Amperes each, which can be configured as Audible
or Visual (silenceable or non-silenceable circuits). Audibles may be steady, Temporal
Code, California Code, or March Time.
• Indicating circuits (NACs) may be configured to provide additional auxiliary power or
resettable auxiliary power. NAC expansion using the INX-10A, INX-10ADS or INX-10AC.
• Fault isolators are present on all in-panel addressable loops.
• Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, Assisted
Walk Test.
• Outputs for 4 Wire resettable Smoke Power Supply, Auxiliary Power Supply, and an
interface to the Mircom RTI-1 Remote Trouble Indicator.
• RS-485 Interface for Remote Annunciators. Remote Annunciators do not occupy a node
on the network. Up to seven annunciators can be connected per node.
• Three Level Password Protection with field settable definition which enables the installer
to determine what functions are accessible for each level of password
• Four queues for acknowledge with Alarm Queue, Supervisory Queue, Trouble Queue,
and BLDG (Monitor) Queue LED indicators and pushbuttons.
• Auxiliary Form-C Relay Contacts for Common Alarm, Common Supervisory, and
Common Trouble.
• RS-232 Port for remote system printer or “CRT terminal”.
• Two Event History Logs; one for Alarm related events and one for all events.
• Common Controls and Indicators for System Reset, Lamp Test (Visual Indicator Test),
Fire Drill, Signal Silence, General Alarm, General Alarm Cancel (Automatic Alm Sig
Stop), AC On, CPU Fault, and Ground Fault.
• Two Spare configurable switches and LED Indicators.
• 16 Zone configurable LED (bi-coloured) Annunciator with slide-in labels for Zone
Description with the DSPL-420-16TZDS Display.
• Provides drift compensation for ionization and photoelectric smoke detectors
• Provides Signal Coding of signal circuits for easy alarm identification (code consists of 1
to 4 digits, each digit consisting of 1-15 pulses on the signal)
• Selection for Canadian (ULC) or USA (ULI) requirements for Smoke Sensor sensitivity.
• Extensive transient protection.
• Surface Mountable Enclosures with removable doors for easy installation and service.
Flush trims available.
• Removable Terminal Blocks for easy wiring and service.
•OPEN Graphic Navigator Software Package allows 3D graphic display of premises
and devices. Use the Ethernet port on the main board to connect to OpenGN graphics
software.

3
1.3 Overall Audio Features:
• Supervises signal circuits while in use.
• Control of fire management operations (e.g. all-call paging and total evacuation
signalling).
•Indication of all required fault conditions.
• Microprocessor-based operations with hardware and software watchdog timer to ensure
reliable system operation.
•Supervised tone generators.
• Up to 100 audio zones per node, 1575 audio amplifiers per Network system.
• Up to 5 (analog) firefighters’ telephone zones per node and 315 (analog) telephone
zones per Network system. 99 addressable telephone zones per loop, maximum of 29
addressable telephone loops per node, maximum of 144 addressable telephone zones
per system.
•Easy configuration process.
• Operates from 24 VDC backup batteries in the event of a power failure.
• Removable terminal blocks for ease of installation and maintenance.
• Speaker circuits integrated with amplifier circuits.
• Maximum of 180 Watts per BBX-FXMNS.
• Maximum of 360 Watts per QBB-5001(R) expansion cabinet and 1260 Watts of total
power per BBX-FXMNS node with maximum expansion [180W +360W(3)=1260W].
• Optional redundant backup amplifier per node.
1.4 Document Conventions
1.5 Circuits and Zones
The term circuits refers to an actual electrical interface, initiating (detection), indicating
(signal), or relay.
The term zone is a logical concept for a fire alarm protected area, and will consist of at least
one circuit.
Often the terms zone and circuit are used interchangeably, but in this manual the term circuit
is used.
On the FleX-Net™ circuits can be hardwired inputs and outputs or addressable inputs and
outputs. Both hardwired inputs and outputs, and addressable inputs and outputs may be
grouped together to form logical zones.
1.6 Wiring Styles
Initiating circuits are configured by default as Class B. They may be configured as Class A
as described in System Configuration. This operation uses odd and even pairs of two-wire
Class B circuits to make one four-wire Class A circuit, thus cutting in half the number of
available initiating circuits.
Indicating circuits (NACs) may be individually wired as Class A or Class B without affecting
the number of circuits available.
Addressable Loops may be configured system wide as Class B, Class A. With the addition of
isolators, a Class A will become a Class X.

