FX-350 Series
Analog/Addressable Fire Alarm Panels
LT-959 Rev. 5
March 2016
Advanced Life Safety Solutions
U.S.A.
60 Industrial Parkway
Cheektowaga, NY 14227
Tel: 1-888-660-4655 Fax: 1-888-660-4113
Installation and Operation Manual
For the latest compatability information visit www.mircom.com/deviceguide


3
Table of Contents
Table of Contents
1.0 Industry Canada and FCC Notice 9
1.1 Notice for all FX-350 Series Built-In UDACTs Sold in Canada ...................................... 9
1.1.1 Industry Canada Notice ................................................................................................. 9
1.1.2 Notice for all FX-350 Series Built-in UDACTs Sold in the U.S.A. .................................. 9
1.1.3 FCC Notice .................................................................................................................... 9
2.0 Introduction 11
2.1 Features ......................................................................................................................... 11
3.0 Conventions 13
3.1 Circuits .......................................................................................................................... 13
3.2 Zone/Group .................................................................................................................... 13
3.3 Display Points ............................................................................................................... 13
3.4 Wiring Styles ................................................................................................................. 13
4.0 System Components 14
4.1 Panel Models ................................................................................................................. 14
4.2 Output Class A converter: four circuits .......................................................................... 16
4.3 Polarity reversal/city tie .................................................................................................. 16
4.4 Remote Annunciator ...................................................................................................... 16
4.5 Smart Relay Module ...................................................................................................... 17
4.6 RAM-216 Ancillary Annunciator ..................................................................................... 17
4.7 Panel Components and System Accessories ................................................................ 18
4.8 Analog/Addressable Devices ......................................................................................... 18
5.0 Mechanical Installation 20
5.1 Installing the Enclosures ................................................................................................ 20
5.2 BBX-1024DS and BBX-1024DSR Mechanical Installation ............................................ 23
6.0 Installing Adder Modules 24
6.1 Cable and Jumper Connections for Main Board and Adder Modules ........................... 25
6.2 Connectors and Jumpers on the Main Fire Alarm Board ............................................... 27
6.3 OCAC-304 Output Class A Converter Adder Module ................................................... 27
6.4 Polarity Reversal and City Tie Module (Model PR-300) ............................................... 28
6.4.1 PR-300 Cable and Jumper Settings ............................................................................. 28

4
Table of Contents
6.5 RAX-332 Display Adder Module .................................................................................... 28
7.0 Circuits and Devices 29
7.1 Addressable/Analog Devices ......................................................................................... 29
7.2 Analog Devices .............................................................................................................. 30
7.2.1 Drift Compensation ........................................................................................................ 30
7.2.2 Auto Test ........................................................................................................................ 30
7.3 Contact Inputs ................................................................................................................ 30
7.4 Contact Outputs ............................................................................................................. 30
8.0 Field Wiring 31
8.1 Main Fire Alarm Board Field Wiring ............................................................................... 31
8.2 Loop Isolators ................................................................................................................. 32
8.3 Loop Operation .............................................................................................................. 32
8.4 Indicating (Powered Output) Circuits ............................................................................. 33
8.5 Indicating Circuit Wiring ................................................................................................. 33
8.6 Dialer Wiring ................................................................................................................... 35
8.7 Polarity Reversal and City Tie Module (PR-300) Wiring ............................................... 37
8.8 Auxiliary Power Supplies ................................................................................................ 38
8.8.1 Aux 2 Resettable Auxiliary Power (supervised, regulated) ............................................ 38
8.8.2 Auxiliary Supply (supervised, regulated) ....................................................................... 38
8.8.3 Unfiltered Supply (unsupervised, unregulated) ............................................................. 38
8.9 Power Supply Connections ............................................................................................ 39
8.10 Connecting to a DCS SurGuard Receiver ...................................................................... 40
9.0 System Checkout 41
9.1 Before turning the power “ON” ....................................................................................... 41
9.2 Power-up procedure ....................................................................................................... 41
10.0 Troubleshooting 42
11.0 Indicators, Controls and Operations 43
11.1 Common Indicators ........................................................................................................ 44
11.1.1 Buzzer ............................................................................................................................ 44
11.1.2 AC On LED .................................................................................................................... 44
11.1.3 Common Alarm LED ...................................................................................................... 44
11.1.4 Common Supervisory LED ............................................................................................. 44
11.1.5 Common Trouble LED ................................................................................................... 44
11.1.6 CPU Fault LED ............................................................................................................... 44
11.1.7 Ground Fault LED .......................................................................................................... 44

