PQHY-P-T(S)LMU-A1, Y(S)LMU-A1
8
1. SPECIFICATIONS WY-Series
Heat Source Model PQHY-P216TLMU-A1 < For Ground source >
Indoor Model Non-Ducted Ducted
Power source 3-phase 3-wire 208-230 V ±10% 60 Hz
Cooling capacity *1, 2 BTU/h 216,000
(Nominal) kW 63.3
Power input kW 19.23
(208-230) Current input A 59.3-53.6
(Rated) BTU/h 206,000
kW 60.4
Power input kW 17.72 16.10
(208-230) Current input A 54.6-49.4 49.6-44.9
Temp. range of Indoor W.B. 59~75°F (15~24°C)
cooling Inlet water ºF 23~113°F (-5~45°C)
Heating capacity *3, 4 BTU/h 243,000
(Nominal) kW 71.2
Power input kW 13.04
(208-230) Current input A 40.2-36.3
(Rated) BTU/h 232,000
kW 68.0
Power input kW 12.01 12.34
(208-230) Current input A 37.0-33.4 38.0-34.4
Temp. range of Indoor D.B. 59~81°F (15~27°C)
heating Inlet water ºF 23~113°F (-5~45°C)
Indoor unit Total capacity 50~130% of heatsource unit capacity
connectable Model/Quantity P04~P96/2~50
Sound pressure level (measured in anechoic room) dB <A> 58.0
Refrigerant Liquid pipe in. (mm) 5/8 (15.88) Brazed
piping diameter Gas pipe in. (mm) 1-1/8 (28.58) Brazed
Minimum Circuit Ampacity A 69-63
Maximum Overcurrent Protection A 110-110
Circulating water Water flow rate G/h 3,044
G/min (gpm) 50.7
m3/h 11.52
L/min 192
cfm 6.8
Pressure drop psi 6.53
kPa 45
Operating volume G/h 1,585 ~ 3,804
range G/min (gpm) 26.4 ~ 63.4
m3/h 6.0 ~ 14.4
Compressor Type x Quantity Inverter scroll hermetic compressor x 1
Starting method Inverter
Motor output kW 14.5
Case heater kW 0.045 (240 V)
Lubricant MEL32
External finish Galvanized steel sheets
External dimension H x W x D in. 57-1/8 x 34-11/16 x 21-11/16
mm 1,450 x 880 x 550
Protection High pressure protection High pressure sensor, High pressure switch at 4.15 MPa (601 psi)
devices Inverter circuit Over-heat protection, Over-current protection
Compressor Over-heat protection
Refrigerant Type x original charge R410A x 25 lbs + 13 oz (11.7 kg)
Control LEV and HIC circuit
Net weight lbs (kg) 552 (250)
Heat exchanger plate type
Water volume in plate G 2.64
l 10.0
Water pressure Max. psi 290
MPa 2.0
HIC circuit (HIC: Heat Inter-Changer) Copper pipe, tube-in-tube structure
Drawing External KL94C231
Wiring KE94G426
Standard Document Installation Manual
attachment Accessory Details refer to External Drw
Optional parts joint: CMY-Y102SS-G2, CMY-Y102LS-G2, CMY-Y202S-G2, CMY-Y302S-G2
Header: CMY-Y104/108/1010C-G
Remarks Details on foundation work, duct work, insulation work, electrical wiring, power source switch, and other items shall be referred to the Installation
Manual.
Due to continuing improvement, above specifications may be subject to change without notice.
The ambient temperature of the Heat Source Unit needs to be kept below 104°FD.B. (40°CD.B.)
The ambient relative humidity of the Heat Source Unit needs to be kept below 80%.
The Heat Source Unit should not be installed at outdoor.
Be sure to mount a strainer (more than 50 meshes) at the water inlet piping of the unit.
Be sure to provide interlocking for the unit operation and water circuit.
Install the supplied insulation material to the unused drain-socket.
When installing insulation material around both water and refrigerant piping, follow the installation manual.
The cooling tower and the water circuit must be a closed circuit (water is not exposed to the atmosphere).
Add brine to circulating water when a unit is operating at water temperature below 50°F (10°C), and turn DipSW4 (773) ON before power ON.
It is recommended to set the brine concentration to a percentage that will keep the freezing temperature at -15°C or less.
Notes: Unit converter
1.<Standard CITY MULTI indoor unit> Nominal cooling conditions (Test conditions are based on AHRI 1230)
Indoor: 81°FD.B./66°FW.B. (27°CD.B./19°CW.B.), Inlet water temperature: 86°F (30°C), Brine concentration 0%
2.<PWFY-P36/72NMU-E2-AU> Nominal cooling conditions
Inlet water Temp.: 86°F (30°C), Pipe length: 25 ft. (7.6 m), Level difference: 0 ft. (0 m),
Inlet water Temp.: 73°F (23°C), Water flow rate: 1.93 m3/h (8.3 gpm) <P36>/3.86 m3/h (16.6 gpm) <P72>,
Brine concentration 0%
3.<Standard CITY MULTI indoor unit> Nominal heating conditions (Test conditions are based on AHRI 1230)
Indoor: 68°FD.B.(20°CD.B.), Inlet water temperature: 68°F (20°C), Brine concentration 0%
4.<PWFY-P36/72NMU-E2-AU> Nominal heating conditions
Inlet water Temp.: 68°F (20°C), Pipe length: 25 ft. (7.6 m), Level difference: 0 ft. (0 m),
Inlet water Temp.: 86°F (30°C), Water flow rate: 2.15 m3/h (9.2 gpm) <P36>/4.30 m3/h (18.5 gpm) <P72>,
Brine concentration 0%
BTU/h =kW x 3,412
cfm =m3/min x 35.31
lbs =kg/0.4536
*Above specification data is
subject to rounding variation.