4
RAXN-4000LCD
in a BB-1001DR
Class A wiring
Twisted Pair Wiring
RAXN-4000LCD
in a BB-1001DR
Node 5
FX-4003-12N in a UB-1024DS
with a DOX-1024DSR Door
RS-485
Node 4
FX-4009-12N in a BB-5008R
CACF
RS-485
Node 3
FX-4017-12N in a BBX-1072ARDS
RAXN-4000LCD
in a BB-1001DR
RS-485
Node 1
FX-4003-12NXT in a
BBX-1024XTR
Node 2
FX-4003-12N in a UB-1024DS
with a DOX-1024DSR Door
Typical FleX-Net FX- 4000 Wiring Without Audio
TM

5
Five Telephone
Five Telephone
RAXN-4000LCD
in BB-1001DR
RAXN-4000LCD
in BB-1001DR
Paging
ARCnet
Audio
Telephone
Internal RS-485
Audio
Typical FleX-Net FX-4000 Wiring With Audio
TM
IPS-4848DS FDX-008W
Fan Damper Controller
RAX-1048TZDS
AGD-048
RAXN-4000LCD
Annunciator
FOM-2000-UM Fiber Optic
Network Module
ALCN-960MISO Analog Loop
Network Module
UDACT-300A Digital
Communicator Module
FX- 4000N
Main Board
-2000
FDX-008K
Fan Damper Controller
Conventional Devices
Addressable Devices (not available with FleX-NetMP)
Addressable Devices
Node 2 - Floor Panel
Node1
Node 3 - Floor Panel
ANC-4000 & TNC-5000 in Audio Card Cage
Phone Line 1
Five Telephone
Circuits per TNC-5000 Handsets
Phone Line 2
FNC-2000 Network
Controller Module
Loop 2
Speakers
Paging Audio
Alert
Evac
RM-1008A
Relays
SGM-1004A
Signal
DM-1008A
Inputs
PTR-2000-1
AGD-048
IPS-4848DS
Zone Bypass
RAX-1048TZDS
Graphic Driver Display Adder
and/or
NOTES:
(5) Annunciators RAXN-4000LCD and RAXN-4000LCDG can support a maximum of 41 frames each,
which include IPS-4848DS, IPS-2424DS, FDX-008W/KI, AGD-048, RAX-1048TZDS and QAZT-5348.
(4) The system supports a maximum of 7 annunciators per node.
(6) If high speed digitized audio is used only the ARCnet or Fiber Optic wiring is required between nodes.
(1) The main board has two conventional loops, one SLC loop (not available when using ALCN-960MISO)
and 4 Class B NAC circuits.
(2) The main FX-4000N supports a maximum of 12 frames (a frame is a measure of display capacity).
(3) Each FX-4000N supports a maximum of seven ALCN-960MISO (ALCN-4792MISO) Quad Addressable Loop
Adder modules plus ALCN-960D (ALCN-792D) for a total of 28 loops per FX-4000N.
ARCnet Network , Fire Control, Paging
Audio and Telephone