5
Table of Contents
11.1.8 System Reset LED ......................................................................................................... 44
11.1.9 Signal Silence LED ........................................................................................................ 45
11.1.10 Fire Drill LED .................................................................................................................. 45
11.1.11 ALM/SUP/TBL/BLDG AUDIBLE SIL LED (Buzzer Silence) ........................................... 45
11.1.12 AUTOMATIC ALARM SIGNAL CANCEL LED (Acknowledge) ...................................... 45
11.1.13 General Alarm LED ........................................................................................................ 45
11.1.14 Lamp Test LED .............................................................................................................. 45
11.1.15 Battery/Charger Trouble LED ........................................................................................ 45
11.1.16 LEDs 1 to 32 for FX-351 and FX-353 Series Only ......................................................... 45
11.1.17 RAX-332 LEDs 33 to 64 for FX-351 and FX-353 Series Only ....................................... 45
11.2 Common Controls .......................................................................................................... 46
11.2.1 LCD Display ................................................................................................................... 46
11.2.2 Cursor Buttons ............................................................................................................... 46
11.2.3 Enter Button ................................................................................................................... 46
11.2.4 Cancel Button ................................................................................................................ 46
11.2.5 Menu Button ................................................................................................................... 46
11.2.6 Info Button ...................................................................................................................... 46
11.2.7 Signal Silence Button ..................................................................................................... 46
11.2.8 Fire Drill Button .............................................................................................................. 46
11.2.9 General Alarm Button .................................................................................................... 46
11.2.10 System Reset Button ..................................................................................................... 47
11.2.11 AUTOMATIC ALARM SIGNAL CANCEL Button (Two Stage or PAS only) ................... 47
11.2.12 Lamp Test Button ........................................................................................................... 47
11.3 Single Stage Operation .................................................................................................. 47
11.4 Two-Stage Operation ..................................................................................................... 48
11.5 Positive Alarm Sequence ............................................................................................... 49
11.6 Enabling or Disabling the Positive Alarm Sequence ...................................................... 50
11.7 Input Types .................................................................................................................... 50
11.8 Output Types ................................................................................................................. 53
11.9 Evacuation Codes .......................................................................................................... 53
11.10 Initial Power-up Sequence ............................................................................................. 54
11.10.1 Status Display Mode ...................................................................................................... 55
11.10.2 Queue Display Mode ..................................................................................................... 56
12.0 Remote Annunciator Operation 57
12.1 Conventional Annunciators (RA-1000 Series) ............................................................... 57
12.2 Supervision .................................................................................................................... 57
12.3 Shared Display Annunciator (RAM-300LCD) ................................................................. 57
12.4 Supervision .................................................................................................................... 57
13.0 Dialer Operation 58
13.1 Event Reporting ............................................................................................................. 58
13.2 Telephone line supervision ............................................................................................ 58

6
Table of Contents
14.0 Appendix A: Compatible Receivers 59
15.0 Appendix B: Reporting 60
16.0 Appendix C: Specifications 62
16.1 FX-350 Series Specifications ......................................................................................... 62
16.2 FX-350 System Modules and Annunciators ................................................................... 63
17.0 Appendix D: Power Supply and Battery Calculations 64
18.0 Warranty & Warning Information 66

7
List of Figures
List of Figures
Figure 1 Wallbox Dimensions / Mounting the FX-350 – Surface ................................................. 20
Figure 2 Mounting the FX-350 - Flush ........................................................................................ 21
Figure 3 Flush Trim Detail ............................................................................................................ 21
Figure 4 Wallbox Dimensions / Mounting the FX-351/FX-353 – Surface /Flush ......................... 22
Figure 5 BBX-1024DS and BBX-1024DSR Installation Instructions and Dimensions ................. 23
Figure 6 Installation of Adder Modules ........................................................................................ 24
Figure 7 Main Fire Alarm Board Cable Connectors and Jumper Locations ................................. 25
Figure 8 Main Board (3 loop model) Cable Connectors and Jumper Locations .......................... 26
Figure 9 OCAC-304 Output Class A Converter Adder Modules .................................................. 27
Figure 10 Polarity Reversal and City Tie Module .......................................................................... 28
Figure 11 Addressable Loop Wiring - Class B or Style 4 ............................................................... 31
Figure 12 Addressable Loop Wiring - Class A or Style 6 ............................................................... 32
Figure 13 Indicating Circuit – Class B or Style Y Wiring ................................................................ 35
Figure 14 Indicating Circuit –Class A or Style Z Wiring ................................................................. 35
Figure 15 Dialer Wiring .................................................................................................................. 36
Figure 16 Polarity Reversal and City Tie Module Terminal Connection ........................................ 37
Figure 17 Supervision Of Auxiliary Supplies .................................................................................. 38
Figure 18 Main Power Supply Connections ................................................................................... 39
Figure 19 Connecting an FX-350 FACP to a DCS Surguard System Receiver ............................. 40
Figure 20 LCD Display, LED indicators and control buttons ......................................................... 43
Figure 21 Evacuation and Alert Codes .......................................................................................... 54

8
List of Tables
List of Tables
Table 1 FX-350 Series Comparison Chart .................................................................................. 15
Table 2 Settings permitted in CAN/ULCS527 ............................................................................. 31
Table 3 Loop Wiring Table .......................................................................................................... 32
Table 4 Maximum Wiring Distances ............................................................................................ 33
Table 5 Input Types .................................................................................................................... 50
Table 6 Output Types .................................................................................................................. 53
Table 7 Ademco Contact-ID - FX-350 Series Event Codes ........................................................ 60
Table 8 Security Industries Association SIA-DCS - FX-350 Series Event Codes ....................... 61
Table 9 FX-350 Series Specifications ......................................................................................... 62
Table 10 FX-350 System Modules and Annunciators ................................................................... 63
Table 11 FX-350 Batteries ............................................................................................................ 65

9
Industry Canada and FCC Notice
1.0 Industry Canada and FCC Notice
1.1 Notice for all FX-350 Series Built-In UDACTs Sold in Canada
Mircom's FX-350 SERIES BUILT-IN UDACT Communicator described in this manual is listed
by Underwriters Laboratories Canada (ULC) for use in slave application in conjunction with a
Listed Fire Alarm Control Panel under Standard ULC-S527 (Standard for Control Units for Fire
Alarm Systems) and ULC/ORD-C693-1994 (Central Station Fire Protective Signalling Systems
and Services). These Communicators should be installed in accordance with this manual; the
Canadian / Provincial / Local Electrical Code; and/or the local Authority Having Jurisdiction
(AHJ).
1.1.1 Industry Canada Notice
Repairs to certified equipment should be made by an authorized Canadian maintenance
facility designated by the supplier. Any repairs or alteration made by the user to this
equipment, or equipment malfunctions, may give the telecommunications company cause to
request the user to disconnect the equipment. Users should ensure for their own protection
that the Earth Ground connections of the power utility, telephone lines and internal metallic
water pipe system, if present, are connected together. This is necessary both for proper
operation and for protection.
1.1.2 Notice for all FX-350 Series Built-in UDACTs Sold in the U.S.A.
Mircom's FX-350 SERIES BUILT-IN UDACT Digital Communicator described in this manual
is listed by Underwriters Laboratories Inc. (ULI) for use in slave application in conjunction with
a Listed Fire Alarm Control Panel under Standard 864 (Control Units for Fire Protective
Signalling Systems). These Communicators comply with the National Fire Protection
Association (NFPA) performance requirements for UDACTs and should be installed in
accordance with NFPA 72 Chapter 4 (Supervising Station Fire Alarm System). These
Communicators should be installed in accordance with this manual; the National Electrical
Code (NFPA 70); and/or the local Authority Having Jurisdiction (AHJ).
1.1.3 FCC Notice
This equipment complies with Part 68 of the FCC rules and the requirements adopted by the
ACTA. On the telco transformer of this equipment is a label that contains, among other
information, a product identifier in the format US:1M8AL02BFX350. If requested, this number
Attention: Users should not attempt to make such connections themselves, but
should contact the appropriate electric inspection authority, or
electrician, as appropriate
Notes: The Ringer Equivalence Number (REN) assigned to each terminal device
provides an indication of the maximum number of terminals allowed to be
connected to a telephone interface. The termination on an interface may consist
of any combination of devices subject only to the requirement that the sum of the
Ringer Equivalence Numbers of all the devices does not exceed 5.
The Label Identification Number for this product is US:1M8AL02BFX350. The
02B represents the REN without a decimal point (e.g., 02B is a REN of 0.2B). For
earlier products, the REN is separately shown on the label.
!
i