6
2.0 System Components
2.1 Chassis Types
Model Description
FX-4003-12N
12 Amp Main Chassis. This main chassis provides
four Class A or B NACs (1.7 Amp each), and a 12
ampere power supply which charges 17-65 AH
batteries. The FX-4003-12N supports the FNC-2000
Network Controller Module and 2 adder modules
over the main board plus additional space in the
chassis for 2 annunciator or programmable modules.
This chassis mounts in the BBX-1024DS enclosure
comprising a UB-1024DS black backbox and a door.
A white door DOX-1024DS or DOX-1024DSR red
door are available.
Shown here with a DSPL-420DS 4 line by 20
character LCD display.
This model does not support any network audio.
FX-4003-12NXT
12 Amp Expanded Main Chassis. This expanded
main chassis provides four Class A or B NACs (1.7
Amp each), and a 12 ampere power supply which
charges 17-65 AH batteries. The FX-4003-12NXT
supports the FNC-2000 Network Controller Module
and 2 adder modules over the main board plus
additional space in the chassis for 6 adder boards
and 2 annunciator or programmable modules. This
chassis mounts in the BBX-1024DS enclosure
comprising a UB-1024DS black backbox and a door.
A white door DOX-1024DS or DOX-1024DSR red
door are available.
Shown here with a DSPL-420DS 4 line by 20
character LCD display.
This model does not support any network audio.
FX-4017-12N
12 Amp Mid-Size Main Chassis. This mid-size main
chassis provides four Class A or B NACs (1.7 Amp
each), and a 12 ampere power supply which charges
17-65 AH batteries. The FX-4017-12N supports the
FNC-2000 Network Controller Module and 2 adder
modules over the main board plus additional space in
the chassis for 14 adder boards and 3 annunciator or
programmable module. This chassis mounts in the
BBX-1072ADS black backbox/white door or BBX-
1072ARDS black backbox/red door.
Shown here with a DSPL-420DS 4 line by 20
character LCD display.
This model does not support any network audio.

7
2.1 Network Controller Modules
Model Description
FX-4009-12N
12 Amp Large Main Chassis. This large main
chassis provides four Class A or B NACs (1.7 Amp
each), and a 12 ampere power supply which charges
17-65 AH batteries. The FX-4009-12N supports the
FNC-2000 Network Controller Module and 2 adder
modules over the main board plus additional space in
the chassis for 6 adder boards and 3 annunciator or
programmable modules. This chassis mounts in the
BB-5008 or BB-5014 black backbox/black door or
BB-5008R black backbox/red door.
Shown here with a DSPL-420DS 4 line by 20
character LCD display.
This is model does not support any network audio.
FX-4000MNS
Consists of a backplate which is mounted into the
BBX-FXMNS backbox and a FX-4000N Fire Alarm
Control board and a battery disconnect board.
ECX-0012
Expander Chassis to use with the FX-4009-12N. It
provides space for 12 adder modules and two display
modules. This chassis mounts into the BB-5008(R) or
BB-5014 backbox.
Model Description
FNC-2000
Provides network capability for the FX-4000N
Fire Alarm panel. One module is required per
one network node panel. The FNC-2000 Fire
Network Controller module is mounted in position
2 over the FX-4000N main board.
ANC-4000
Audio Network Controller module. The ANC-
4000 Audio Network Controller module is
mounted over a metal plate (which is packaged
with the FX-4009-12N) and then the plate is
mounted in a BB-5008 or BB-5014 backbox in
positions marked 4 to 9 inclusive. The
recommended plate mounting is sideways with
LEDs across the top.

8
2.2 Adder Modules
Model Description
TNC-5000
Telephone Network Controller module. The TNC-
5000 Telephone Network Controller module is
mounted over the ANC-4000 Audio Network
Controller module and both are mounted on a
metal plate and then the plate is mounted in a
BB-5008 or BB-5014 backbox in positions
marked 4 to 9 inclusive. The recommended plate
mounting is sideways with LEDs across the top.
FOM-2000-UM
Fiber Optics Module (Optional)
Connects to the FNC-2000 Fire Alarm Network
Controller Module and allows fiber optics cabling.
Model Description
ALCN-960MISO MGC Protocol Quad Loop Adder module
provides two SLC loops.
ALCN-960D
MGC Protocol Quad Loop Daughter Adder board
provides an additional two SLC loops to the two
provided with the ALCN-906MISO.
ALCN-4792MISO AP Protocol Quad Loop Adder module provides
two SLC loops.
ALCN-792D
AP Protocol Quad Loop Daughter Adder board
provides an additional two SLC loops to the two
provided with the ALCN-4792MISO.
DM-1008A Eight Initiating Circuit Module