10
Industry Canada and FCC Notice
must be provided to the telephone company. This equipment is capable of seizing the line.
This capability is provided in the hardware.
Type of Service: The Communicator is designed to be used on standard device telephone
lines. It connects to the telephone line by means of a standard jack called the USOC RJ-11C
(or USOC FJ45S). Connection to telephone company provided coin service (central office
implemented systems) is prohibited. Connection to party lines service is subject to state tariffs.
Telephone Company Procedures: The goal of the telephone company is to provide you with
the best service it can. In order to do this, it may occasionally be necessary for them to make
changes in their equipment, operations or procedures. If these changes might affect your
service or the operation of your equipment, the telephone company will give you notice, in
writing, to allow you to make any changes necessary to maintain uninterrupted service.
In certain circumstances, it may be necessary for the telephone company to request
information from you concerning the equipment which you have connected to your telephone
line. Upon request of the telephone company, provide the FCC registration number and the
ringer equivalence number (REN); both of these items are listed on the equipment label. The
sum of all of the REN’s on your telephone lines should be less than five in order to assure
proper service from the telephone company. In some cases, a sum of five may not be usable
on a given line.
If Problems Arise: If any of your telephone equipment is not operating properly, you should
immediately remove it from your telephone line, as it may cause harm to the telephone
network. If the telephone company notes a problem, they may temporarily discontinue service.
When practical, they will notify you in advance of this disconnection. If advance notice is not
feasible, you will be notified as soon as possible. When you are notified, you will be given the
opportunity to correct the problem and informed of your right to file a complaint with the FCC.
Contact your telephone company if you have any questions about your phone line. In the
event repairs are ever needed on the Communicator, they should be performed by Mircom
Technologies Ltd. or an authorized representative of Mircom Technologies Ltd. For information
contact Mircom Technologies Ltd. at the address and phone numbers shown on the back page
of this document.

11
Introduction
2.0 Introduction
Mircom’s FX-350 Series Analog/Addressable Fire Alarm Control Panel provides a loop for
60,126 or three loops for 378 input and output devices, four supervised Class B or A (Style Y
or Z) indicating circuits, a full range of auxiliary power supplies, and extensive common control
features via its integrated LCD display and push button console. Many of its features are fully
configurable utilizing the built-in configuration capability via the front panel display and
switches. The panels are available with or without an optional, integrated dialer/modem
(except the FX-353 version which always includes the dialer/modem), and is available (FX-
351 and FX-353 - in a larger enclosure) with an internal LED display for up to 64 points (32
standard). Optional modules include Polarity Reversal and City Tie, RAX-332 LED Display
Adder, and Class A Converter for indicating circuits. Semi-flush or surface mountable
enclosures can be used for retrofits and on new installations. This manual covers the following
panels:
2.1 Features
•The FX-350 panels support a loop of 60 or 126 analog devices and up to 3 loops of 378
analog devices, including thermal, ion, photo detectors, and contact input and output
devices. Drift compensation and Auto Test features are provided for analog devices.
•Four Power Limited Class B (Style Y) indicating circuits. Each indicating circuit may be
configured as Class A (Style Z) using an output Class A converter adder module. Each
indicating circuit may be configured as silenceable signal, non-silenceable signal,
silenceable strobes, non-silenceable strobes, or relay output. The audible signal may be
Steady, Temporal Code, California Code, or March Time. The system provides the
necessary protocols to sync strobes from major manufacturers.
•Two-stage, alarm verification, and waterflow retard operations available.
•Configurable Signal Silence Inhibit, Auto Signal Silence, Two-Stage Operation, and
One-Man Walk Test. For Canadian installations, disable Auto Signal Silence.
•Subsequent Alarm, Supervisory, and Trouble operation.
Note: Installation of the FX-350 Series Fire Alarm Control panel should be in
accordance with Canadian Electrical Code Part 1, ULC-S524 installation of Fire
Alarm System, National Electrical Code NFPA 70 and NFPA 72. Final
acceptance subject to the Local Authority Having Jurisdiction (AHJ).
FX-350-60-DR 60 pt addressable FACP (w/ dialer)
FX-351-LW 126 pt addressable FACP (w/ one 32 point LED display)
FX-351-LDW 126 pt addressable FACP (w/ dialer and one 32 point LED display)
FX-351-LDR 126 pt addressable FACP (w/ dialer)
FX-353-LW 378 pt addressable FACP without LED strip (w/ dual loop adder and one
32 point LED display)
FX-353-LDR 378 pt addressable FACP without LED strip (w/ dialer and dual loop
adder)
FX-350-60D 60 pt addressable FACP (w/ dialer)
FX-351-LD 126 pt addressable FACP (w/ dialer)
i

12
Introduction
•provides a regulated, supervised 21.1VDC auxiliary power supply @ 500mA max.;
unfiltered, unsupervised 24V FWR power supply @ 1.7 A max and a resettable auxiliary
power supply @ 300mA max.
•Relay Contacts for Common Alarm, Common Supervisory and Common Trouble all
non-disconnectable and Auxiliary Alarm Relay (disconnectable).
•Output for remote trouble indicator and Buzzer (RTI).
•RS-485 Interface for RAM-300LCD Annunciators, RA-1000 Series Remote
Annunciators and SRM-312 Smart Relay Modules (max total of 7 remote annunciators).
•Optional Module for City Tie and Polarity Reversal Signaling.
•Extensive transient protection
•With or without built-in UDACT (Digital Alarm Communicator Transmitter)
•Extensive and easy configuration of the panel via the integrated LCD display and
keypad
•Remote dial up (with built-in UDACT version) for event log checking and/or configuration
changing

13
Conventions
3.0 Conventions
3.1 Circuits
Refers to a physical electrical interface for the analog loop, indicating signals or relays, and
common alarm, supervisory, and trouble relay outputs.
3.2 Zone/Group
Is a logical concept for a Fire Alarm Protected Area, and will consist of at least one Circuit.
Groups are used extensively in the FX-350 to facilitate annunciation of multiple input and
output points on the 32 (up to 64) LED display and to facilitate bypassing of inputs and
outputs.
3.3 Display Points
The FX-350 provides an LCD display to annunciate the status of the system and connected
devices. The FX-351 and FX-353 also provides up to 64 LED display points on the panel front
in addition to the LCD display. Display points may be assigned to LEDs during configuration to
groups of inputs or outputs. There are two LEDs for every display point: one single color
(amber) and one dual color (red/amber).
3.4 Wiring Styles
The analog loop can be connected in Class B (Style Y) or Class A (Style D) configurations.
Changing the indicating circuits to Class A requires an OCAC-304 adder board which will
convert four indicating zones from Class B (Style Y) circuits to Class A (Style Z). This is done
without reducing the number of circuits.
Note: The Model FX-350-60-R and FX-350-60DR panels DO NOT recognize any
devices with addresses higher than 60.
i