9
2.3 Display Modules
Model Description
SGM-1004A Four NAC circuit Module
RM-1008A Eight Relay Circuit Module
PR-300 Polarity Reversal and City Tie Module
UDACT-300A Digital Communicator/Dialer Module
Model Description
DSPL-420DS
4 line by 20 character display which can be
mounted into backboxes BBX-
1072ADS(ARDS), BB-5008(R), BB-5014 and
the BBX-FXMNS Backbox.
DSPL-2440
Graphic display which can be mounted in
backboxes BBX-1072ADS(ARDS), BB-
5008(R), BB-5014 and the BBX-FXMNS
Backbox
DSPL-420-16TZDS
4 line by 20 character display which provides 16
zone alarm and trouble indicators. can be
mounted in backboxes, BBX-1072ADS(ARDS),
BB-5008(R), BB-5014 and the BBX-FXMNS
Backbox.

10
2.4 Programmable Modules
2.5 Audio and Telephone Modules
Model Description
IPS-4848DS 48 Programmable Input Switches Module
IPS-2424DS 24 Programmable Input Switches Module
FDX-008W
FDX-008WKI
Fan Damper Module with white LEDs for AUTO
switch position indication. FDX-008W provides
switch operation of 8 fan damper zones and the
FDX-008WKI provides switch operation of 7
fan damper zones and one keyswitch operation
of the 8th fan damper zone.
Model Description
QMP-5101N Network Master Paging Control Panel
QMP-5101NV
Network Master Paging Control Panel (Vertical
Mount) mounts within the BBX-FXMNS
enclosure.
QMT-5302N Network Master Telephone Control Panel

11
2.6 Booster Power Supply
Model Description
QMT-5302NV
Network Master Telephone Control Panel
(Vertical Mount) mounts within the BBX-
FXMNS enclosure.
QAZT-5348DS 48 Zone Paging and Telephone Selector Panel
QAZT-5302DS 24 Zone Paging and Telephone Selector Panel
Model Description
INX-10AC
Addressable Booster Power Supply mounts to
backboxes BB-5014 and BBX-FXMNS. Same
unit as the INX-10A and INX-10ADS, except
this model comes with a chassis for mounting.
Refer to LT-899 manual for more detailed
instructions.

12
2.7 Enclosures
2.8 Remote Annunciators
Model Description
BBX-1024DS white door black backox
(add suffix “R” for red door/black backbox)
Enclosure 27.5”H x 16.5”W x 5.5”D
BBX-1024XT white door black backbox
(add suffix “R” for red door/blackbox)
Enclosure 35.5”H x 16.5”W x 5.5”D
BBX-1072ADS white door black backbox (or
BBX-1072ARDS for red door black backbox) Enclosure 34”H x 26.5”W x 7.7”D
BB-5008 black door and backbox
(add suffix “R” for red door/black backbox)
Backbox 36”H x 30”W x 7”D
BB-5014 black door and backbox Backbox 60”H x 30”W x 7”D
BBX-FXMNS Enclosure with white door
assembly (add suffix “R” for red door/black
backbox)
Backbox 61.5”H x 22”W x 9”D
FA-1072TR Flush Trim Ring Black flush trim for BBX-1072ADS
and BBX-1072ARDS Backboxes.
Model Description
RAXN-4000LCD
Remote Shared Display
Annunciator. Please refer to LT-
895MP RAXN-4000LCD manual
for further information.
RAXN-4000LCDG
Remote Shared Graphical
Display Annunciator. Please refer
to LT-6033MP RAXN-4000LCDG
manual for further information.
DSPL-420-16TZDS
4 line by 20 character display
which provides 16 zone alarm
and trouble indicators. can be
mounted in the BBX-FXMNS-
6000 backbox