14
System Components
4.0 System Components
4.1 Panel Models
All FX-350 Series Panels have the following features:
•Multi-zone fire alarm control panel with 2 x 20 LCD display.
•Style Y or Style D analog loop(s).
•Four Power Limited Class B (Style Y) indicating circuits (max 1.7 Amps each - 5 Amps
total).
•Dedicated common alarm, supervisory, trouble, and auxiliary alarm relays.
•Additional RAX-332 Display Adders can be added to provide 64 annunciation points per
added.
•An optional OCAC-304 Class A converter module may be used to convert the indicating
circuits to Class A (Style Z).
•Additional outputs include connections for a RTI remote trouble indicator, PR-300
Reverse Polarity Module, an RS-485 bus for connection of up to seven RAM-300LCDs,
SRM-312s and RA-1000 Series annunciators.
•Auxiliary power is available in the form of 24V FWR unfiltered and unsupervised, 24VDC
filtered and regulated, and resettable auxiliary power supply.
COMMONALARM
COMMONSUPV
COMMON
TROUB LE
CPUFAULT
GROUND
FAULT
SYSTEM
RESET
FIRE
DRILL
AUTOMATIC ALARM
SIGNAL CANCEL
GENE RA L
ALARM
SIGNAL
SILENCE
ALM/SUP/TBL/BLDG
AUDIBLE SIL
LAMP
TES T
SPARE
ACON
1 2
ABC
3
DEF
5
JKL
6
MNO
7 8
TUV
9
WXY
* 0
QZ
#
4
GHI
PRS
X
M
?
SYSTEM NORMAL
DEC 03, 2010 02:41PM
FX-350 SERIES
Fire Alarm Control Panel
SYSTEM
RESET
FIRE
DRILL
GENER AL
ALARM
SIGNAL
SILE NCE
LAMP
TEST
SPARE
AC ON
1 2
ABC
3
5 6
7 8 9
* 0 #
4
X
M
?
DEF
GHI JKL MNO
PRS TUV WXY
QZ
COMMON AL ARM
COMMON SUPV
COMMON T ROUBL E
CPU F AUL T
GROUNDF AUL T
SYSTEM NORMAL
DEC 03, 2009 10:25AM
ZON E -1
ZON E -1
ZON E -1
ZON E -1
ZON E - 1
ZON E - 1
ZON E - 1
ZON E - 1
ZON E -1
ZON E -1
ZON E -1
ZON E -1
ZON E - 1
ZON E - 1
ZON E - 1
ZON E - 1
ZON E -1
ZON E -1
ZON E -1
ZON E -1
ZON E - 1
ZON E - 1
ZON E - 1
ZON E - 1
ZON E -1
ZON E -1
ZON E -1
ZON E -1
ZON E - 1
ZON E - 1
ZON E - 1
ZON E - 1
FX-350 SERIES
Fire Alarm Control Panel
ALM/SUP/TBL/BLDG
AUDIBLE SIL
AUTOMATIC ALARM
SIGNAL CANCEL
SYSTEM
RESET
FIRE
DRILL
GENER AL
ALARM
SIGNAL
SILE NCE
LAMP
TEST
SPARE
AC ON
1 2
ABC
3
5 6
7 8 9
* 0 #
4
X
M
?
DEF
GHI JKL MNO
PRS TUV WXY
QZ
COMMON AL ARM
COMMON SUPV
COMMONTROUBLE
CPU F AUL T
GROUND F AUL T
SYSTEM NORMAL
DEC 3, 2009 3:25AM
FX-350 SERIES
Fire Alarm Control Panel
AUTOMATIC ALARM
SIGNAL CANCEL
ALM/SUP/TBL/BLDG
AUDIBLE SIL
FX-350-60DR FX-351-LDR
FX-353-LDR FX-351-LW
FX-351-LDW
FX-353-LW
FX-350-60D
FX-351-LD

15
System Components
See Table 1 for the specifics of each panel.
Some models may not be available in all markets. Verify with your local distributor.
Table 1 FX-350 Series Comparison Chart
Model # of devices # of
analog
loops
2 line UDACT
Digital
Communicator
(y/n)
Door
Color
# of 32
pointLED
Displays
Max # of
LED
Displays
Dual
Loop
Adder
(y/n)
FX-350-60-DR 60 1 y red n/a n/a n
FX-351-LW 126 1 n white 1 2 n
FX-351-LDW 126 1 y white 1 2 n
FX-351-LDR 126 1 y red 0 2 n
FX-353-LW 378 3 n white 1 2 y
FX-353-LDR 378 3 y red 0 2 y
FX-350-60D 60 1 y purchased
separately
purchased
separately 2n
FX-351-LD 126 1 y purchased
separately
purchased
separately 2n

16
System Components
4.2 Output Class A converter: four circuits
4.3 Polarity reversal/city tie
4.4 Remote Annunciator
Model Description
OCAC-304 Output Class A converter module (four
circuits)
Model Description
PR-300 Polarity Reversal and/or City Tie Module
Model Description
RAM-300LCDR Remote Annunciator module, LCD display,
white painted box
RAM-300LCDR Remote Annunciator Module, LCD display,
red painted box
- SIG1 OUT+- SIG2 OUT+
- SIG1 RET+- SIG2 RET+
BLK RED
BLK RED
- SIG3 OUT+- SIG4 OUT+
- SIG3 RET+- SIG4 RET+
BLK RED
BLK RED
POLARITY
REVE R SAL
ALARM
POLARITY
REVE R SAL
SUPV
CIT Y
TIE
+ | - + | - + | -
JW4
P1 P2
Mounting hol e for
#6 - 32 scr ews
Mounting hol e for
# 6- 32 scr ews
FA-300 SERIES
Remote Annunciator
SYSTEM
RES E T
SIGNAL
SILENCE
FI RE
DRI LL
LA MP
TEST
1
4
7
*
2
5
8
0
3
6
9
#
ENTER
MEN U
CANCEL
INFO
ABC DEF
GHI JKL MNO
PRS TUV WXY
QZ
A. C. ON ALARM SUPV TRB L CP U FAIL
SYSTE M NORMAL
18:01 MO N 2003-04-05
Adv anced Life Safety S ol utions
BUZZER
SILENCE

17
System Components
4.5 Smart Relay Module
4.6 RAM-216 Ancillary Annunciator
Model Description
SRM-312W Smart Relay Module (12 relays) with white
enclosure
SRM-312R Smart Relay Module (12 relays) with red
enclosure
Model Description
RAM-216 16 Zone ancillary annunciator
REMOTE RELAY
Advanced Life Safety S olutions
FA-300 SERIES
A.C.
ON COMMON
TROUBLE SIGNAL
SILEBCE
BUZZER
SILENCE SI GNAL
SILENCE
LAMP
TEST SYSTEM
RESET
SWITCH
ENABLE
FIREALARM
ANNUNCIATOR