13
Model Description
RAM-1032TZDS
RAM-1032TZDS-CC
Model RAM-1032TZDS Main
Chassis Remote Annunciator with
16 Bi-coloured LEDs and 32
trouble LEDs. Model RAM-
1032TZDS-CC is the same as the
RAM-1032TZDS, except it has
conformal coating and is to be
used in a BB-1001WP(R)A or BB-
1002WP(R)A weather protected
box.
RAX-1048TZDS
RAX-1048TZDS-CC
Model RAX-1048TZDS Adder
Annunciator Chassis with 48 Bi-
coloured LEDs and 48 trouble
LEDs. Model RAM-1048TZDS-
CC is the same as the RAM-
1058TZDS, except it has
conformal coating and is to be
used in a BB-1002WP(R)A
weather protected box.
MGD-32 Master Graphic Driver
Annunciator Board
AGD-048 Adder Graphic Driver Board
RAM-216(R) Annunciator with 16 Bi-coloured
LEDs.
RAM-208(R) Annunciator with 8 Bi-coloured
LEDs.
RTI-1 Remote Trouble Indicator (single
LED and trouble buzzer).

14
2.9 FX-LOC(R) Local Operating Console
2.10 Batteries
2.11 FleX-Net™ Accessories
Model Description
FX-LOC(R) consists
of:
FX-LOC Enclosure
includes backbox, inner
door and outer white door.
FX-LOCR, the R suffix
represents a red door.
Main Display RAXN-
4000LCD.
Audio indication and
selector panel QAZT-
5348DS.
Master paging
microphone, model
QMP-5101N.
The FX-LOC(R) Local Operating Console along
with the Mircom FleX-Net™ Network Fire Alarm
system facilitates a Mass Notification System.
The FX-LOC(R) provides critical emergency (as
well as fire) information to be communicated
within buildings.
Refer to LT-6039 FX-LOC(R) Installation
Instruction Manual for further details.
Model Description
BAT-12V18A
BAT-12V26A
BAT-12V33A
BAT-12V42A
BAT-12V55A
BAT-12V75A
Batteries available from 18 to 75 AH
FleX-Net™ charging range is 17 to 65 AH.
Model Description
MP-300(R)(S) End-of-line Resistor Plate, R for red, S for stainless steel finish
BC-160(R) External Battery Cabinet (ULC and ULI listed)

15
3.0 Mechanical Installation and Dimensions
Install the enclosure as shown for the BBX-1024DS installation information is in Figure 1. For
the BBX-1072ADS see Figure 2. Figure 3 demonstrates the BB-5008 backbox installation.
Figure 1 .BX-1024DS Flush and Surface Enclosure Installation and Dimensions
23 1/2”
5 3/4”
1 1/2”
4 1/4”
12”
LEFT SIDE VIEW
BACKBOX FRONT VIEW
17”
14 1/2”
28 ”
26 ”
BACKBOX
DOOR
1 3/4” 1 3/4”
6”
2”
9 1/2”
1 3/4”
1 3/4”
2” 2”
TOP VIEW
RIGHT SIDE VIEW
KNOCKOUT LOCATIONS
Dimensions of backbox (minus built-in trim ring)
Horizontal distance between mounting screws
Vertical distance between mounting screws
Complete dimensions of enclosure with door
Size of Knockouts:
Material of backbox and door: 16 GA (0.059”) thick cold rolled steel
Finish of backbox and door: Painted
26”H x 14 1/2”W x 4 1/4” D
12”
1”
23 1/2”
28”H x 17”W x 5 3/4”D
BBX-1024DS BACKBOX AND DOOR

16
Figure 2 BBX-1072ADS Flush and Surface Installation and Dimensions
Material: Cold rolled steel, 16GA
(0.059”)thick for backbox,
14GA (0.075”) thick for door
Finish: Painted except for hinges

17
Figure 3 BB-5008 Enclosure Installation Instructions and Dimensions
Backbox
BB-5008 Backbox
DOX-5008M Metal Door
Backbox with DOX-5008M Door
Material: Cold rolled steel
16GA (0.059”) thick for backbox
14GA (0.075”) thick for door
Finish: Painted except for hinges