18
System Components
4.7 Panel Components and System Accessories
4.8 Analog/Addressable Devices
MODEL NO. DESCRIPTIONS
ALC-252 252 Point Dual Loop Addressable Adder
RAX-332 32 Zone Internal Display Adder (for FX-351 and FX-353 only)
RAM-208/R 8 LED Remote Annunciator
RAM-1016/TZ Remote Annunciator with 16 bi-colored (red and yellow) LEDs.
TZ version has 32 yellow LEDs for trouble indication.
RAM-1032/TZ Remote Annunciator with 32 bi-colored (red and yellow) LEDs.
TZ version has 32 yellow LEDs for trouble indication.
RAX-1048/TZ Remote Annunciator with 48 bi-colored (red and yellow) LEDs.
TZ version has 48 yellow LEDs for trouble indication.
MGD-32 Graphic Annunciator
AGD-048 Graphic Annunciator Adder Driver Board
RTI-1 Remote Trouble Indicator, Buzzer and LED
FA-300-TRB Trim Ring For Small Enclosure (Black)
FA-UNIV-TRB Universal Trim Ring For Big Enclosure (Black)
BB-1001(R) Enclosure for one annunciator, white. R version is red.
BB-1002(R) Enclosure for two annunciators, white. R version is red.
BB-1003(R) Enclosure for three annunciators, white. R version is red.
BB-1008(R) Enclosure for eight annunciators, white. R version is red.
BB-1012(R) Enclosure for twelve annunciators, white. R version is red.
MP-300 End-of-line resistor plate, 3.9K ohm
BC-160 External Battery Cabinet
Description Mircom Model
Ionization Smoke Detector (U.S. Model Only) MIX-3000
Photoelectric Smoke Detector MIX-3100
*Multi-sensor (photoelectric with supplemental rate-of-rise heat sensor) MIX-3200
Heat Detector MIX-3300
Bases Mircom Model
4 inch Standard Base MIX-2000
6 inch E-Z Fit Base MIX-2001

19
System Components
6 inch Base with Relay MIX-2001R
6 inch Base with Sounder MIX-2001H
6 inch Base with Temporal Tone Sounder MIX-2001HT
Ancillary Modules Mircom Model
Priority Monitor Module MIX-100P
Mini Priority Monitor Module MIX-101P
Single Relay Output Module (1 Form C Contacts, 2 Gang Mount) 55000-820
Supervised Control Module MIX-100S
Isolator c/w Mounting Base
MIX-100X (Kit)
100XH (Isolator)
100XB (Base)
Addressable Duct Detectors Mircom Model
Ionization Duct Smoke Detector (UL Listed) MIX-DH3000
Photoelectric Duct Smoke Detector (UL Listed) MIX-DH3100
Ionization Duct Smoke Detector with relay (UL Listed) MIX-DH3000R
Photoelectric Duct Smoke Detector with relay (UL Listed) MIX-DH-3100R
Addressable Pull Stations Mircom Model
Addressable Single Stage Pull Station MS-401ID(U)
Addressable Two Stage Pull Station (Canadian Model Only) MS-402ID
Addressable Single Stage Single Action Pull Station MS-701ID(U)
Addressable Two Stage Single Action Pull Station MS-702ID(U)
Addressable Single Stage Dual Action Pull Station MS-710ID(U)
*Unit employs an integral heat sensor; however it must not be used as a regular heat detector. Refer to the
product data sheet for detailed functionality, operation and application.
Manual configuration for the MIX-3200 is NOT PERMITTED. This device must be configured via the AUTO
CONFIG
.

20
Mechanical Installation
5.0 Mechanical Installation
5.1 Installing the Enclosures
Install the FX-350 Series Fire Alarm Panel enclosure as shown below. Mount the enclosure
using the four mounting holes and the screws provided.
Figure 1 Wallbox Dimensions / Mounting the FX-350 – Surface
11"
14.5"
1.5"
14.5"
5.4"
4.5"
20"
Mounting
Hole
Mounting Hole
Mounting
Hole
Mounting Hole
Other manuals for FX-350 Series
4
Table of contents
Other Mircom Security System manuals

Mircom
Mircom QX-mini Operating instructions

Mircom
Mircom FA-300-6DDR User manual

Mircom
Mircom flexnet User manual

Mircom
Mircom FA-101T User manual

Mircom
Mircom Flex-Net Phase II User guide

Mircom
Mircom MS-700MP Series Quick start guide

Mircom
Mircom MS-400AP Series User manual

Mircom
Mircom BL-10B User manual

Mircom
Mircom Fire-Link NMC-100 Series User manual

Mircom
Mircom QX-5000 Series User manual